PDFWAC 296-307-03935

Inspect and activate your emergency washing facilities.

You must:
• Make sure all plumbed emergency washing facilities are inspected once a year to make sure they function correctly.
Note:
Inspections should include:
 
• Examination of the piping
 
• Making sure that water is available at the appropriate temperature and quality
 
• Activation to check that the valves and other hardware work properly
 
• Checking the water flow rate.
You must:
• Make sure plumbed emergency eyewashes and hand-held drench hoses are activated weekly to check the proper functioning of the valves, hardware, and availability of water
• Make sure all self-contained eyewash equipment and personal eyewash units are inspected and maintained according to manufacturer instructions.
– Inspections to check proper operation must be done once a year
– Sealed personal eyewashes must be replaced after the manufacturer's expiration date.
Note:
Most manufacturers recommend replacing fluid in open self-contained eyewashes every six months. The period for sealed containers is typically two years.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 03-10-068, § 296-307-03935, filed 5/6/03, effective 8/1/03.]