PERMANENT RULES
Date Adopted: November 21, 2003.
Purpose: To adopt chapter 51-51 WAC. Chapter 51-51 WAC adopts and amends the International Residential Code, 2003 Edition, published by the International Code Council.
Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.
Adopted under notice filed as WSR 03-18-077 on August 29, 2003.
Changes Other than Editing from Proposed to Adopted Version: Sections G2415.4 and P2802.1 are not amended; the model code language for those sections is adopted. Section G2439.5.3 is not adopted.
Number of Sections Adopted in Order to Comply with Federal Statute: New 0, Amended 0, Repealed 0; Federal Rules or Standards: New 0, Amended 0, Repealed 0; or Recently Enacted State Statutes: New 18, Amended 0, Repealed 0.
Number of Sections Adopted at Request of a Nongovernmental Entity: New 0, Amended 0, Repealed 0.
Number of Sections Adopted on the Agency's Own Initiative: New 18, Amended 0, Repealed 0.
Number of Sections Adopted in Order to Clarify, Streamline, or Reform Agency Procedures: New 0, Amended 0, Repealed 0.
Number of Sections Adopted Using Negotiated Rule Making:
New 0,
Amended 0,
Repealed 0;
Pilot Rule Making:
New 0,
Amended 0,
Repealed 0;
or Other Alternative Rule Making:
New 18,
Amended 0,
Repealed 0.
Effective Date of Rule: July 1, 2004.
November 21, 2003
Tim Nogler
for Stan Price
Council Chair
OTS-6589.3
STATE BUILDING CODE ADOPTION AND AMENDMENT OF THE 2003 EDITION OF THE INTERNATIONAL RESIDENTIAL CODE
[]
[]
[]
The provisions of this code do not apply to temporary growing structures used solely for the commercial production of horticultural plants including ornamental plants, flowers, vegetables, and fruits. "Temporary growing structure" means a structure that has the sides and roof covered with polyethylene, polyvinyl, or similar flexible synthetic material and is used to provide plants with either frost protection or increased heat retention. A temporary growing structure is not considered a building for purposes of this code.
The provisions of this code do not apply to the construction, alteration, or repair of temporary worker housing except as provided by rule adopted under chapter 70.114A RCW or chapter 37, Laws of 1998 (SB 6168). "Temporary worker housing" means a place, area, or piece of land where sleeping places or housing sites are provided by an employer for his or her employees or by another person, including a temporary worker housing operator, who is providing such accommodations for employees, for temporary, seasonal occupancy, and includes "labor camps" under RCW 70.54.110.
Codes referenced which are not adopted through RCW 19.27.031 or chapter 19.27A RCW shall not apply unless specifically adopted by the authority having jurisdiction.
The standards for liquefied petroleum gas installations shall be NFPA 58 (Liquefied Petroleum Gas Code) and NFPA 54 (National Fuel Gas Code). All other fuel gas installations shall be regulated by the International Mechanical Code and International Fuel Gas Code.
[]
[]
R101.2 Scope. The provisions of the International Residential
Code for One- and Two-Family Dwellings shall apply to the
construction, alteration, movement, enlargement, replacement,
repair, equipment, use and occupancy, location, removal and
demolition of detached one- and two-family dwellings and
multiple single-family dwellings (townhouses) not more than
three stories in height with a separate means of egress and
their accessory structures, including adult family homes,
foster family care homes and family day care homes licensed by
the Washington state department of social and health services.
[]
R102.7.2 Moved buildings. Buildings or structures moved into
or within a jurisdiction shall comply with the provisions of
this code, the International Building Code (chapter 51-50 WAC), the International Mechanical Code (chapter 51-52 WAC),
the International Fire Code (chapter 51-54 WAC), the Uniform
Plumbing Code and Standards (chapters 51-56 and 51-57 WAC),
the Washington State Energy Code (chapter 51-11 WAC) and the
Washington State Ventilation and Indoor Air Quality Code
(chapter 51-13 WAC) for new buildings or structures.
EXCEPTION: | Group R-3 buildings or structures are not required to comply if: |
1. The original occupancy classification is not changed; and | |
2. The original building is not substantially remodeled or rehabilitated. |
[]
ADULT FAMILY HOME means a dwelling in which a person or persons
provide personal care, special care, room and board to more
than one but not more than six adults who are not related by
blood or marriage to the person or persons providing the
services.
CHILD DAY CARE, shall, for the purposes of these regulations,
mean the care of children during any period of a 24 hour day.
CHILD DAY CARE HOME, FAMILY is a child day care facility, licensed
by the state, located in the dwelling of the person or persons
under whose direct care and supervision the child is placed,
for the care of twelve or fewer children, including children
who reside at the home.
UNUSUALLY TIGHT CONSTRUCTION. Construction meeting the following
requirements:
1. Walls exposed to the outside atmosphere having a continuous water vapor retarder with a rating of 1 perm (57 ng/s·m˛·Pa) or less with openings gasketed or sealed;
2. Openable windows and doors meeting the air leakage requirements of the International Energy Conservation Code, Section 502.1.4; and
3. Caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, and at other openings; or
4. Buildings built in compliance with the 1986 or later editions of the Washington State Energy Code chapter 51-11 WAC, Northwest Energy Code, or Super Good Cents weatherization standards or equivalent.
[]
R303.8.1 Definitions. For the purposes of this section only,
the following definitions apply.
DESIGNATED AREAS are those areas designated by a county to be an
urban growth area in chapter 36.70A RCW and those areas
designated by the U.S. Environmental Protection Agency as
being in nonattainment for particulate matter.
SUBSTANTIALLY REMODELED means any alteration or restoration of a
building exceeding 60 percent of the appraised value of such
building within a 12 month period. For the purpose of this
section, the appraised value is the estimated cost to replace
the building and structure in kind, based on current
replacement costs.
R303.8.2 Primary Heating Source. Primary heating sources in
all new and substantially remodeled buildings in designated
areas shall not be dependent upon wood stoves.
R303.8.3 Solid Fuel Burning Devices. No used solid fuel
burning device shall be installed in new or existing buildings
unless such device is United States Environmental Protection
Agency certified or a pellet stove either certified or exempt
from certification by the United States Environmental
Protection Agency.
EXCEPTION: | Antique wood cook stoves and heaters manufactured prior to 1940. |
[]
R311.1 General. Stairways, ramps, exterior exit balconies,
hallways and doors shall comply with this section.
EXCEPTION: | Stairs or ladders within an individual dwelling unit used to gain access to areas of 200 square feet (18.6 m2) or less, and not containing the primary bathroom or kitchen. |
[]
R313.3 Family child day care homes. In family child day care
homes operable smoke alarms shall be located in all sleeping
and napping areas. When the family child day care home has
more than one story, and in family child day care homes with
basements, an operable smoke alarm shall be installed on each
story and in the basement. In family child day care homes
where a story or basement is split into two or more levels,
the smoke alarm shall be installed in the upper level, except
that when the lower level contains a sleeping or napping area,
an operable smoke alarm shall be located on each level. When
sleeping rooms are on an upper level, the smoke alarm shall be
placed at the ceiling of the upper level in close proximity to
the stairway. In family child day care homes where the
ceiling height of a room open to the hallway serving the
bedrooms exceeds that of the hallway by 24 inches or more,
smoke alarms shall be installed in the hallway and the
adjacent room. Smoke alarms shall sound an alarm audible in
all areas of the building.
[]
ADULT FAMILY HOMES
R324.1 General. This section shall apply to all newly constructed adult family homes and all existing single family homes being converted to adult family homes. This section shall not apply to those adult family homes licensed by the state of Washington department of social and health services prior to July 1, 2001.
R324.2 Submittal Standards. In addition to those requirements
in Section 106.1, the submittal shall identify the project as
a Group R-3 Adult Family Home Occupancy. A floor plan shall
be submitted identifying the means of egress and the
components in the means of egress such as stairs, ramps,
platform lifts and elevators. The plans shall indicate the
rooms used for clients and the sleeping room classification of
each room.
R324.3 Sleeping Room Classification. Each sleeping room in an
adult family home shall be classified as:
1. Type S - where the means of egress contains stairs,
elevators or platform lifts.
2. Type NS1 - where one means of egress is at grade level
or a ramp constructed in accordance with R311.6 is provided.
3. Type NS2 - where two means of egress are at grade
level or ramps constructed in accordance with R311.6 are
provided.
R324.4 Types of Locking Devices. All bedroom and bathroom
doors shall be openable from the outside when locked.
Every closet shall be readily openable from the inside.
R324.5 Smoke Alarm Requirements. All adult family homes shall
be equipped with smoke alarms installed as required in Section
R313. Alarms shall be installed in such a manner so that the
fire warning may be audible in all parts of the dwelling upon
activation of a single device.
R324.6 Escape Windows and Doors. Every sleeping room shall be
provided with emergency escape and rescue windows as required
by Section R310.
R324.7 Fire Apparatus Access Roads and Water Supply for Fire
Protection. Adult family homes shall be served by fire
apparatus access roads and water supplies meeting the
requirements of the local jurisdiction.
[]
FAMILY CHILD DAY CARE HOMES
Basements located more than 4 feet below grade level
shall not be used for family child day care homes unless one
of following conditions exist:
1. Stairways from the basement open directly to the
exterior of the building without entering the first floor; or
2. One of the two required means of egress discharges
directly to the exterior from the basement level, and a self
closing door is installed at the top or bottom of the interior
stair leading to the floor above; or
3. One of the two required means of egress is an operable
window or door, approved for emergency escape or rescue, that
opens directly to a public street, public alley, yard or exit
court; or
4. A residential sprinkler system is provided throughout
the entire building in accordance with National Fire
Protection Association Standard 13d.
Floors located more than 4 feet above grade level shall
not be occupied by children in family day care homes.
EXCEPTIONS: | 1. Use of toilet facilities while under supervision of an adult staff person. |
2. Family child day care homes may be allowed on the second story if one of the following conditions exists: | |
2.1 Stairways from the second story open directly to the exterior of the building without entering the first floor; or | |
2.2 One of the two required means of egress discharges directly to the exterior from the second story level, and a self-closing door is installed at the top or bottom of the interior stair leading to the floor below; or | |
2.3 A residential sprinkler system is provided throughout the entire building in accordance with National Fire Protection Association Standard 13d. |
EXCEPTION: | Sleeping or napping rooms having doors leading to two separate means of egress, or a door leading directly to the exterior of the building. |
EXCEPTION: | A fire-resistive separation shall not be required where the food preparation kitchen contains only a domestic cooking range, and the preparation of food does not result in the production of smoke or grease laden vapors. |
[]
R1004.1.1 Emission Standards for Factory-built Fireplaces.
After January 1, 1997, no new or used factory-built fireplace
shall be installed in Washington state unless it is certified
and labeled in accordance with procedures and criteria
specified in the Washington State Building Code Standard 31-2.
To certify an entire fireplace model line, the internal
assembly shall be tested to determine its particulate matter
emission performance. Retesting and recertifying is required
if the design and construction specifications of the fireplace
model line internal assembly change. Testing for
certification shall be performed by a Washington state
department of ecology (DOE) approved and U.S. Environmental
Protection Agency (EPA) accredited laboratory.
R1004.1.2 Emission Standards for Certified Masonry and
Concrete Fireplaces. After January 1, 1997, new certified
masonry or concrete fireplaces installed in Washington state
shall be tested and labeled in accordance with procedures and
criteria specified in the Washington State Building Code
Standard 31-2.
To certify an entire fireplace model line, the internal
assembly shall be tested to determine its particulate matter
emission performance. Retesting and recertifying is required
if the design and construction specifications of the fireplace
model line internal assembly change. Testing for
certification shall be performed by a Washington state
department of ecology (DOE) approved and U.S. Environmental
Protection Agency (EPA) accredited laboratory.
[]
SECTION M2001 -- BOILERS, is not adopted.
SECTION M2002 -- OPERATING AND SAFETY CONTROLS, is not adopted.
SECTION M2003 -- EXPANSION TANKS, is not adopted.
[]
G2401.1 (101.2) Application. This chapter covers those
fuel-gas piping systems, fuel-gas utilization equipment and
related accessories, venting systems and combustion air
configurations most commonly encountered in the construction
of one- and two-family dwellings and structures regulated by
this code.
EXCEPTIONS: | 1. As an alternative to the provisions of this code, fuel-gas piping systems, fuel-gas utilization equipment and related accessories in existing buildings that are undergoing repairs, alterations, changes in occupancy or construction of additions shall be permitted to comply with the provisions of the International Existing Building Code. |
2. The standards for liquefied petroleum gas installations shall be NFPA 58 (Liquefied Petroleum Gas Code) and ANSI Z223.1/NFPA 54 (National Fuel Gas Code). |
The omission from this chapter of any material or method
of installation provided for in the International Fuel Gas
Code shall not be construed as prohibiting the use of such
material or method of installation. Fuel-gas piping systems,
fuel-gas utilization equipment and related accessories,
venting systems and combustion air configurations not
specifically covered in these chapters shall comply with the
applicable provisions of the International Fuel Gas Code.
Gaseous hydrogen systems shall be regulated by Chapter 7
of the International Fuel Gas Code.
This chapter shall not apply to the following:
1. Liquified natural gas (LNG) installations.
2. Temporary LP-gas piping for buildings under
construction or renovation that is not to become part of the
permanent piping system.
3. Except as provided in Section G2412.1.1, gas piping,
meters, gas pressure regulators, and other appurtenances used
by the serving gas supplier in the distribution of gas, other
than undiluted LP-gas.
4. Portable LP-gas equipment of all types that is not
connected to a fixed fuel piping system.
5. Portable fuel cell appliances that are neither
connected to a fixed piping system nor interconnected to a
power grid.
6. Installation of hydrogen gas, LP-gas and compressed
natural gas (CNG) systems on vehicles.
[]
G2415.8 (404.8) Protection against corrosion. Metallic pipe
or tubing exposed to corrosive action, such as soil condition
or moisture, shall be protected in an approved manner, and
cathodically protected in accordance with NACE RP-01-69. Zinc
coatings (galvanizing) shall not be deemed adequate protection
for gas piping underground. Ferrous metal exposed in exterior
locations shall be protected from corrosion in a manner
satisfactory to the code official. Where dissimilar metals
are joined underground, an insulation coupling or fitting
shall be used. Piping shall not be laid in contact with
cinders.
[]
STANDARD TEST METHOD FOR PARTICULATE EMISSIONS FROM FIREPLACES
See Section R1004.1, International Residential Code
Standard is located in International Building Code, Chapter 35
[]