PROPOSED RULES
Original Notice.
Preproposal statement of inquiry was filed as WSR 04-13-076.
Title of Rule and Other Identifying Information: Chapter 51-50 WAC, Adoption and amendment of the 2003 International Building Code, Chapters 4, 11, 12, 14, 16, 17, 21, and 29.
Hearing Location(s): Renton, Holiday Inn Select, One Grady Way South, Renton, WA, on October 15, 2004, at 10:00 a.m.
Date of Intended Adoption: November 12, 2004.
Submit Written Comments to: Stan Price, Chairman, State Building Code Council, P.O. Box 42525, Olympia, WA 98504-2525, e-mail sbcc@cted.wa.gov, fax (360) 586-9383, by October 15, 2004.
Assistance for Persons with Disabilities: Contact Sue Mathers by October 1, 2004, TTY (360) 753-7427 or (360) 725-2967.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: The purpose of the proposed rule is to amend chapter 51-50 WAC that adopts the 2003 International Building Code (IBC). The anticipated effects include providing an improved state building code which will benefit public health, safety and welfare, and to serve Washington state interests.
The amendments include changes that are needed to update to ICC A117.1-2003, the current edition of Accessible and Usable Buildings and Facilities, the accessibility standard referenced by the IBC. These changes will bring the state building code into compliance with updated federal accessibility regulations and continue to provide for the accessibility needs of the state's citizens. This update of the code will maintain state accessibility regulations that are certifiable by the Federal Department of Justice for the benefit of the building design and construction industry.
This proposed rule also includes the following changes to published language in the IBC: Special approved locks in nursing homes are identified; where minimum ceiling heights are required in buildings is clarified; changes are made regarding the application of structural load combinations, special inspections, and how to place anchor bolts supporting masonry veneer; and corrections are made to language specifying plumbing system fixture requirements.
Reasons Supporting Proposal: RCW 19.27.031 and 19.27.074.
Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.
Statute Being Implemented: Chapters 19.27 and 34.05 RCW.
Rule is not necessitated by federal law, federal or state court decision.
Name of Proponent: State Building Code Council, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Al Rhoades, Olympia, Washington 98504-2525, (360) 725-2970; and Enforcement: Local jurisdictions.
No small business economic impact statement has been prepared under chapter 19.85 RCW. This rule provides for maintaining the state building code current with national standards and practice for the benefit of industry and Washington state interests. No economic impact on small business was identified.
A cost-benefit analysis is not required under RCW 34.05.328. This rule clarifies code requirements and does not affect cost.
August 6, 2004
Tim Nogler
for Stan Price
Chairman
OTS-7370.1
AMENDATORY SECTION(Amending WSR 04-01-108, filed 12/17/03,
effective 7/1/04)
WAC 51-50-003
International Building Code.
The 2003
edition of the International Building Code, including
((Sections 101 through 106 of)) Appendix E, published by the
International Code Council is hereby adopted by reference with
the exceptions noted in this chapter of the Washington
Administrative Code.
[Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-003, filed 12/17/03, effective 7/1/04.]
Pursuant to RCW 19.27.040, Chapter 11 and requirements affecting barrier-free access shall not be amended by local governments.
[Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-005, filed 12/17/03, effective 7/1/04.]
407.8 Locks on exit doors. Approved, listed locks without
delayed egress shall be permitted in nursing homes or portions
of nursing homes, provided that:
1. The clinical needs of one or more patients require specialized security measures for their safety.
2. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.
3. The doors unlock upon loss of electrical power controlling the lock or lock mechanism.
4. The lock shall be capable of being deactivated by a signal from a switch located in an approved location.
5. There is a system, such as a keypad and code, in place to inform visitors, staff persons and appropriate residents how they can exit. Instructions for exiting shall be posted within six feet of the door.
[]
1101.2 Design. Buildings and facilities shall be designed and
constructed to be accessible in accordance with this code and
ICC A117.1, except those portions of ICC A117.1 amended by
this section.
1101.2.1 (ICC A117.1 Section 403) Landings for walking
surfaces. The maximum rise for any run is 30 inches (762 mm).
Landings shall be provided at the top and bottom of any run.
Landings shall be level and have a minimum dimension measured
in the direction of travel of not less than 60 inches (1525
mm).
1101.2.2 (ICC A117.1 Section 403.5) Clear width of accessible
route. Clear width of an accessible route shall comply with
ICC A117.1 Table 403.5. For exterior routes of travel, the
minimum clear width shall be 44 inches (1118 mm).
1101.2.3 (ICC A117.1 Section 404.2.9) Door-opening force.
Fire doors shall have the minimum opening force allowable by
the appropriate administrative authority. The maximum force
for pushing open or pulling open doors other than fire doors
shall be as follows:
1. Interior hinged door: 5.0 pounds (22.2 N)
2. Sliding or folding doors: 5.0 pounds (22.2 N)
At exterior doors where environmental conditions require a closing pressure greater than 8.5 pounds, power operated doors shall be used within the accessible route of travel.
These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door in a closed position.
((1101.2.4 (ICC A117.1 Section 502.6) Identification of
accessible parking spaces. Where accessible parking spaces
are required to be identified by signs, the signs shall
include the International Symbol of Accessibility complying
with ICC A117.1 Section 703.7. Such signs shall be 60 inches
(1525 mm) minimum above the floor or ground surface of the
parking space, measured to the bottom of the sign. Van
accessible parking spaces shall have an additional sign
mounted below the International Symbol of Accessibility
identifying the spaces as "Van Accessible."))
1101.2.5 (ICC A117.1 Sections 603.4 and 604.11) Coat hooks,
shelves, dispensers, and other fixtures. Coat hooks provided
((within toilet rooms)) shall accommodate a forward reach or
side reach complying with ICC A117.1 Section 308. Where
provided, shelves shall be installed so that the top of the
shelf is 40 inches (1015 mm) maximum above the floor or
ground. Drying equipment, towel or other dispensers, and
disposal fixtures shall be located 40 inches (1015 mm) maximum
above the floor or ground to any rack, operating controls,
receptacle or dispenser.
1101.2.6 (ICC A117.1 Section 604.6) Flush controls. ((Flush
controls shall be hand operated or automatic.)) Hand operated
flush controls for water closets shall be mounted ((for use
from the wide side of the water closet area and)) not more
than 44 inches (1118 mm) above the floor.
((1101.2.7 (ICC A117.1 Section 604.7) Toilet paper dispensers.
Toilet paper dispensers shall comply with ICC A117.1 Section
309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230
mm) maximum in front of the water closet. The outlet of the
dispenser shall be 15 inches (380 mm) minimum and 48 inches
(1015 mm) maximum above the floor or ground. There shall be a
clearance of 1 1/2 inches (38 mm) minimum below and 12 inches
(305 mm) minimum above the grab bar. Dispensers shall not be
of a type that control delivery, or that do not allow
continuous paper flow. Other dispensers, and disposal
fixtures shall be located 40 inches (1015 mm) maximum above
the floor or ground to any rack, operating controls,
receptacle or dispenser.
1101.2.8 (ICC A117.1 Section 609.2) Grab bars size. Grab bars
shall have an outside diameter of not less than 1 1/4 inch (32
mm) nor more than 1 1/2 inches (38 mm) and shall provide a
clearance of 1 1/2 inches (38 mm) between the grab bar and the
wall.))
1101.2.9 (ICC A117.1 Section ((703.7.2.1)) 703.6.3.1)
International Symbol of Accessibility. Where the
International Symbol of Accessibility is required, it shall be
proportioned complying with ICC A117.1 Figure 703.7.2.1. All
interior and exterior signs depicting the International Symbol
of Accessibility shall be white on a blue background.
((1101.2.10 (ICC A117.1 Section 802.8) Lines of sight. Wheelchair spaces shall be located in places with unobstructed
sight lines.))
1101.2.11 (ICC A117.1 Section 404.3.5) Control switches.
Control switches shall be mounted 36 inches above the floor
and not less than 18 inches nor more than 36 inches
horizontally from the nearest point of travel of the moving
doors.
[Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-1101, filed 12/17/03, effective 7/1/04.]
((1109.2 Toilet and bathing facilities. Toilet rooms and
bathing facilities shall be accessible. Where a floor level
is not required to be connected by an accessible route, the
only toilet rooms or bathing facilities provided within the
facility shall not be located on the inaccessible floor. At
least one of each type of fixture, element, control or
dispenser in each accessible toilet room and bathing facility
shall be accessible.
1109.6 Elevators. Passenger elevators on an accessible route
shall be accessible and comply with ICC A117.1. Elevators
required to be accessible shall be designed and constructed to
comply with chapter 296-96 of the Washington Administrative
Code.
1109.9 Detectable warnings. Passenger transit platform edges
bordering a drop-off and not protected by platform screens or
guards shall have a detectable warning. Curb ramps shall have
detectable warnings. ((Detectable warnings shall extend the
full width and depth of the curb ramp.))
EXCEPTION: | Detectable warnings are not required at bus stops. |
[Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-1109, filed 12/17/03, effective 7/1/04.]
1208.2 Minimum ceiling heights. Occupiable spaces((,)) and
habitable spaces ((and corridors)) shall have a ceiling height
of not less than 7 feet 6 inches (2286 mm). Bathrooms, toilet
rooms, kitchen, storage rooms and laundry rooms shall be
permitted to have a ceiling height of not less than 7 feet
(2134 mm).
EXCEPTIONS: | 1. In one- and two-family dwellings, beams or girders spaced not less than 4 feet (1219 mm) on center and projecting not more than 6 inches (152 mm) below the required ceiling height. |
2. If any room in a building has a sloped ceiling, the prescribed ceiling height for the room is required in one-half the area thereof. Any portion of the room measuring less than 5 feet (1524 mm) from the finished floor to the ceiling shall not be included in any computation of the minimum area thereof. | |
3. Mezzanines constructed in accordance with Section 505.1. | |
4. Residential Group R Occupancies shall be permitted to have a ceiling height of not less than 7 feet (2134 mm). |
EXCEPTION: | Every kitchen in a one- and two-family dwelling shall have not less than 50 square feet (4.64 m2) of gross floor area. |
[Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-1208, filed 12/17/03, effective 7/1/04.]
1210.5 Toilet rooms. This section is not adopted.
(The requirements of this section have been moved to Section 2902.2.1.1)
[]
1405.5.2 Seismic requirements. Anchored masonry veneer located in Seismic Design Category C, D, E, or F shall conform to the requirements of Section 6.2.2.10, except Section 6.2.2.10.2.2, of ACI 530/ASCE 5/TMS 402.
[]
1605.3.1.1 Load reduction. It is permitted to multiply the
combined effect of two or more variable loads by 0.75 and add
to the effect of dead load. The combined load used in design
shall not be less than the sum of the effects of dead load and
any one of the variable loads.
Increases in allowable stresses specified in the appropriate materials section of this code or referenced standard shall not be used with the load combinations of Section 1605.3.1 except that a duration of load increase shall be permitted in accordance with Chapter 23.
[]
1707.1 Special inspections for seismic resistance. Special
inspections itemized in Sections 1707.2 through 1707.8 are
required for the following:
1. The seismic-force-resisting systems in structures assigned to Seismic Design Category C, D, E or F, as determined in Section 1616.
2. Designated seismic systems in structures assigned to Seismic Design Category D, E or F.
3. Architectural, mechanical and electrical components in structures assigned to Seismic Design Category C, D, E or F that are required in Sections 1707.6 and 1707.7.
[]
2107.2.3 ACE 530/ASCE 5/TMS 402, Section 2.1.10.6.1.1, lap
splices. In regions of moment where the design tensile
stresses in the reinforcement are greater than 80 percent of
the allowable steel stress Fs, the lap length determined by
equation (2.9) shall be increased by 50 percent.
[]
2108.2 ACI 530/ASCE 5/TMS 402, Section 3.1.6. Modify Section
3.1.6 as follows:
3.1.6 Headed and bent-bar anchor bolts. All embedded bolts
shall be grouted in place, except that 1/4 inch (6.4 mm)
diameter bolts are permitted to be placed in bed joints that
are at least 1/2 inch (12.7 mm) in thickness.
[]
SECTION 2901 -- PLUMBING CODE.
Plumbing systems shall comply with the Plumbing Code.
SECTION 2902 -- GENERAL.
2902.1 Number of fixtures.
2902.1.1 Requirements. Plumbing fixtures shall be provided in
the minimum number shown in Table 2902.1 and in this chapter.
Where the proposed occupancy is not listed in Table 2902.1,
the building official shall determine fixture requirements
based on the occupancy which most nearly resembles the
intended occupancy.
Plumbing fixtures need not be provided for unoccupied buildings or facilities.
2902.1.2 Private offices. Fixtures only accessible to private
offices shall not be counted to determine compliance with this
section.
2902.1.3 Occupancy load distribution. The occupant load shall
be divided equally between the sexes, unless data approved by
the building official indicates a different distribution of
the sexes.
2902.1.4 Food preparation areas. In food preparation, serving
and related storage areas, additional fixture requirements may
be dictated by health codes.
2902.1.5 Other requirements. For other requirements for
plumbing facilities, see Sections 419.15 and 1210 and Chapter
11.
2902.2 Access to fixtures.
2902.2.1 Location. Plumbing fixtures shall be located in each
building or conveniently in a building adjacent thereto on the
same property.
2902.2.1.1 Toilet rooms. Toilet rooms shall not open directly
into a room used for the preparation of food for service to
the public.
2902.2.2 Multiple tenants. Access to toilets serving multiple
tenants shall be through a common use area and not through an
area controlled by a tenant.
2902.2.3 Multistory buildings. Required fixtures shall not be
located more than one vertical story above or below the area
served.
2902.3 Separate facilities.
2902.3.1 Requirements. Separate toilet facilities shall be
provided for each sex.
EXCEPTION(( |
(( |
(( |
2902.4 Pay facilities. Required facilities shall be free of
charge. Where pay facilities are installed, they shall be in
addition to the minimum required facilities.
2902.5 is not adopted.
2902.6 is not adopted.
SECTION 2903 -- SPECIAL PROVISIONS.
2903.1 Dwelling units. Dwelling units shall be provided with
a kitchen sink.
2903.2 Water closet space requirements. The water closet
stool in all occupancies shall be located in a clear space not
less than 30 inches (762 mm) in width, with a clear space in
front of the stool of not less than 24 inches (610 mm).
2903.3 Water. Each required sink, lavatory, bathtub and
shower stall shall be equipped with hot and cold running water
necessary for its normal operation.
2903.4 Drinking fountains.
2903.4.1 Number. Occupant loads over 30 shall have one
drinking fountain for the first 150 occupants, then one per
each additional 500 occupants.
EXCEPTIONS: | 1. Sporting facilities with concessions serving drinks shall have one drinking fountain for each 1000 occupants. |
2. A drinking fountain need not be provided in a drinking or dining establishment. |
2903.4.3 Penal institutions. Penal institutions shall have
one drinking fountain on each cell block floor and one on each
exercise floor.
2903.4.4 Location. Drinking fountains shall not be located in
toilet rooms.
TYPE OF BUILDING OR OCCUPANCY | WATER CLOSETS (fixtures per person) |
LAVATORIES5 (fixtures per person) |
BATHTUB OR SHOWER (fixtures per person) |
||
MALE3 | FEMALE | MALE | FEMALE | ||
For the occupancies listed below, use 30 square feet (2.79 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Group A | |||||
Conference rooms, dining
rooms, drinking
establishments, exhibit
rooms, gymnasiums,
lounges, stages and
similar uses including
(( |
1:1-25 | 1:1-25 | One per 2 water closets | ||
2:26-75 | 2:26-75 | ||||
3:76-125 | 3:76-125 | ||||
4:126-200 | 4:126-200 | ||||
5:201-300 | 5:201-300 | ||||
6:301-400 | 6:301-400 | ||||
Over 400, add one fixture for each additional 200 males or 150 females | |||||
For the assembly occupancies listed below, use the number of fixed seating or, where no fixed seating is provided, use 15 square feet (1.39 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Assembly places -- Theaters, auditoriums, convention halls, dance floors, lodge rooms, casinos, and such places which have limited time for fixture use (intermissions) |
1:1-100 | One per 25 | 1:1-200 | 1:1-200 | |
2:101-200 | Up to 400 | 2:201-400 | 2:201-400 | ||
3:201-400 | 3:401-750 | 3:401-750 | |||
Over 400, add one fixture for each additional 250 males or 50 females | Over 750, add one fixture for each additional 500 persons | ||||
Assembly places -- Stadiums, arena and other sporting facilities where fixture use is not limited to intermissions |
1:1-100 | One per 50 | 1:1-200 | 1:1-200 | |
2:101-200 | Up to 400 | 2:201-400 | 2:201-400 | ||
3:201-400 | 3:401-750 | 3:401-750 | |||
Over 400, add one fixture for each additional 300 males or 100 females | Over 750, add one fixture for each additional 500 persons | ||||
For the assembly occupancies listed below, use the number of fixed seating or, where no fixed seating is provided, use 30 square feet (2.79 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Worship places | |||||
Principal assembly area | One per 150 | One per 75 | One per 2 water closets | ||
Educational & activity unit | One per 125 | One per 75 | One per 2 water closets | ||
For the occupancies listed below, use 200 square feet (18.58 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Group B and other clerical or administrative employee accessory use |
1:1-15 | 1:1-15 | One per 2 water closets | ||
2:16-35 | 2:16-35 | ||||
3:36-55 | 3:36-55 | ||||
Over 55, add one for each additional 50 persons | |||||
For the occupancies listed below, use 100 square feet ( 9.3 m2) per student for the minimum number of plumbing fixtures. | |||||
Group E | 1:1-15 | 1:1-15 | One per 2 water closets | ||
Schools - for staff use | 2:16-35 | 2:16-35 | |||
All schools | 3:36-55 | 3:36-55 | |||
(One staff per 20 students) | Over 55, add one fixture for each additional 40 persons | ||||
Schools - for student use | 1:1-20 | 1:1-20 | 1:1-20 | 1:1-20 | |
Day care | 2:21-50 | 2:21-50 | 2:21-50 | 2:21-50 | |
Over 50, add one fixture for each additional 50 persons | Over 50, add one fixture for each additional 50 persons | ||||
Elementary | One per 30 | One per 25 | One per 2 water closets | ||
Secondary | One per 40 | One per 30 | One per 2 water closets | ||
For the occupancies listed below, use 50 square feet (4.65 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Education facilities other than Group E | |||||
Others (colleges, universities, adult centers, etc.) | One per 40 | One per 25 | One per 2 water closets | ||
For the occupancies listed below, use 2,000 square feet (185.8 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Group F and Group H | 1:1-10 | 1:1-10 | One per 2 water closets | ||
Workshop, foundries and similar establishments, and hazardous occupancies | 2:11-25 | 2:11-25 | One shower for each 15 persons exposed to excessive heat or to skin contamination with irritating materials | ||
3:26-50 | 3:26-50 | ||||
4:51-75 | 4:51-75 | ||||
5:76-100 | 5:76-100 | ||||
Over 100, add one fixture for each additional 30 persons | |||||
For the occupancies listed below, use the designated application and 200 square feet (18.58 m2) per occupant of the general use area for the minimum number of plumbing fixtures. | |||||
Group I7 | |||||
Hospital waiting rooms | One per room (usable by either sex) | One per room | |||
Hospital general use areas | 1:1-15 | 1:1-15 | One per 2 water closets | ||
2:16-35 | 3:16-35 | ||||
3:36-55 | 3:36-55 | ||||
Over 55, add one fixture for each additional 40 persons | |||||
Hospital patient rooms: | |||||
Single Bed | One adjacent to and directly accessible from | One per toilet room | One per toilet room | ||
Isolation | One adjacent to and directly accessible from | One per toilet room | One per toilet room | ||
Multibed | One per 4 patients | One per 4 patients | One per 8 patients | ||
Long-term | One per 4 patients | One per 4 patients | One per 15 patients | ||
Jails and reformatories | |||||
Cell | One per cell | One per cell | |||
Exercise room | One per exercise room | One per exercise room | |||
Other institutions (on each occupied floor) | One per 25 | One per 25 | One per 2 water closets | One per 8 | |
Group LC | For Group LC Occupancies, the minimum number of plumbing fixtures is specified in Section 419.15. | ||||
For the occupancies listed below, use 200 square feet (18.58 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Group M | |||||
Retail or wholesale stores | 1:1-50 | 1:1-50 | One per 2 water closets | ||
2:51-100 | 2:51-100 | ||||
3:101-400 | 3:101-200 | ||||
4:201-300 | |||||
5:301-400 | |||||
Over 400, add one fixture for each additional 300 males or 150 females | |||||
For Group R Occupancies containing dwelling units or guest rooms, use the table below. For dormitories, use 200 square feet (18.58 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Group R | |||||
Dwelling units | One per dwelling unit | One per dwelling unit | One per dwelling unit | ||
Hotel, motel, and boarding house guest rooms | One per guest room | One per guest room | One per guest room | ||
Dormitories | One per 10 | One per 8 | One per 12 | One per 12 | One per 8 |
Over 10, add one fixture for each additional 25 males and over 8, add one for each additional 20 females | Over 12, add one fixture for each additional 20 males and one for each additional 15 females | For females, add one additional unit per each additional 30. Over 150 persons, add one additional unit per each additional 20 persons | |||
For the occupancies listed below, use 5,000 square feet (464.5 m2) per occupant for the minimum number of plumbing fixtures. | |||||
Group S | 1:1-10 | 1:1-10 | One per 40 occupants of each sex | One shower for each 15 persons exposed to excessive heat or to skin contamination with poisonous, infectious or irritating materials | |
Warehouses | 2:11-25 | 2:11-25 | |||
3:26-50 | 3:26-50 | ||||
4:51-75 | 4:51-75 | ||||
5:76-100 | 5:76-100 | ||||
Over 100, add one for each 30 persons |
1The figures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction thereof. | |
2For occupancies not shown, see Section 2902.1.1. | |
3Where urinals are provided, one water closet less than the number specified may be provided for each urinal installed, except the number of water closets in such cases shall not be reduced to less than one quarter (25%) of the minimum specified. For men's facilities serving 26 or more persons, not less than one urinal shall be provided. | |
4For drinking fountains, see Section 2903.4. | |
5Twenty-four inches (610 mm) of wash sink or 18 inches (457 mm) of a circular basin, when provided with water outlets for such space, shall be considered equivalent to one lavatory. | |
6For when a facility may be usable by either sex, see Section 2902.3.1. | |
7See WAC 246-320 for definitions, other fixtures and equipment for hospitals. |
[Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-2900, filed 12/17/03, effective 7/1/04.]