EXPEDITED RULES
LABOR AND INDUSTRIES
Title of Rule and Other Identifying Information: Chapter 296-304 WAC, Safety standards for ship repairing, shipbuilding
and shipbreaking.
THIS RULE IS BEING PROPOSED UNDER AN EXPEDITED RULE-MAKING PROCESS THAT WILL ELIMINATE THE NEED FOR THE AGENCY TO HOLD PUBLIC HEARINGS, PREPARE A SMALL BUSINESS ECONOMIC IMPACT STATEMENT, OR PROVIDE RESPONSES TO THE CRITERIA FOR A SIGNIFICANT LEGISLATIVE RULE. IF YOU OBJECT TO THIS USE OF THE EXPEDITED RULE-MAKING PROCESS, YOU MUST EXPRESS YOUR OBJECTIONS IN WRITING AND THEY MUST BE SENT TO Rules Coordinator, Department of Labor and Industries, P.O. Box 44001, Olympia, WA 98504-4001 , AND RECEIVED BY July 2, 2007.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: The Occupational Safety and Health Administration (OSHA) promulgated a new fire protection rule for shipyard employment that incorporated by reference, National Fire Protection Association (NFPA) standards. In this proposal, we are replacing the references to those NFPA standards by adding the most recent versions.
These proposed amendments will enhance DOSH's fire protection in our shipyard standard by adding the most current NFPA consensus standards to our chapter. These changes will benefit the safety of employees by requiring employers to comply with the newer standards, which may be even more protective than the older standards.
In addition, we are also making some minor housekeeping changes. For example, we are proposing to move a nonmandatory appendix relating to a model fire safety plan into its own section.
These proposed changes will not result in additional compliance costs.
WAC 296-304-01007 Fire safety plan.
• | In subsection (1), propose to replace "Appendix 1" with "Appendix A." |
• | Move the Appendix 1, model fire safety plan, into its own WAC section and call it "Appendix A." |
• | Create this new section and move the nonmandatory Appendix 1 to this section. |
• | In subsection (3)(b), propose to replace "WAC 296-304-09007" with "chapter 296-842 WAC, Respirators." |
• | In subsection (5)(c)(v), propose to replace "NFPA 1981-1997" with "NFPA 1981-2002." |
• | In subsection (2)(a), propose to replace "NFPA 10-1998" with "NFPA 10-2002." |
• | In subsection (2)(b), propose to replace "NFPA 10-1998" with "NFPA 10-2002" and "NFPA 14-2000" with "NFPA 14-2003." |
• | In subsection (3)(f), propose to replace "NFPA 72-1999" with "NFPA 72-2002." |
• | In subsection (4)(a), propose to replace "NFPA 14-2000" with "NFPA 14-2003." |
• | In subsection (4)(b), propose to replace "NFPA 13-1999" with "NFPA 13-2002" and "NFPA 750-2000" with "NFPA 750-2003." |
• | In subsection (4)(c), propose to replace "NFPA 11-1998 Standard for Low-Expansion Foam" with "NFPA 11-2005 Standard for Low, Medium, and High Expansion Foam Systems." |
• | In subsection (4)(e), propose to replace "NFPA 12-2000" with "NFPA 12-2005," "NFPA 12A-1997" with "NFPA 12A-2004," and "NFPA 2001-2000" with "NFPA 2001-2004." |
• | In the definition of "Coast Guard authorized person" propose to replace "Appendix B" with "Appendix C." |
• | In the note after subsection (2)(d), propose to replace "Appendix A" with "Appendix B." |
• | In the note at the end of this section, propose to replace "Appendix A" with "Appendix B." |
• | Propose to change this Appendix to "Appendix B." |
• | Propose to change this Appendix to "Appendix C." |
Statutory Authority for Adoption: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060.
Statute Being Implemented: Chapter 49.17 RCW.
Rule is not necessitated by federal law, federal or state court decision.
Name of Proponent: Department of labor and industries, governmental.
Name of Agency Personnel Responsible for Drafting: Tracy Spencer, Tumwater, Washington, (360) 902-5530; Implementation and Enforcement: Stephen M. Cant, Tumwater, Washington, (360) 902-5495.
May 1, 2007
Judy Schurke
Director
OTS-9635.2
AMENDATORY SECTION(Amending WSR 07-03-163, filed 1/24/07,
effective 4/1/07)
WAC 296-304-01007
Fire safety plan.
(1) Employer
responsibilities. The employer must develop and implement a
written fire safety plan that covers all the actions that
employers and employees must take to ensure employee safety in
the event of a fire. (See Appendix ((1)) A to this section for a
model fire safety plan.)
(2) Plan elements. The employer must include the following information in the fire safety plan:
(a) Identification of the significant fire hazards;
(b) Procedures for recognizing and reporting unsafe conditions;
(c) Alarm procedures;
(d) Procedures for notifying employees of a fire emergency;
(e) Procedures for notifying fire response organizations of a fire emergency;
(f) Procedures for evacuation;
(g) Procedures to account for all employees after an evacuation; and
(h) Names, job titles, or departments for individuals who can be contacted for further information about the plan.
(3) Reviewing the plan with employees. The employer must review the plan with each employee at the following times:
(a) By March 1, 2006, for employees who are currently working;
(b) Upon initial assignment for new employees; and
(c) When the actions the employee must take under the plan change because of a change in duties or a change in the plan.
(4) Additional employer requirements. The employer also must:
(a) Keep the plan accessible to employees, employee representatives, and WISHA;
(b) Review and update the plan whenever necessary, but at least annually;
(c) Document that affected employees have been informed about the plan as required by this subsection; and
(d) Ensure any outside fire response organization that the employer expects to respond to fires at the employer's worksite has been given a copy of the current plan.
(5) Contract employers. Contract employers in shipyard employment must have a fire safety plan for their employees, and this plan must comply with the host employer's fire safety plan.
1. Purpose.
2. Worksite fire hazards and how to properly control them.
3. Alarm systems and how to report fires.
4. How to evacuate in different emergency situations.
5. Employee awareness.
1. Purpose
The purpose of this fire safety plan is to inform our employees of how we will control and reduce the possibility of fire in the workplace and to specify what equipment employees may use in case of fire.
2. Work site fire hazards and how to properly control them
(a) Measures to contain fires.
(b) Teaching selected employees how to use fire protection equipment.
(c) What to do if you discover a fire.
(d) Potential ignition sources for fires and how to control them.
(e) Types of fire protection equipment and systems that can control a fire.
(f) The level of fire fighting capability present in the facility, vessel, or vessel section.
(g) Description of the personnel responsible for maintaining equipment, alarms, and systems that are installed to prevent or control fire ignition sources, and to control fuel source hazards.
3. Alarm systems and how to report fires
(a) A demonstration of alarm procedures, if more than one type exists.
(b) The worksite emergency alarm system.
(c) Procedures for reporting fires.
4. How to evacuate in different emergency situations
(a) Emergency escape procedures and route assignments.
(b) Procedures to account for all employees after completing an emergency evacuation.
(c) What type of evacuation is needed and what the employee's role is in carrying out the plan.
(d) Helping physically impaired employees.
5. Employee awareness
Names, job titles, or departments of individuals who can be contacted for further information about this plan.))
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 07-03-163, § 296-304-01007, filed 1/24/07, effective 4/1/07; 05-19-086, § 296-304-01007, filed 9/20/05, effective 12/1/05.]
(a) Decide what type of response will be provided and who will provide it; and
(b) Create, maintain, and update a written policy that:
(i) Describes the internal and outside fire response organizations that the employer will use; and
(ii) Defines what evacuation procedures employees must follow, if the employer chooses to require a total or partial evacuation of the worksite at the time of a fire.
(2) Required written policy information.
(a) Internal fire response. If an internal fire response is to be used, the employer must include the following information in the employer's written policy:
(i) The basic structure of the fire response organization;
(ii) The number of trained fire response employees;
(iii) The fire response functions that may need to be carried out;
(iv) The minimum number of fire response employees necessary, the number and types of apparatuses, and a description of the fire suppression operations established by written standard operating procedures for each type of fire response at the employer's facility;
(v) The type, amount, and frequency of training that must be given to fire response employees; and
(vi) The procedures for using protective clothing and equipment.
(b) Outside fire response. If an outside fire response organization is used, the employer must include the following information in the written policy:
(i) The types of fire suppression incidents to which the fire response organization is expected to respond at the employer's facility or worksite;
(ii) The liaisons between the employer and the outside fire response organizations; and
(iii) A plan for fire response functions that:
(A) Addresses procedures for obtaining assistance from the outside fire response organization;
(B) Familiarizes the outside fire response organization with the layout of the employer's facility or worksite, including access routes to controlled areas, and site-specific operations, occupancies, vessels or vessel sections, and hazards; and
(C) Sets forth how hose and coupling connection threads are to be made compatible and includes where the adapter couplings are kept; or
(D) States that the employer will not allow the use of incompatible hose connections.
(c) A combination of internal and outside fire response. If a combination of internal and outside fire response is to be used, the employer must include the following information, in addition to the requirements in (a) and (b) of this subsection, in the written policy:
(i) The basic organizational structure of the combined fire response;
(ii) The number of combined trained fire responders;
(iii) The fire response functions that may need to be carried out;
(iv) The minimum number of fire response employees necessary, the number and types of apparatuses, and a description of the fire suppression operations established by written standard operating procedures for each particular type of fire response at the worksite; and
(v) The type, amount, and frequency of joint training with outside fire response organizations if given to fire response employees.
(d) Employee evacuation. The employer must include the following information in the employer's written policy:
(i) Emergency escape procedures;
(ii) Procedures to be followed by employees who may remain longer at the worksite to perform critical shipyard employment operations during the evacuation;
(iii) Procedures to account for all employees after emergency evacuation is completed;
(iv) The preferred means of reporting fires and other emergencies; and
(v) Names or job titles of the employees or departments to be contacted for further information or explanation of duties.
(e) Rescue and emergency response. The employer must include the following information in the employer's written policy:
(i) A description of the emergency rescue procedures; and
(ii) Names or job titles of the employees who are assigned to perform them.
(3) Medical requirements for shipyard fire response employees. The employer must ensure that:
(a) All fire response employees receive medical examinations to assure that they are physically and medically fit for the duties they are expected to perform;
(b) Fire response employees, who are required to wear
respirators in performing their duties, meet the medical
requirements of ((WAC 296-304-09007)) chapter 296-842 WAC,
Respirators;
(c) Each fire response employee has an annual medical examination; and
(d) The medical records of fire response employees are kept in accordance with chapter 296-802 WAC, Employee medical and exposure records.
(4) Organization of internal fire response functions. The employer must:
(a) Organize fire response functions to ensure enough resources to conduct emergency operations safely;
(b) Establish lines of authority and assign responsibilities to ensure that the components of the internal fire response are accomplished;
(c) Set up an incident management system to coordinate and direct fire response functions, including:
(i) Specific fire emergency responsibilities;
(ii) Accountability for all fire response employees participating in an emergency operation; and
(iii) Resources offered by outside organizations; and
(d) Provide the information required in this subsection to the outside fire response organization to be used.
(5) Personal protective clothing and equipment for fire response employees.
(a) General requirements. The employer must:
(i) Supply to all fire response employees, at no cost, the appropriate personal protective clothing and equipment they may need to perform expected duties; and
(ii) Ensure that fire response employees wear the appropriate personal protective clothing and use the equipment, when necessary, to protect them from hazardous exposures.
(b) Thermal stability and flame resistance. The employer must:
(i) Ensure that each fire response employee exposed to the hazards of flame does not wear clothing that could increase the extent of injury that could be sustained; and
(ii) Prohibit wearing clothing made from acetate, nylon, or polyester, either alone or in blends, unless it can be shown that:
(A) The fabric will withstand the flammability hazard that may be encountered; or
(B) The clothing will be worn in such a way to eliminate the flammability hazard that may be encountered.
(c) Respiratory protection. The employer must:
(i) Provide self-contained breathing apparatus (SCBA) to all fire response employees involved in an emergency operation in an atmosphere that is immediately dangerous to life or health (IDLH), potentially IDLH, or unknown;
(ii) Provide SCBA to fire response employees performing emergency operations during hazardous chemical emergencies that will expose them to known hazardous chemicals in vapor form or to unknown chemicals;
(iii) Provide fire response employees who perform or support emergency operations that will expose them to hazardous chemicals in liquid form either:
(A) SCBA; or
(B) Respiratory protective devices certified by the National Institute for Occupational Safety and Health (NIOSH) under 42 CFR Part 84 as suitable for the specific chemical environment;
(iv) Ensure that additional outside air supplies used in conjunction with SCBA result in positive pressure systems that are certified by NIOSH under 42 CFR Part 84;
(v) Provide only SCBA that meet the requirements of NFPA
1981-((1997)) 2002 Standard on Open-Circuit Self-Contained
Breathing Apparatus for the Fire Service (incorporated by
reference, see WAC 296-304-01003); and
(vi) Ensure that the respiratory protection program and all respiratory protection equipment comply with chapter 296-842 WAC, Respiratory protection.
(d) Interior structural firefighting operations. The employer must:
(i) Supply at no cost to all fire response employees exposed to the hazards of shipyard fire response, a helmet, gloves, footwear, and protective hoods, and either a protective coat and trousers or a protective coverall; and
(ii) Ensure that this equipment meets the applicable recommendations in NFPA 1971-2000 Standard on Protective Ensemble for Structural Fire Fighting (incorporated by reference, see WAC 296-304-01003).
(e) Proximity fire fighting operations. The employer must provide, at no cost, to all fire response employees who are exposed to the hazards of proximity fire fighting, appropriate protective proximity clothing that meets the applicable recommendations in NFPA 1976-2000 Standard on Protective Ensemble for Proximity Fire Fighting (incorporated by reference, see WAC 296-304-01003).
(f) Personal alert safety system (PASS) devices. The employer must:
(i) Provide each fire response employee involved in fire fighting operations with a PASS device; and
(ii) Ensure that each PASS device meets the recommendations in NFPA 1982-1998 Standard on Personal Alert Safety Systems (PASS) (incorporated by reference, see WAC 296-304-01003).
(g) Life safety ropes, body harnesses, and hardware. The employer must ensure that:
(i) All life safety ropes, body harnesses, and hardware used by fire response employees for emergency operations meet the applicable recommendations in NFPA 1983-2001, Standard on Fire Service Life Safety Rope and System Components (incorporated by reference, see WAC 296-304-01003);
(ii) Fire response employees use only Class I body harnesses to attach to ladders and aerial devices; and
(iii) Fire response employees use only Class II and Class III body harnesses for fall arrest and rappelling operations.
(6) Equipment maintenance.
(a) Personal protective equipment. The employer must inspect and maintain personal protective equipment used to protect fire response employees to ensure that it provides the intended protection.
(b) Fire response equipment. The employer must:
(i) Keep fire response equipment in a state of readiness;
(ii) Standardize all fire hose coupling and connection threads throughout the facility and on vessels and vessel sections by providing the same type of hose coupling and connection threads for hoses of the same or similar diameter; and
(iii) Ensure that either all fire hoses and coupling connection threads are the same within a facility or vessel or vessel section as those used by the outside fire response organization, or supply suitable adapter couplings if such an organization is expected to use the fire response equipment within a facility or vessel or vessel section.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 05-19-086, § 296-304-01013, filed 9/20/05, effective 12/1/05.]
(2) Portable fire extinguishers and hose systems.
(a) The employer must select, install, inspect, maintain,
and test all portable fire extinguishers according to NFPA
10-((1998)) 2002 Standard for Portable Fire Extinguishers
(incorporated by reference, see WAC 296-304-01003).
(b) The employer is permitted to use Class II or Class III
hose systems, in accordance with NFPA 10-((1998)) 2002, as
portable fire extinguishers if the employer selects, installs,
inspects, maintains, and tests those systems according to the
specific recommendations in NFPA 14-((2000)) 2003 Standard for
the Installation of Standpipe, Private Hydrant, and Hose Systems
(incorporated by reference, see WAC 296-304-01003).
(3) General requirements for fixed extinguishing systems. The employer must:
(a) Ensure that any fixed extinguishing system component or extinguishing agent is approved by an OSHA nationally recognized testing laboratory for use on the specific hazards the employer expects it to control or extinguish;
(b) Notify employees and take the necessary precautions to ensure employees are safe from fire if for any reason a fire extinguishing system stops working, until the system is working again;
(c) Ensure all repairs to fire extinguishing systems and equipment are done by a qualified technician or mechanic;
(d) Provide and ensure employees use proper personal protective equipment when entering discharge areas in which the atmosphere remains hazardous to employee safety or health, or provide safeguards to prevent employees from entering those areas. See WAC 296-304-02003 for additional requirements applicable to safe entry into spaces containing dangerous atmospheres;
(e) Post hazard warning or caution signs at both the entrance to and inside of areas protected by fixed extinguishing systems that use extinguishing agents in concentrations known to be hazardous to employee safety or health; and
(f) Select, install, inspect, maintain, and test all
automatic fire detection systems and emergency alarms according
to NFPA 72-((1999)) 2002 National Fire Alarm Code (incorporated
by reference, see WAC 296-304-01003).
(4) Fixed extinguishing systems. The employer must select, install, maintain, inspect, and test all fixed systems required by WISHA as follows:
(a) Standpipe and hose systems according to NFPA 14-((2000))
2003 Standard for the Installation of Standpipe, Private Hydrant,
and Hose Systems (incorporated by reference, see WAC 296-304-01003);
(b) Automatic sprinkler systems according to NFPA 25-2002
Standard for the Inspection, Testing, and Maintenance of
Water-based Fire Protection Systems, and either NFPA 13-((1999))
2002 Standard for the Installation of Sprinkler Systems or NFPA
750-((2000)) 2003 Standard on Water Mist Fire Protection Systems
(incorporated by reference, see WAC 296-304-01003);
(c) Fixed extinguishing systems that use water or foam as
the extinguishing agent according to NFPA 15-2001 Standard for
Water Spray Fixed Systems for Fire Protection; NFPA 11-((1998))
2005 Standard for Low, Medium, and High-Expansion Foam Systems;
((and NFPA 11A-1999 Standard for Medium- and High-Expansion Foam
Systems)) (incorporated by reference, see WAC 296-304-01003);
(d) Fixed extinguishing systems using dry chemical as the extinguishing agent according to NFPA 17-2002 Standard for Dry Chemical Extinguishing Systems (incorporated by reference, see WAC 296-304-01003); and
(e) Fixed extinguishing systems using gas as the
extinguishing agent according to NFPA 12-((2000)) 2005 Standard
on Carbon Dioxide Extinguishing Systems; NFPA 12A-((1997)) 2004
Standard on Halon 1301 Fire Extinguishing Systems; and NFPA
2001-((2000)) 2004 Standard on Clean Agent Fire Extinguishing
Systems (incorporated by reference, see WAC 296-304-01003).
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 05-19-086, § 296-304-01017, filed 9/20/05, effective 12/1/05.]
Note: | This appendix is nonmandatory and provides guidance to assist employers in establishing a fire safety plan as required in WAC 296-304-01007. |
1. Purpose.
2. Worksite fire hazards and how to properly control them.
3. Alarm systems and how to report fires.
4. How to evacuate in different emergency situations.
5. Employee awareness.
1. Purpose
The purpose of this fire safety plan is to inform our employees of how we will control and reduce the possibility of fire in the workplace and to specify what equipment employees may use in case of fire.
2. Work site fire hazards and how to properly control them
(a) Measures to contain fires.
(b) Teaching selected employees how to use fire protection equipment.
(c) What to do if you discover a fire.
(d) Potential ignition sources for fires and how to control them.
(e) Types of fire protection equipment and systems that can control a fire.
(f) The level of fire fighting capability present in the facility, vessel, or vessel section.
(g) Description of the personnel responsible for maintaining equipment, alarms, and systems that are installed to prevent or control fire ignition sources, and to control fuel source hazards.
3. Alarm systems and how to report fires
(a) A demonstration of alarm procedures, if more than one type exists.
(b) The worksite emergency alarm system.
(c) Procedures for reporting fires.
4. How to evacuate in different emergency situations
(a) Emergency escape procedures and route assignments.
(b) Procedures to account for all employees after completing an emergency evacuation.
(c) What type of evacuation is needed and what the employee's role is in carrying out the plan.
(d) Helping physically impaired employees.
5. Employee awareness
Names, job titles, or departments of individuals who can be contacted for further information about this plan.
[]
(1) Scope and application. This section applies to work in confined and enclosed spaces and other dangerous atmospheres in shipyard employment, including vessels, vessel sections, and on land-side operations regardless of geographic location.
(2) Definitions applicable to this section:
Adjacent spaces means those spaces bordering a subject space in all directions, including all points of contact, corners, diagonals, decks, tank tops, and bulkheads.
Certified industrial hygienist (CIH) means an industrial hygienist who is certified by the American Board of Industrial Hygiene.
Coast Guard authorized person means an individual who meets
the requirement of WAC 296-304-02015, Appendix ((B)) C, for tank
vessels, for passenger vessels, and for cargo and miscellaneous
vessels.
Dangerous atmosphere means an atmosphere that may expose employees to the risk of death, incapacitation, impairment of ability to self-rescue (i.e., escape unaided from a confined or enclosed space), injury, or acute illness.
Director means the director of the department of labor and industries or his/her designated representative.
Enter with restrictions denotes a space where entry for work is permitted only if engineering controls, personal protective equipment, clothing, and time limitations are as specified by the marine chemist, certified industrial hygienist, or the shipyard competent person.
Entry means the action by which a person passes through an opening into a space. Entry includes ensuing work activities in that space and is considered to have occurred as soon as any part of the entrant's body breaks the plane of an opening into the space.
Hot work means any activity involving riveting, welding, burning, the use of powder-actuated tools or similar fire-producing operations. Grinding, drilling, abrasive blasting, or similar spark-producing operations are also considered hot work except when such operations are isolated physically from any atmosphere containing more than 10 percent of the lower explosive limit of a flammable or combustible substance.
Immediately dangerous to life or health (IDLH) means an atmosphere that poses an immediate threat to life or that is likely to result in acute or immediate severe health effects.
Inert or inerted atmosphere means an atmospheric condition where:
(a) The oxygen content of the atmosphere in the space is maintained at a level equal to or less than 8.0 percent by volume or at a level at or below 50 percent of the amount required to support combustion, whichever is less; or
(b) The space is flooded with water and the vapor concentration of flammable or combustible materials in the free space atmosphere above the water line is less than 10 percent of the lower explosive limit for the flammable or combustible material.
Labeled means identified with a sign, placard, or other form of written communication, including pictograms, that provides information on the status or condition of the work space to which it is attached.
Lower explosive limit (LEL) means the minimum concentration of vapor in air below which propagation of a flame does not occur in the presence of an ignition source.
Marine chemist means an individual who possesses a current marine chemist certificate issued by the National Fire Protection Association (NFPA).
NFPA means National Fire Protection Association.
Nationally Recognized Testing Laboratory (NRTL) means an organization recognized by OSHA, in accordance with Appendix A of 29 CFR 1910.7, which tests for safety and lists or labels or accepts equipment and materials that meet all the criteria found in Section 1910.7 (b)(1) through (b)(4)(ii).
Not safe for hot work denotes a space where hot work may not be performed because the conditions do not meet the criteria for "safe for hot work."
Not safe for workers denotes a space where an employee may not enter because the conditions do not meet the criteria for "safe for workers."
Oxygen-deficient atmosphere means an atmosphere having an oxygen concentration of less than 19.5 percent by volume.
Oxygen-enriched atmosphere means an atmosphere that contains 22.0 percent or more oxygen by volume.
Safe for hot work denotes a space that meets all of the following criteria:
(a) The oxygen content of the atmosphere does not exceed 22.0 percent by volume;
(b) The concentration of flammable vapors in the atmosphere is less than 10 percent of the lower explosive limit;
(c) The residues or materials in the space are not capable of producing a higher concentration than permitted in (a) or (b) of the above, under existing atmospheric conditions in the presence of hot work and while maintained as directed by the marine chemist or competent person; and
(d) All adjacent spaces have been cleaned, or inerted, or treated sufficiently to prevent the spread of fire.
Safe for workers denotes a space that meets the following criteria:
(a) The oxygen content of the atmosphere is at least 19.5 percent and below 22.0 percent by volume;
(b) The concentration of flammable vapors is below 10 percent of the lower explosive limit (LEL);
(c) Any toxic materials in the atmosphere associated with cargo, fuel, tank coatings, or inerting media are within permissible concentrations at the time of the inspection; and
(d) Any residues or materials associated with the work authorized by the marine chemist, certified industrial hygienist, or competent person will not produce uncontrolled release of toxic materials under existing atmospheric conditions while maintained as directed.
Space means an area on a vessel or vessel section or within a shipyard such as, but not limited to: Cargo tanks or holds; pump or engine rooms; storage lockers; tanks containing flammable or combustible liquids, gases, or solids; rooms within buildings; crawl spaces; tunnels; or accessways. The atmosphere within a space is the entire area within its bounds.
Upper explosive limit (UEL) means the maximum concentration of flammable vapor in air above which propagation of flame does not occur on contact with a source of ignition.
Vessel section means a subassembly, module, or other component of a vessel being built, repaired, or broken.
Visual inspection means the physical survey of the space, its surroundings and contents to identify hazards such as, but not limited to, restricted accessibility, residues, unguarded machinery, and piping or electrical systems.
[Statutory Authority: Chapter 49.17 RCW. 95-04-006, § 296-304-020, filed 1/18/95, effective 3/10/95; 93-04-111 (Order 92-15), § 296-304-020, filed 2/3/93, effective 3/15/93; Order 74-25, § 296-304-020, filed 5/7/74.]
(a) Spaces containing or having last contained bulk quantities of combustible or flammable liquids or gases; and
(b) Spaces containing or having last contained bulk quantities of liquids, gases or solids that are toxic, corrosive or irritating.
(2) Requirements for performing cleaning or cold work.
(a) Liquid residues of hazardous materials shall be removed from work spaces as thoroughly as practicable before employees start cleaning operations or cold work in a space. Special care shall be taken to prevent the spilling or the draining of these materials into the water surrounding the vessel, or for shore-side operations, onto the surrounding work area.
(b) Testing shall be conducted by a competent person to determine the concentration of flammable, combustible, toxic, corrosive, or irritant vapors within the space prior to the beginning of cleaning or cold work.
(c) Continuous ventilation shall be provided at volumes and flow rates sufficient to ensure that the concentration(s) of:
(i) Flammable vapor is maintained below 10 percent of the lower explosive limit; and
Note to (2)(c)(i): | Spaces containing highly volatile residues may require additional ventilation to keep the concentration of flammable vapors below 10 percent of the lower explosive limit and within the permissible exposure limit. |
(d) Testing shall be conducted by the competent person as often as necessary during cleaning or cold work to assure that air concentrations are below 10 percent of the lower explosive limit and within the PELs and below IDLH levels. Factors such as, but not limited to, temperature, volatility of the residues and other existing conditions in and about the spaces are to be considered in determining the frequency of testing necessary to assure a safe atmosphere.
Note to (2)(d): | See WAC 296-304-02013--Appendix (( |
(f) An employee may not enter a confined or enclosed space or other dangerous atmosphere if the concentration of flammable or combustible vapors in work spaces exceeds 10 percent of the lower explosive limit.
Exception: An employee may enter for emergency rescue or for a short duration for installation of ventilation equipment provided:
(i) No ignition sources are present;
(ii) The atmosphere in the space is monitored continuously;
(iii) The atmosphere in the space is maintained above the upper explosive limit; and
(iv) Respiratory protection, personal protective equipment, and clothing are provided in accordance with WAC 206-304-090 through 296-304-09007.
Note to (2)(f): | Other provisions for work in IDLH and other dangerous atmospheres are located in WAC 296-304-090 through 296-304-09007. |
(h) If the tests required in (g) of this subsection indicate that concentrations of exhaust vapors that are hazardous to employees are accumulating, all work in the contaminated area shall be stopped until the vapors have dissipated or been removed.
(i) Only explosion-proof, self-contained portable lamps, or other electric equipment approved by a National Recognized Testing Laboratory (NRTL) for the hazardous location shall be used in spaces described in subsection (1) of this section, until such spaces have been certified as "safe for workers."
Note to (2)(i): | Battery-fed, portable lamps or other electric equipment bearing the approval of a NRTL for the class, and division of the location in which they are used are deemed to meet the requirements of (i) of this subsection. |
(i) At the entrance to those spaces;
(ii) In adjacent spaces; and
(iii) In the open area adjacent to those spaces.
(k) All air moving equipment and its component parts, including duct work, capable of generating a static electric discharge of sufficient energy to create a source of ignition, shall be bonded electrically to the structure of a vessel or vessel section or, in the case of land-side spaces, grounded to prevent an electric discharge in the space.
(l) Fans shall have nonsparking blades, and portable air ducts shall be of nonsparking materials.
Note to (2): | See WAC 296-304-02003(3) and applicable requirements of chapter 296-62 WAC, general occupational health standards, for other provisions affecting cleaning and cold work. |
[Statutory Authority: Chapter 49.17 RCW. 95-04-006, § 296-304-02005, filed 1/18/95, effective 3/10/95; Order 74-25, § 296-304-02005, filed 5/7/74.]
(a) The employer shall ensure that hot work is not performed in or on any of the following confined and enclosed spaces and other dangerous atmospheres, boundaries of spaces or pipelines until the work area has been tested and certified by a marine chemist or a U.S. Coast Guard authorized person as "safe for hot work":
(i) Within, on, or immediately adjacent to spaces that contain or have contained combustible or flammable liquids or gases.
(ii) Within, on, or immediately adjacent to fuel tanks that contain or have last contained fuel; and
(iii) On pipelines, heating coils, pump fittings or other accessories connected to spaces that contain or have last contained fuel.
(iv) Exception: On dry cargo, miscellaneous and passenger vessels and in the landside operations within spaces which meet the standards for oxygen, flammability and toxicity in WAC 296-304-02003, but are adjacent to spaces containing flammable gases or liquids, as long as the gases or liquids with a flash point below 150 deg. F (65.6 deg. C) when the distance between such spaces and the work is 25 feet (7.62 m) or greater.
(2) Hot work requiring testing by a competent person. (a) Hot work is not permitted in or on the following spaces
or adjacent spaces or other dangerous atmospheres until they have
been tested by a competent person and determined to contain no
concentrations of flammable vapors equal to or greater than 10
percent of the lower explosive limit: (i) Dry cargo holds; (ii) The bilges; (iii) The engine room and boiler spaces for which a marine
chemist or a Coast Guard authorized person certificate is not
required under subsection (1)(a)(i) of this section; and (iv) Vessels and vessel sections for which a marine chemist
or Coast Guard authorized person certificate is not required
under subsection (1)(a)(i) of this section; and (v) Land-side confined and enclosed spaces or other
dangerous atmospheres not covered by subsection (1)(a) of this
section. (b) If the concentration of flammable vapors or gases is
equal to or greater than 10 percent of the lower explosive limit
in the space or an adjacent space where the hot work is to be
done, then the space shall be labeled "not safe for hot work" and
ventilation shall be provided at volumes and flow rates
sufficient to ensure that the concentration of flammable vapors
or gases is below 10 percent by volume of the lower explosive
limit. The warning label may be removed when the concentration
of flammable vapors and gases are below 10 percent of the lower
explosive limit.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and
49.17.060. 03-04-099, § 296-304-02007, filed 2/4/03, effective
8/1/03. Statutory Authority: RCW 49.17.010, [49.17].050 and
[49.17].060. 95-22-015, § 296-304-02007, filed 10/20/95,
effective 1/16/96. Statutory Authority: Chapter 49.17 RCW. 95-04-006, § 296-304-02007, filed 1/18/95, effective 3/10/95;
Order 76-7, § 296-304-02007, filed 3/1/76; Order 74-25, §
296-304-02007, filed 5/7/74.] WAC 296-304-020 through 296-304-02011. These standards are
minimum safety standards for entering and working safely in
vessel tanks and compartments. WAC 296-304-020(2) Definition of "Hot work." There are
several instances in which circumstances do not necessitate that
grinding, drilling, abrasive blasting be regarded as hot work. Some examples are: (1) Abrasive blasting of the hull for paint preparation does
not necessitate pumping and cleaning the tanks of a vessel. (2) Prior to hot work on any hollow structure, the void
space should be tested and appropriate precautions taken. WAC 296-304-020(2) Definition of "Lower explosive limit."
The terms lower flammable limit (LFL) and lower explosive limit
(LEL) are used interchangeably in fire science literature. WAC 296-304-020(2) Definition of "Upper explosive limit."
The terms upper flammable limit (UFL) and upper explosive limit
(UEL) are used interchangeably in fire science literature. WAC 296-304-02003(1) After a tank has been properly washed
and ventilated, the tank should contain 20.8 percent oxygen by
volume. This is the same amount found in our normal atmosphere
at sea level. However, it is possible that the oxygen content
will be lower. When this is the case, the reasons for this
deficiency should be determined and corrective action taken. An oxygen content of 19.5 percent can support life and is
adequate for entry. However, any oxygen level less than 20.8
percent and greater than 19.5 percent level should also alert the
competent person to look for the causes of the oxygen deficiency
and to correct them prior to entry. WAC 296-304-02003(2) Flammable atmospheres. Atmospheres
with a concentration of flammable vapors at or above 10 percent
of the lower explosive limit (LEL) are considered hazardous when
located in confined spaces. However, atmospheres with flammable
vapors below 10 percent of the LEL are not necessarily safe. Such atmospheres are too lean to burn. Nevertheless, when a
space contains or produces measurable flammable vapors below the
10 percent LEL, it might indicate that flammable vapors are being
released or introduced into the space and could present a hazard
in time. Therefore, the cause of the vapors should be
investigated and, if possible, eliminated prior to entry. Some situations that have produced measurable concentrations
of flammable vapors that could exceed 10 percent of the LEL in
time are: (1) Pipelines that should have been blanked or disconnected
have opened, allowing product into the space. (2) The vessel may have shifted, allowing product not
previously cleaned and removed during washing to move into other
areas of the vessel. (3) Residues may be producing the atmosphere by releasing
flammable vapor. WAC 296-304-02003(2) Flammable atmospheres that are toxic. An atmosphere with a measurable concentration of a flammable
substance below 10 percent of the LEL may be above the WISHA
permissible exposure limit for that substance. In that case,
refer to WAC 296-304-02003 (3)(b), (c), and (d). WAC 296-304-02005 (2)(d), 296-304-02009(3), and
296-304-02009(5). The frequency with which a tank is monitored
to determine if atmospheric conditions are being maintained is a
function of several factors that are discussed below: (1) Temperature. Higher temperatures will cause a
combustible or flammable liquid to vaporize at a faster rate than
lower temperatures. This is important since hotter days may
cause tank residues to produce more vapors and that may result in
the vapors exceeding 10 percent of the LEL or an overexposure to
toxic contaminants. (2) Work in the tank. Any activity in the tank could change
the atmospheric conditions in that tank. Oxygen from a leaking
oxyfuel hose or torch could result in an oxygen-enriched
atmosphere that would more easily propagate a flame. Some
welding operations use inert gas, and leaks can result in an
oxygen-deficient atmosphere. Manual tank cleaning with high
pressure spray devices can stir up residues and result in
exposures to toxic contaminants. Simple cleaning or mucking out,
where employees walk through and shovel residues and sludge, can
create a change in atmospheric conditions. (3) Period of time elapsed. If a period of time has elapsed
since a marine chemist or Coast Guard authorized person has
certified a tank as safe, the atmospheric condition should be
rechecked by the competent person prior to entry and starting
work. (4) Unattended tanks or spaces. When a tank or space has
been tested and declared safe, then subsequently left unattended
for a period of time, it should be retested prior to entry and
starting work. For example, when barges are left unattended at
night, unidentified products from another barge are sometimes
dumped into their empty tanks. Since this would result in a
changed atmosphere, the tanks should be retested prior to entry
and starting work. (5) Work break. When workers take a break or leave at the
end of the shift, equipment sometimes is inadvertently left in
the tanks. At lunch or work breaks and at the end of the shift
are the times when it is most likely someone will leave a burning
or cutting torch in the tank, perhaps turned on and leaking
oxygen or an inert gas. Since the former can produce an
oxygen-enriched atmosphere, and the latter an oxygen-deficient
atmosphere, tanks should be checked for equipment left behind,
and atmosphere, monitored if necessary prior to reentering and
resuming work. In an oxygen-enriched atmosphere, the flammable
range is severely broadened. This means that an oxygen-enriched
atmosphere can promote very rapid burning. (6) Ballasting or trimming. Changing the position of the
ballast, or trimming or in any way moving the vessel so as to
expose cargo that had been previously trapped, can produce a
change in the atmosphere of the tank. The atmosphere should be
retested after any such move and prior to entry or work. WAC 296-304-02007 (1) and (2) hot work. This is a reminder
that other sections of the WISHA shipyard safety and health
standards in chapter 296-304 WAC should be reviewed prior to
starting any hot work. Most notably, WAC 296-304-040 through
296-304-04013, welding, cutting and heating, places additional
restrictions on hot work: The requirements of WAC 296-304-04001
and 296-304-04005 must be met before hot work is begun on any
metal that is toxic or is covered by a preservative coating
respectively; the requirements of WAC 296-304-04007 must be met
before welding, cutting, or heating is begun on any structural
voids. WAC 296-304-02003 (1)(b). During hot work, more than 20.8
percent oxygen by volume can be unsafe since it extends the
normal flammable range. The standard permits the oxygen level to
reach 22.0 percent by volume in order to account for instrument
error. However, the cause of excess oxygen should be
investigated and the source removed. WAC 296-304-02011(2). If the entire vessel has been found
to be in the same condition, then employers shall be considered
to be in compliance with this requirement when signs using
appropriate warning language in accordance with WAC 296-304-02011(1) are posted at the gangway and at all other means
of access to the vessel.
[Statutory Authority: Chapter 49.17 RCW. 95-04-006, §
296-304-02013, filed 1/18/95, effective 3/10/95.] (1) Title 46 CFR 35.01-1 (a) through (c) covering hot work
on tank vessels reads as follows: (a) The provisions of "Standard for the Control of Gas
Hazards on Vessels to be Repaired," NFPA No. 306, published by
National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02269, shall be used as a guide in conducting the
inspections and issuance of certificates required by this
chapter. (b) Until an inspection has been made to determine that such
operation can be undertaken with safety, no alterations, repairs,
or other such operations involving riveting, welding, burning, or
like fire-producing actions shall be made: (i) Within or on the boundaries of cargo tanks that have
been used to carry flammable or combustible liquid or chemicals
in bulk, or within spaces adjacent to such cargo tanks; or (ii) Within or on the boundaries of fuel tanks; or (iii) To pipe lines, heating coils, pumps, fittings, or
other appurtenances connected to such cargo or fuel tanks. (c) Such inspections shall be made and evidenced as follows: (i) In ports or places in the United States or its
territories and possessions, the inspection shall be made by a
marine chemist certificated by the National Fire Protection
Association; however, if the services of such certified marine
chemists are not reasonably available, the Officer in Charge,
Marine Inspection, upon the recommendation of the vessel owner
and his/her contractor or their representative, shall select a
person who, in the case of an individual vessel, shall be
authorized to make such inspection. (ii) If the inspection indicates that such operations can be
undertaken with safety, a certificate setting forth the fact in
writing and qualified as may be required, shall be issued by the
certified marine chemist or the authorized person before the work
is started. (iii) Such qualifications shall include any requirements as
may be deemed necessary to maintain, insofar as can reasonably be
done, the safe conditions in the spaces certified, throughout the
operation and shall include such additional tests and
certifications as considered required. (iv) Such qualifications and requirements shall include
precautions necessary to eliminate or minimize hazards that may
be present from protective coatings or residues from cargoes. (2) Title 46 CFR 71.60 (c)(1) covering hot work on passenger
vessels reads as follows: (a) The provisions of "Standard for the Control of Gas
Hazards on Vessels to be Repaired," NFPA No. 306, published by
National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02269, shall be used as a guide in conducting the
inspections and issuance of certificates required by this
chapter. (b) Until an inspection has been made to determine that such
operation can be undertaken with safety, no alterations, repairs,
or other such operations involving riveting, welding, burning, or
like fire-producing actions shall be made: (i) Within or on the boundaries of cargo tanks which have
been used to carry flammable or combustible liquid or chemicals
in bulk, or within spaces adjacent to such cargo tanks; or (ii) Within or on the boundaries of fuel tanks; or (iii) To pipe lines, heating coils, pumps, fittings, or
other appurtenances connected to such cargo or fuel tanks. (c) Such inspections shall be made and evidenced as follows: (i) In ports or places in the United States or its
territories and possessions the inspection shall be made by a
marine chemist certificated by the National Fire Protection
Association; however, if the services of such certified marine
chemist are not reasonably available, the Officer in Charge,
Marine Inspection, upon the recommendation of the vessel owner
and his/her contractor or their representative, shall select a
person who, in the case of an individual vessel, shall be
authorized to make such inspection. (ii) If the inspection indicated that such operations can be
undertaken with safety, a certificate setting forth the fact in
writing and qualified as may be required, shall be issued by the
certified marine chemist or the authorized person before the work
is started. (iii) Such qualifications shall include any requirements as
may be deemed necessary to maintain, insofar as can reasonably be
done, the safe conditions in the spaces certified throughout the
operation and shall include such additional tests and
certifications as considered required. (iv) Such qualifications and requirements shall include
precautions necessary to eliminate or minimize hazards that may
be present from protective coatings or residues from cargoes. (3) Title 46 CFR 91.50-1 (c)(1) covering hot work on cargo
and miscellaneous vessels as follows: (a) The provisions of "Standard for the Control of Gas
Hazards on Vessels to be Repaired," NFPA No. 306, published by
National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02269, shall be used as a guide in conducting the
inspections and issuance of certificates required by this
chapter. (b) Until an inspection has been made to determine that such
operation can be undertaken with safety, no alterations, repairs,
or other such operations involving riveting, welding, burning, or
like fire-producing actions shall be made: (i) Within or on the boundaries of cargo tanks which have
been used to carry flammable or combustible liquid or chemicals
in bulk, or within spaces adjacent to such cargo tanks; or, (ii) Within or on the boundaries of fuel tanks; or, (iii) To pipe lines, heating coils, pumps, fittings, or
other appurtenances connected to such cargo or fuel tanks. (c) Such inspections shall be made and evidenced as follows: (i) In ports or places in the United States or its
territories and possessions the inspection shall be made by a
marine chemist certificated by the National Fire Protection
Association; however, if the services of such certified marine
chemist are not reasonably available, the Officer in Charge,
Marine Inspection, upon the recommendation of the vessel owner
and his/her contractor or their representative, shall select a
person who, in the case of an individual vessel, shall be
authorized to make such inspection. (ii) If the inspection indicated that such operations can be
undertaken with safety, a certificate setting forth the fact in
writing and qualified as may be required, shall be issued by the
certified marine chemist or the authorized person before the work
is started. (iii) Such qualifications shall include any requirements as
may be deemed necessary to maintain, insofar as can reasonably be
done, the safe conditions in the spaces certified throughout the
operation and shall include such additional tests and
certifications as considered required. (iv) Such qualifications and requirements shall include
precautions necessary to eliminate or minimize hazards that may
be present from protective coatings or residues from cargoes.
[Statutory Authority: Chapter 49.17 RCW. 95-04-006, §
296-304-02015, filed 1/18/95, effective 3/10/95.]
Note:
For flammable liquids with flash points above 150 deg. F (65.6 deg. C), see subsection (2) of this section.
Note to (1)(a):
The criteria for "safe for hot work" is located in the definition section, WAC 296-304-020(2).
(b) The certificate issued by the marine chemist or Coast
Guard authorized person shall be posted in the immediate vicinity
of the affected operations while they are in progress and kept on
file for a period of at least three months from the date of the
completion of the operation for which the certificate was
generated.
Note to WAC 296-304-02007:
See WAC 296-304-02013--Appendix ((
A)) B,
for additional information relevant to performing
hot work safely.
AMENDATORY SECTION(Amending WSR 95-04-006, filed 1/18/95,
effective 3/10/95)
WAC 296-304-02013
Appendix ((A)) B -- Compliance assistance
guidelines for confined and enclosed spaces and other dangerous
atmospheres.
This appendix is a nonmandatory set of guidelines
provided to assist employers in complying with the requirements
of WAC 296-304-020 through 296-304-02011. This appendix neither
creates additional obligations nor detracts from obligations
otherwise contained in this chapter. It is intended to provide
explanatory information and educational material to employers and
employees to foster understanding of, and compliance with, this
chapter.
AMENDATORY SECTION(Amending WSR 95-04-006, filed 1/18/95,
effective 3/10/95)
WAC 296-304-02015
Appendix ((B)) C -- Confined and enclosed
spaces and other dangerous atmospheres in shipyard employment.
This appendix provides a complete reprint of U.S. Coast Guard
regulations as of October 1, 1993 referenced in WAC 296-304-020
for purposes of determining who is a Coast Guard authorized
person.
© Washington State Code Reviser's Office