EXPEDITED RULES
Title of Rule and Other Identifying Information: Chapter 51-54 WAC, State Building Code adoption and amendment of the
2009 Edition of the International Fire Code.
THIS RULE IS BEING PROPOSED UNDER AN EXPEDITED RULE-MAKING PROCESS THAT WILL ELIMINATE THE NEED FOR THE AGENCY TO HOLD PUBLIC HEARINGS, PREPARE A SMALL BUSINESS ECONOMIC IMPACT STATEMENT, OR PROVIDE RESPONSES TO THE CRITERIA FOR A SIGNIFICANT LEGISLATIVE RULE. IF YOU OBJECT TO THIS USE OF THE EXPEDITED RULE-MAKING PROCESS, YOU MUST EXPRESS YOUR OBJECTIONS IN WRITING AND THEY MUST BE SENT TO Tim Nogler, State Building Code Council, 128 10th Avenue S.W., Olympia, WA 98504-2525 , AND RECEIVED BY October 5, 2010.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: To correct numerical citations.
WAC 51-54-0500, adds section title and correct[s] numerical error.
WAC 51-54-0907, corrects numerical citation.
WAC 51-54-1000, eliminates duplicate language contained in base code and renumbers several sections; reincorporates several sections incorrectly filed as separate WAC sections.
Repeals the following WAC sections (reincorporates provisions into WAC 51-54-1000), WAC 51-54-1007, 51-54-1008, 51-54-1009, 51-54-1010, 51-54-1014, 51-54-1015, 51-54-1017, 51-54-1018, and 51-54-1019.
Reasons Supporting Proposal: Full public hearings were held on these issues during the rule adoption process; these editorial changes will clarify the rules, resulting in consistent enforcement.
Statutory Authority for Adoption: Chapter 19.27 RCW.
Statute Being Implemented: Chapter 19.27A RCW.
Rule is not necessitated by federal law, federal or state court decision.
Name of Proponent: State building code council, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Joanne T. McCaughan, 128 10th Avenue S.W., Olympia, WA 98504-1014, (360) 725-2970; and Enforcement: Local jurisdictions.
Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: These changes will provide consistent enforcement and reduce confusion at the local level.
July 19, 2010
John C. Cochran
Chair
OTS-3262.3
AMENDATORY SECTION(Amending WSR 10-03-100, filed 1/20/10,
effective 7/1/10)
WAC 51-54-0500
Chapter 5 -- Fire service features.
SECTION 503 FIRE APPARATUS ACCESS ROADS.
503.1 Where required. Fire apparatus access roads shall be
provided and maintained in accordance with locally adopted
street, road, and access standards.
503.1.1 Buildings and facilities, is not adopted.
503.1.2 Additional access, is not adopted.
503.1.3 High-piled storage, is not adopted.
503.2 Specifications. This section is not adopted.
503.3 Marking. This section is not adopted.
503.4 Obstruction of fire apparatus access roads. This
section is not adopted.
SECTION 507 FIRE PROTECTION WATER SUPPLIES
507.3 Fire flow. Fire flow requirements for buildings or
portions of buildings and facilities shall be determined by an
approved method.
EXCEPTION: | Fire flow is not required for structures under 500 square feet with a B, U or R-1 occupancy where structures are at least 30 feet from any other structure and are used only for recreation. |
SECTION 508 FIRE COMMAND CENTER
508.1.2 Separation. The fire command center shall be
separated from the remainder of the building by not less than
a 2-hour fire barrier constructed in accordance with Section
707 of the International Building Code or horizontal assembly
constructed in accordance with Section 712 of the
International Building Code, or both.
[Statutory Authority: RCW 19.27.031 and 19.27.074. 10-03-100, § 51-54-0500, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.031, 19.27.074, and chapters 19.27 and 34.05 RCW. 07-01-093, § 51-54-0500, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-105, § 51-54-0500, filed 12/17/03, effective 7/1/04.]
902.1 Definitions.
ALERT SIGNAL. See Section 402.1.
ALERTING SYSTEM. See Section 402.1.
PORTABLE SCHOOL CLASSROOM. A structure, transportable in one or
more sections, which requires a chassis to be transported, and
is designed to be used as an educational space with or without
a permanent foundation. The structure shall be trailerable
and capable of being demounted and relocated to other
locations as needs arise.
903.2.3 Group E. An automatic sprinkler system shall be
provided for Group E Occupancies.
EXCEPTIONS: | 1. Portable school classrooms, provided aggregate area of any cluster or portion of a cluster of portable school classrooms does not exceed 5,000 square feet (1465 m2); and clusters of portable school classrooms shall be separated as required by the building code. |
2. Group E Occupancies with an occupant load of 50 or less, calculated in accordance with Table 1004.1.1. |
1. A Group M fire area exceeds 12,000 square feet (1115 m2).
2. A group M fire area is located more than three stories above grade plane.
3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2).
4. Where a Group M occupancy that is used for the display and sale of upholstered furniture or mattresses exceeds 5000 square feet (464 m2).
903.2.8 Group R. An automatic sprinkler system installed in
accordance with Section 903.3 shall be provided throughout all
buildings with a Group R fire area.
EXCEPTION: | Group R-1 if all of the following conditions apply: |
1. The Group R fire area is no more than 500 square feet and is used for recreational use only. | |
2. The Group R fire area is on only one story. | |
3. The Group R fire area does not include a basement. | |
4. The Group R fire area is no closer than 30 feet from another structure. | |
5. Cooking is not allowed within the Group R fire area. | |
6. The Group R fire area has an occupant load of no more than 8. | |
7. A hand held (portable) fire extinguisher is in every Group R fire area. |
SECTION 906 -- PORTABLE FIRE EXTINGUISHERS
906.1 Where required. Portable fire extinguishers shall be
installed in the following locations:
1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
2. Within 30 feet (9144 mm) of commercial cooking equipment.
3. In areas where flammable or combustible liquids are stored, used or dispensed.
4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 1415.1.
5. Where required by the sections indicated in Table 906.l.
6. Special-hazard areas, including, but not limited to, laboratories, computer rooms and generator rooms, where required by the fire code official.
SECTION 907 -- FIRE ALARM AND DETECTION SYSTEMS
[F] 907.2.8 Group R-1. Fire alarm systems, smoke alarms and
carbon monoxide alarms shall be installed in Group R-1
occupancies as required in this section and Section 907.2.8.4.
[F] 907.2.8.4. Carbon monoxide alarms. For new construction,
an approved carbon monoxide alarm shall be installed by
January 1, 2011, outside of each separate sleeping area in the
immediate vicinity of the bedroom in sleeping units. In a
building where a tenancy exists, the tenant shall maintain the
CO alarm as specified by the manufacturer including
replacement of the batteries.
[F] 907.2.8.4.1 Existing sleeping units. Existing sleeping
units shall be equipped with carbon monoxide alarms by July 1,
2011.
[F] 907.2.8.4.2 Alarm requirements. Single station carbon
monoxide alarms shall be listed as complying with UL 2034 and
shall be installed in accordance with this code and the
manufacturer's installation instructions.
[F] 907.2.9 Group R-2. Fire alarm systems, smoke alarms and
carbon monoxide alarms shall be installed in Group R-2
occupancies as required in Sections 907.2.9.1 through
907.2.9.3.
((907.2.9.1)) [F] 907.2.9.1.1 Group R-2 boarding homes. A
manual fire alarm system shall be installed in Group R-2
occupancies where the building contains a boarding home
licensed by the state of Washington.
EXCEPTION: | In boarding homes licensed by the state of Washington, manual fire alarm boxes in resident sleeping areas shall not be required at exits if located at all constantly attended staff locations, provided such staff locations are visible, continuously accessible, located on each floor, and positioned so no portion of the story exceeds a horizontal travel distance of 200 feet to a manual fire alarm box. |
[F] 907.2.9.3.1 Existing dwelling units. Existing dwelling
units shall be equipped with carbon monoxide alarms by July 1,
2011.
[F] 907.2.10 Group R-3. Carbon monoxide alarms shall be
installed in Group R-3 occupancies as required in Sections
907.2.10.1 through 907.2.10.3.
[F] 907.2.l0.1 Carbon monoxide alarms. For new construction,
an approved carbon monoxide alarm shall be installed by
January 1, 2011, outside of each separate sleeping area in the
immediate vicinity of the bedroom in dwelling units. In a
building where a tenancy exists, the tenant shall maintain the
CO alarm as specified by the manufacturer including
replacement of the batteries.
[F] 907.2.10.2 Existing dwelling units. Existing dwelling
units shall be equipped with carbon monoxide alarms by July 1,
2011.
EXCEPTION: | Owner-occupied Group R-3 residences legally occupied prior to July 1, 2010. |
909.6.3 Elevator shaft pressurization. Where elevator shaft
pressurization is required to comply with Exception 6 of IBC
Section 708.14.1, the pressurization system shall comply with
and be maintained in accordance with IBC 708.14.2.
909.6.3.1 Activation. The elevator shaft pressurization
system shall be activated by a fire alarm system which shall
include smoke detectors or other approved detectors located
near the elevator shaft on each floor as approved by the
building official and fire code official. If the building has
a fire alarm panel, detectors shall be connected to, with
power supplied by, the fire alarm panel.
909.6.3.2 Power system. The power source for the fire alarm
system and the elevator shaft pressurization system shall be
in accordance with Section 909.11.
SECTION 915 ALERTING SYSTEMS
915.1 General. An approved alerting system shall be provided
in buildings and structures as required in chapter 4 and this
section, unless other requirements are provided by another
section of this code.
EXCEPTION: | Approved alerting systems in existing buildings, structures or occupancies. |
EXCEPTION: | Systems which do not require electrical power to operate. |
915.4 Combination system. Alerting system components and
equipment shall be allowed to be used for other purposes.
915.4.1 System priority. The alerting system use shall take
precedence over any other use.
915.4.2 Fire alarm system. Fire alarm systems sharing
components and equipment with alerting systems must be in
accordance with Section 6.8.4 of NFPA 72.
915.4.2.1 Signal priority. Recorded or live alert signals
generated by an alerting system that shares components with a
fire alarm system shall, when actuated, take priority over
fire alarm messages and signals.
915.4.2.2 Temporary deactivation. Should the fire alarm
system be in the alarm mode when such an alerting system is
actuated, it shall temporarily cause deactivation of all fire
alarm-initiated audible messages or signals during the time
period required to transmit the alert signal.
915.4.2.3 Supervisory signal. Deactivation of fire alarm
audible and visual notification signals shall cause a
supervisory signal for each notification zone affected in the
fire alarm system.
915.5 Audibility. Audible characteristics of the alert signal
shall be in accordance with Section 7.4.1 of NFPA 72
throughout the area served by the alerting system.
EXCEPTION: | Areas served by approved visual or textual notification, where the visible notification appliances are not also used as a fire alarm signal, are not required to be provided with audibility complying with Section 915.6. |
[Statutory Authority: RCW 19.27.031 and 19.27.074. 10-03-100, § 51-54-0900, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 09-04-027, § 51-54-0900, filed 1/28/09, effective 7/1/10; 08-01-101, § 51-54-0900, filed 12/18/07, effective 4/1/08. Statutory Authority: RCW 19.27.031, 19.27.074, and chapters 19.27 and 34.05 RCW. 07-01-093, § 51-54-0900, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.020, 19.27.031, 19.27.074 and chapters 19.27 and 34.05 RCW. 05-24-071, § 51-54-0900, filed 12/5/05, effective 7/1/06. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-105, § 51-54-0900, filed 12/17/03, effective 7/1/04.]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION(Amending WSR 09-04-027, filed 1/28/09,
effective 7/1/10)
WAC 51-54-1000
Chapter 10 -- Means of egress.
((1008.1.2 Door swing. Egress doors shall be side-hinged
swinging.
The opening force for interior side-swinging doors
without closers shall not exceed a 5-pound (22 N) force. For
other side-swinging, sliding, and folding doors, the door
latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound
(133 N) force. The door shall swing to a full-open position
when subjected to a 15-pound (67 N) force. Forces shall be
applied to the latch side.
1008.1.8.3 Locks and latches. Locks and latches shall be
permitted to prevent operation of doors where any of the
following exists:
1. Places of detention or restraint.
2. In buildings in occupancy Group A having an occupant load of 300 or less, Group B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1 The locking device is readily distinguishable as locked.
2.2 A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background; and
2.3 The use of the key-operated locking device is revocable by the fire code official for due cause.
3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware.
4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool.
5. Approved, listed locks without delayed egress shall be permitted in nursing homes or portions of nursing homes, and boarding homes licensed by the state of Washington, provided that:
5.1 The clinical needs of one or more patients require specialized security measures for their safety;
5.2 The doors unlock upon actuation of the automatic sprinkler systems or automatic fire detection system;
5.3 The doors unlock upon loss of electrical power controlling the lock or lock mechanism;
5.4 The lock shall be capable of being deactivated by a signal from a switch located in an approved location; and
5.5 There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
1009.12 Stairways in individual dwelling units. Stairs or
ladders within an individual dwelling unit used for access to
areas of 200 square feet (18.6 m2) or less, and not containing
the primary bathroom or kitchen, are exempt from the
requirements of Section 1009.
1014.2.2 Group I-2. Habitable rooms or suites in Group I-2
Occupancies shall have an exit access door leading directly to
a corridor.
1014.2.3 Suites in patient sleeping areas. Patient sleeping
areas in Group I-2 Occupancies shall be permitted to be
divided into suites if one of the following conditions is met:
1. The intervening room within the suite is not used as an exit access for more than eight patient beds.
2. The arrangement of the suite allows for direct and constant visual supervision by nursing personnel.
1014.2.3.1 Area. Suites of sleeping rooms shall not exceed
5,000 square feet (465 m2).
1014.2.3.2 Exit access. Any patient sleeping room, or any
suite that includes patient sleeping rooms, of more than 1,000
square feet (93 m2) shall have at least two exit access doors
remotely located from each other.
1014.2.3.3 Travel distance. The travel distance between any
point in a suite of sleeping rooms and an exit access door of
that suite shall not exceed 100 feet (30,480 mm).
1014.2.4 Suites in areas other than patient sleeping areas.
Areas other than patient sleeping areas in Group I-2
Occupancies shall be permitted to be divided into suites.
1014.2.4.1 Area. Suites of rooms, other than patient rooms,
shall not exceed 10,000 square feet (929 m2).
1014.2.4.2 Exit access. Any rooms or suite of rooms, other
than patient sleeping rooms, of more than 2,500 square feet
(232 m2) shall have at least two exit access doors remotely
located from each other.
1014.2.4.3 One intervening room. For rooms other than patient
sleeping rooms, suites of rooms are permitted to have one
intervening room if the travel distance within the suite is
not greater than 100 feet (30,480 mm).
1014.2.4.4 Two intervening rooms. For rooms other than
patient sleeping rooms located within a suite, exit access
travel from within the suite shall be permitted through two
intervening rooms where the travel distance to the exit access
door is not greater than 50 feet (15,240 mm).
1014.2.5 Travel distance. The travel distance between any
point in a Group I-2 Occupancy patient room and an exit access
door in that room shall not exceed 50 feet (15,240 mm).
1014.2.6 Separation. Suites in Group I-2 Occupancies shall be
separated from other portions of the building by a smoke
partition complying with Section 710.
1015.1 Exits or exit access doorways from spaces. Two exits
or exit access doorways from any space shall be provided where
one of the following conditions exists:
1. The occupant load of the space exceeds one of the values in Table 1015.1.
3. Where required by Sections 1015.3, 1015.4, 1015.5, 1015.6 or 1015.6.1.
(( |
|
1019.1 Exits from stories. All spaces within each story shall
have access to the minimum number of exits as specified in
Table 1019.1 based on the occupant load of the story, except
as modified in Section 1019.2. For the purposes of this
chapter, occupied roofs shall be provided with exits as
required for stories. The required number of exits from any
story, including basements, shall be maintained until arrival
at grade or the public way.
(( |
|
1. Buildings meeting the limitations of Table 1019.2, provided the building has not more than one level below the first story above grade plane.
2. Buildings of Group R-3 Occupancy.
3. Single-level buildings with occupied spaces at the level of exit discharge provided each space complies with Section 1015.1 as a space with one exit or exit access doorway.
(( |
||
SECTION 1007 ACCESSIBLE MEANS OF EGRESS
1007.1 Accessible means of egress required. Accessible means
of egress shall comply with this section. Accessible spaces
shall be provided with not less than one accessible means of
egress. Where more than one means of egress are required by
Section 1015.1 or 1021.1 from any accessible space, each
accessible portion of the space shall be served by not less
than two accessible means of egress.
EXCEPTIONS: | 1. Accessible means of egress are not required in alterations to existing buildings. |
2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1007.3, 1007.4 or 1007.5. | |
3. In assembly areas with sloped or stepped aisles, one accessible means of egress is permitted where the common path of travel is accessible and meets the requirements in Section 1028.8. | |
4. In parking garages, accessible means of egress are not required to serve parking areas that do not contain accessible parking spaces. |
EXCEPTIONS: | 1. Two-way communication systems are not required at the elevator landing where two-way communication is provided within the areas of refuge in accordance with Section 1007.6.3. |
2. Two-way communication systems are not required on floors provided with exit ramps conforming to provisions of Section 1010. |
SECTION 1008 DOORS, GATES AND TURNSTILES
1008.1.9.3 Locks and latches. Locks and latches shall be
permitted to prevent operation of doors where any of the
following exists:
1. Places of detention or restraint.
2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1 The locking device is readily distinguishable as locked;
2.2 A readily visible sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background; and
2.3 The use of the key-operated locking device is revocable by the building official for due cause.
3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware.
4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt, or security chain, provided such devices are openable from the inside without the use of a key or a tool.
5. Fire doors after the minimum elevated temperature has disabled the unlatching mechanism in accordance with listed fire door test procedures.
6. Approved, listed locks without delayed egress shall be permitted in Group R-2 boarding homes licensed by Washington state, provided that:
6.1. The clinical needs of one or more patients require specialized security measures for their safety.
6.2. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.
6.3. The doors unlock upon loss of electrical power controlling the lock or lock mechanism.
6.4. The lock shall be capable of being deactivated by a signal from a switch located in an approved location.
6.5. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
1008.1.9.6 Special locking arrangements in Group I-2.
Approved locks shall be permitted in a Group I-2 Occupancy
where the clinical needs of persons receiving care require
such locking. Locks shall be permitted in such occupancies
where the building is equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.1 or an
approved automatic smoke or heat detection system installed in
accordance with Section 907, provided that the doors unlock in
accordance with Items 1 through 6 below.
1. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.
2. The doors unlock upon loss of power controlling the lock or lock mechanism.
3. The door locks shall have the capability of being unlocked by a signal from the fire command center, a nursing station or other approved location.
4. The procedures for the operation(s) of the unlocking system shall be described and approved as part of the emergency planning and preparedness required by Chapter 4 of the International Fire Code.
5. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
6. Emergency lighting shall be provided at the door.
EXCEPTION: | Items 1, 2, 3, and 5 shall not apply to doors to areas where persons which because of clinical needs require restraint or containment as part of the function of a Group I-2 mental hospital provided that all clinical staff shall have the keys, codes or other means necessary to operate the locking devices. |
1009.15 Stairways in individual dwelling units. Stairs or
ladders within an individual dwelling unit used for access to
areas of 200 square feet (18.6 m2) or less, and not containing
the primary bathroom or kitchen, are exempt from the
requirements of Section 1009.
SECTION 1010 RAMPS
1010.1 Scope. The provisions of this section shall apply to
ramps used as a component of a means of egress.
EXCEPTIONS: | 1. Other than ramps that are part of the accessible routes providing access in accordance with Sections 1108.2 through 1108.2.4 and 1108.2.6, ramped aisles within assembly rooms or spaces shall conform with the provisions in Section 1028.11. |
2. Curb ramps shall comply with ICC A117.1. | |
3. Vehicle ramps in parking garages for pedestrian exit access shall not be required to comply with Sections 1010.3 through 1010.9 when they are not an accessible route serving accessible parking spaces or other required accessible elements. | |
4. In a parking garage where one accessible means of egress serving accessible parking spaces or other accessible elements is provided, a second accessible means of egress serving that area may include a vehicle ramp that does not comply with Sections 1010.4 through 1010.8. |
1014.2.2 Group I-2. General. Habitable spaces and suites in
Group I-2 Occupancies are permitted to comply with this
Section 1014.2.2.
1014.2.2.1 Exit access doors. Habitable spaces and suites in
Group I-2 Occupancies shall have an exit access door leading
directly to a corridor.
EXCEPTION: | Rooms with exit doors opening directly to the outside at ground level. |
1014.2.2.3 Separation. Suites in Group I-2 Occupancies shall
be separated from other portions of the building by a smoke
partition complying with Section 711. Partitions within
suites are not required to be smoke-resistant or
fire-resistance-rated unless required by another section of
this Code.
1014.2.2.4 Suites containing patient sleeping areas. Patient
sleeping areas in Group I-2 Occupancies shall be permitted to
be divided into suites with one intervening room if one of the
following conditions is met:
1. The intervening room within the suite is not used as an exit access for more than eight patient beds.
2. The arrangement of the suite allows for direct and constant visual supervision by nursing personnel.
1014.2.2.4.1 Area. Suites of sleeping rooms shall not exceed
5,000 square feet (465 m2).
1014.2.2.4.2 Exit access. Any patient sleeping room, or any
suite that includes patient sleeping rooms, of more than 1,000
square feet (93 m2) shall have at least two exit access doors
located in accordance with Section 1015.2.
1014.2.2.4.3 Travel distance. The travel distance between any
point in a suite of sleeping rooms and an exit access door of
that suite shall not exceed 100 feet (30,480 mm). The travel
distance between any point in a Group I-2 Occupancy patient
sleeping room and an exit access door in that room shall not
exceed 50 feet (15,240 mm).
1014.2.2.5 Suites not containing patient sleeping areas.
Areas other than patient sleeping areas in Group I-2
Occupancies shall be permitted to be divided into suites that
comply with Sections 1014.2.2.5.1 through 1014.2.2.5.4.
1014.2.2.5.1 Area. Suites of rooms, other than patient
sleeping rooms, shall not exceed 10,000 square feet (929 m2).
1014.2.2.5.2 Exit access. Any room or suite of rooms, other
than patient sleeping rooms, of more than 2,500 square feet
(232 m2) shall have at least two exit access doors located in
accordance with Section 1015.2.
1014.2.2.5.3 One intervening room. For rooms other than
patient sleeping rooms, suites of rooms are permitted to have
one intervening room if the travel distance within the suite
to the exit access door is not greater than 100 feet (30,480
mm).
1014.2.2.5.4 Two intervening rooms. For rooms other than
patient sleeping rooms located within a suite, exit access
travel from within the suite shall be permitted through two
intervening rooms where the travel distance to the exit access
door is not greater than 50 feet (15,240 mm).
SECTION 1018 CORRIDORS
1018.5 Air movement in corridors. Corridors shall not serve
as supply, return, exhaust, relief or ventilation air ducts.
EXCEPTIONS: | 1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor closets, shall be permitted, provided that each such corridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor. |
2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited. | |
3. Where located within tenant spaces of one thousand square feet (93 m2) or less in area, utilization of corridors for conveying return air is permitted. | |
4. Incidental air movement from pressurized rooms within health care facilities, provided that a corridor is not the primary source of supply or return to the room. | |
5. Where such air is part of an engineered smoke control system. | |
6. Air supplied to corridors serving residential occupancies shall not be considered as providing ventilation air to the dwelling units subject to the following: | |
6.1 The air supplied to the corridor is one hundred percent outside air; and | |
6.2 The units served by the corridor have conforming ventilation air independent of the air supplied to the corridor; and | |
6.3 For other than high-rise buildings, the supply fan will automatically shut off upon activation of corridor smoke detectors which shall be spaced at no more than thirty feet (9,144 mm) on center along the corridor; or | |
6.4 For high-rise buildings, corridor smoke detector activation will close required smoke/fire dampers at the supply inlet to the corridor at the floor receiving the alarm. |
EXCEPTIONS: | 1. Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms. |
2. In Group R-2 boarding homes and residential treatment facilities licensed by Washington state, seating areas shall be allowed to be open to the corridor provided: | |
2.1 The seating area is constructed as required for the corridor; | |
2.2 The floor is separated into at least two compartments complying with Section 407.4; | |
2.3 Each individual seating area does not exceed 150 square feet, excluding the corridor width; | |
2.4 The combined total space of seating areas per compartment does not exceed 300 square feet, excluding the corridor width; | |
2.5 Combustible furnishings located within the seating area shall be in accordance with the International Fire Code Section 805; and | |
2.6 Emergency means of egress lighting is provided as required by Section 1006 to illuminate the area. |
[Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 09-04-027, § 51-54-1000, filed 1/28/09, effective 7/1/10. Statutory Authority: RCW 19.27.031, 19.27.074, and chapters 19.27 and 34.05 RCW. 07-01-093, § 51-54-1000, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-105, § 51-54-1000, filed 12/17/03, effective 7/1/04.]
The following sections of the Washington Administrative Code are repealed:
WAC 51-54-1007 | Section 1007 -- Accessible means of egress. |
WAC 51-54-1008 | Section 1008 -- Doors, gates and turnstiles. |
WAC 51-54-1009 | Section 1009 -- Stairways and handrails. |
WAC 51-54-1010 | Section 1010 -- Ramps. |
WAC 51-54-1014 | Exit access. |
WAC 51-54-1015 | Reserved. |
WAC 51-54-1017 | Reserved. |
WAC 51-54-1018 | Section 1018 -- Corridors. |
WAC 51-54-1019 | Reserved. |