WSR 15-16-098
PROPOSED RULES
BUILDING CODE COUNCIL
[Filed August 4, 2015, 8:38 a.m.]
Original Notice.
Preproposal statement of inquiry was filed as WSR 15-10-076.
Title of Rule and Other Identifying Information: Adoption and amendment of the 2015 International Mechanical Code, chapter 51-52 WAC.
Hearing Location(s): Fire Department Training Center, 1618 South Rebecca Street, Spokane, WA, on September 11, 2015, at 10 a.m.; and at the DES Presentation Room, 1500 Jefferson S.E., Olympia, WA 98504, on October 16, 2015, at 10 a.m.
Date of Intended Adoption: November 13, 2015.
Submit Written Comments to: Dave Kokot, Chair, State Building Code Council (SBCC), P.O. Box 41449, Olympia, WA 98504-1449, e-mail sbcc@ga.wa.gov, fax (360) 586-9088, by October 23, 2015.
Assistance for Persons with Disabilities: Contact Peggy Bryden by August 24, 2015, (360) 407-9280.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: The proposed rules adopt the most recently published edition of the International Mechanical Code and make changes to the state amendments to this code.
1. References to the code edition were updated to and the expected effective date cited in 003/008.
2. Section 101.2 was updated to cite the most recent code editions for the National Fuel Gas Code and Liquefied Petroleum Gas Code. This same change was also made to Section 101.2 of the International Fuel Gas Code (WAC 51-52-21101).
3. The exception in Section 102.4 was moved to Section 403.8.5.
4. A new definition for Permanent Construction was added to coordinate with the new Section 306.6.
5. The state amendment to Section 301.3 was removed, as it was felt to be unnecessary. This change was also made to Section 401.9 of the International Fuel Gas Code (WAC 51-52-21401).
6. Section 306.6 was added to clarify access requirements for installations in ceilings.
7. Section 307.2.4.1 is a new section in the model code that was amended to allow for any type of condensate trap allowed by the ductless mini-split manufacturer.
8. Chapter 4 was reorganized slightly in the 2015 International Model Code, so there are instances of updating section citations. The Washington state residential ventilation provisions were left as Section 403.8 for convenience; however, there are no longer any Sections 403.4 through 403.7 in the model code. Those sections were moved to be subsections of Section 403.3.1.1, Outdoor airflow rate.
9. The new residential ventilation section of the model code, Section 403.3.2 is not adopted and a pointer to the Washington state amendment is added to Section[s] 401.2, 401.3 and 403.1 in addition to Section 403.3.2.
10. The model code also introduced a new section for ventilation in health care facilities in Section 407. This section was amended to cite the department of health requirements for licensed health care facilities. Coordinating changes were also made to Section 401.2.
11. The change in Section 403.2 is editorial to match the 2015 International Mechanical Code language.
12. Section 403.3 was renumbered by the model code as Section 403.3.1.1 under the chapter reorganization. Table 403.3 was also renumbered accordingly, and all the references were changed to reflect this. There was also some clarifying language added to match the changes in the model code. Table 403.3.1.1 was modified to:
(1) A footnote was added to the kitchens line in the offices category that clarifies that hoods are not required for microwaves in office kitchenettes;
(2) Remove the ventilation rate for single dwelling garages, mirroring a change in the model code;
(3) Add an increased ventilation rate for residential corridors where the dwelling units are ventilated per the option in 403.8.6, to increase the pressure differential to keep infiltration of odors from the dwellings from entering the corridor;
(4) Include ventilation rates for elevator lobbies in parking garages;
(5) Include ventilation requirements for freezer[s];
(6) The other changes shown added in the body of the table mirror requirements in the model code and have not been changed from the 2012 requirements;
(7) Footnote b was updated to coordinate with the 2015 model code language, as was footnote h, which clarifies that ventilation is required at each workstation in a nail salon and coordinates with new model code language in Section 502.20. Footnote k coordinates with the change described in item (1).
13. A new ventilation rate table from ASHRAE 62.1 was substituted for the previous Table 403.8.1. The new table is specifically formulated for multi-family dwellings, whereas the previous table was intended for single-family dwellings.
14. Section 403.8.2, item 4 was modified to allow flexibility in the types of controls used for whole house ventilation, along with clarification that it needs to be labeled.
15. Section 403.8.3, item 8 was added to specify that outdoor air intakes are not permitted to be on asphalt roofs unless there are no other options, and criteria to be met if this is the case. This will help prevent fumes and chemicals from off-gassing roofing materials to contaminate the indoor air quality.
16. Section 403.8.5 - see item 1, above.
17. Section 403.8.6.1 was modified to allow windows and other operable openings to be used for outdoor air in lieu of outdoor air inlets in all building types, not just high-rises.
18. The current language in Section 403.8.6.1, item 3 is copied over to Sections 403.8.7.1, 403.8.8.1 and 403.8.9.1 to allow all whole house ventilation methods to use the same options for ventilating interior rooms and spaces.
19. Sections 403.8.7.2 and 403.8.9.2 were modified to clarify that each habitable space needs to be served by the forced air system or energy recovery ventilator.
20. Section 407 - see item 10, above.
21. The state amendment to Section 504.6.4.1 was deleted, as this requirement was integrated into the model code in 2015 edition.
22. The state amendment to Section 504.7.1 was deleted, as this requirement was integrated into the model code in the 2015 edition.
23. Sections 504.4 and 505.1 were both modified to clarify that residential dryer, range and local exhausts are allowed to terminate at a common plenum as long as each has their own damper.
24. The changes to Section 506.3.11 reflect changes made to the model code to make it explicit that fire and smoke dampers are prohibited from being installed in grease ducts.
25. In the 2015 edition of the International Mechanical Code, the commercial kitchen hood Section 507 was reorganized, with many of the general sections that were previously repeated in both the Type 1 [I] and Type II hood subsections pulled out and placed in Section 507.1. Existing sections were renumbered and moved around but remain essentially unchanged.
26. A new Section 515 was added to specify that chute venting needed to comply with NFPA 82 or be located outside the building.
27. In Section 602.1, the model code added a sentence stating that air systems must be ducted from the air handler to the area served. Washington state clarified this amendment to specify that this was true if the system served multiple fire areas.
28. The model code added language to require filters upstream of all coils and heat exchangers. The state amended that language with an exception for chilled beams.
29. The amendment to Section 606.2 clarifies that smoke detectors are not required on the supply or return/exhaust air on dedicated outside air systems since this air is not recirculated into any other portion of the building.
30. The Washington state amendment to Section 928 is deleted; it was deemed unnecessary with the change in language in the 2015 Model Code.
31. A Washington state amendment to Section 1107.2 attempts to clarify language prohibiting refrigerant piping in certain locations.
32. Two amendments are proposed to the hydronic piping section. Section 1209.5.1 amends the insulation requirements to be consistent with the energy code. Section 1210.7.6 requires a means of draining expansion tanks downstream of the shutoff valve.
Reasons Supporting Proposal: RCW 19.27.031 and 19.27.074.
Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.
Statute Being Implemented: Chapters 19.27 and 34.05 RCW.
Rule is not necessitated by federal law, federal or state court decision.
Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: SBCC is seeking comments on the issues proposed in the rules shown below.
Name of Proponent: SBCC, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Krista Braaksma, 1500 Jefferson S.E., P.O. Box 41449, Olympia, WA, (360) 407-9278.
A small business economic impact statement has been prepared under chapter 19.85 RCW.
Small Business Economic Impact Statement
Description: SBCC is filing a proposed rule to adopt the updated 2015 edition of the International Building Code (chapter 51-50 WAC). Since 1985 SBCC has been responsible to update new editions of the building code through RCW 19.27.074.
The administrative compliance requirements are under the authority of the local government. RCW 19.27.050. Compliance activities, including permit issuance, plan review and approval, and inspections occur at the local level. Requirements for construction document submittal and other reporting requirements are determined by the local jurisdiction and are consistent with previously established policies. The proposed amendments to chapter 51-52 WAC include specific technical requirements for building construction to be consistent with national standards.
The IMC is updated every three years by the International Code Council (ICC). The code development process conducted by the model code organization is open to all interest groups within the design and construction industry and from governmental organizations. See www.iccsafe.org for more information about the model code development process.
Professional Services: Washington has had a statewide building code in effect since 1974. The local enforcement authority having jurisdiction administers the codes through the building departments. Administrative procedures for state building code compliance are established and will not be changed by the adoption of the update to the current building codes. Small businesses will employ the same types of professional services for the design and construction of buildings and systems to comply with the state building code.
The proposed rule updates the state building code and does not require additional equipment, supplies, labor or other services. Services needed to comply with the building code are existing within the construction industry as required by the local authority having jurisdiction.
Costs of Compliance for Businesses: The cost of compliance incurred by Washington businesses includes training and educational materials. A complete set of the 2015 model codes on CD rom costs $985 for ICC members. The cost for just the 2015 IMC is $62. These publications are also available online at http://codes.iccsafe.org/I-Codes.html. The ICC chapters offer training for continuing education credits to architects, engineers and building inspectors for $285.
The 2015 edition of the IMC, with state amendments, contains four significant amendments with a cost impact. These items were identified through the model code development process, and reviewed by the SBCC Mechanical Code technical advisory group and the economic workgroup.
1. Table 403.3.1.1 was modified by state amendment to provide an increase in the minimum ventilation rate for corridors in residential multi-family dwellings where the whole house ventilation is provided through whole house exhaust fans and trickle vents, to ensure the corridor maintains positive pressure in relation to each residence, minimizing contaminates. The increased rate is not an increase over the typical ventilation rate provided under the current code, but could result in increased energy use over the life of the building.
2. Table 403.3.1.1 was also modified to clarify that elevator lobbies in parking garages are required to be ventilated. This is currently only implied by the codes and may not have been enforced by all jurisdictions.
3. Section 1209.5.1 was modified to require that hydronic piping systems include a means of draining the expansion tank after the shutoff valve. This would increase the initial cost of the system, but significantly reduce the cost of system maintenance.
4. Section 908.8 of the 2015 IMC requires that cooling towers and evaporative condensers include automatic bleed controls for conservation of water. The proponent of this change estimates considerable water savings achieved in the first year, with a similar savings in energy use, based on a California utility study. The initial cost of this added control is estimated to be $1,500.
Loss of Sales or Revenue: The proposed rules make the state code for building construction consistent with national standards. Businesses with new products or updated test or design standards are recognized in the updated code.
The update will result in some cost outlay for some small businesses for specific projects, for a transition period. Other small businesses would see an increase in revenue. Amendments to the building codes affect over twenty-five thousand small businesses in the state, where construction activity occurs. The primary intent of the amendments is to improve the safety features in buildings and provide consistency and fairness across the state, for a predictable business environment. The amendments should result in enhanced safety and value in buildings.
Cost of Compliance for Small Businesses: Determine whether the proposed rule will have a disproportionate cost impact on small businesses, compare the cost of compliance for small business with the cost of compliance for the ten percent of businesses that are the largest businesses.
The majority of businesses affected by the updates to the building codes are small businesses; over ninety-five percent of those listed in the construction and related industries have under fifty employees. The costs per employee are comparable between the largest businesses and the majority of small businesses. The cost to comply with the updated codes is not a disproportionate impact on small business. Where SBCC found the cost of compliance for small businesses to be disproportionate, the proposed rule mitigates the cost. The proposed rules include a definition of small business and provide exceptions for compliance with the updated rule.
Reducing the Costs of the Rule on Small Businesses: The revision history for the 2015 model code amendments includes over two hundred amendments proposed by industry and local governments which add flexibility and clarity to the code and coordinate rules. The majority of the changes show no impact to cost, and a number of them represent a savings for small business building owners and operators. Some examples of these savings are noted below:
A state amendment to Table 403.3.1.1 clarifies that microwaves in office kitchenettes are not required to be provided with additional ventilation.
Section 504.8 specifically allows common exhaust systems for multi-story buildings.
Sections 908.5 and 928.1 allow the use of alternate water sources for cooling towers if approved by the code official and the manufacturer.
Small Businesses Involved in the Development of the Rule: The SBCC conducted twelve open public meetings of the mechanical code technical advisory group, available via telephone conference bridge and over the internet, and allowed comment on every item on every agenda. The SBCC appointed over one hundred representatives of all segments of the business and construction community to serve on the technical advisory groups.
List of Industries: Below is a list of industries required to comply with the mechanical code:
NAICS #
Type of Business
Businesses with fewer than 50 employees
Businesses with 50 or more employees
236116
New multifamily housing construction
69
4
236210
Industrial building construction
88
8
236220
Commercial and institutional building construction
1151
40
238220
Plumbing, heating, and air-conditioning contractors
2245
66
238290
Other building equipment contractors
315
6
238990
All other specialty trade contractors
1141
15
332322
Sheet metal work manufacturing
69
8
333415
Air-conditioning and warm air heating equipment
13
2
423390
Other construction material merchant wholesalers
78
0
423720
Plumbing and heating equipment and supplies (hydronics)
99
6
423730
Warm air heating and air-conditioning equipment and supplies
48
1
531120
Lessors of nonresidential buildings (except miniwarehouse)
2046
7
541310
Architectural services
579
19
541330
Engineering services
2351
82
541340
Drafting services
69
0
541350
Building inspection services
168
1
922160
Fire protection
246
31
 
Total
10,775
296
Estimate of the Number of Jobs That Will Be Created or Lost: The adoption of the latest code edition is not expected to significantly impact the number of jobs in the construction industry. These rules are likely to be job neutral overall, i.e., they will not result in any job gains or losses. The scheduled effective date of the new edition is July 1, 2016. Building permits issued prior to that date will be vested under the 2012 code. Permits issued for projects under the 2015 code edition will start with the 2017 construction season.
The construction industry has experienced growth over the period June 2014 to June 2015. (Data from Current Employment Statistics (CES).)
Wage and salary workers
2015
2014
Residential building construction
25,600
22,400
Nonresidential building construction
18,700
16,500
Specialty trade contractors
114,200
101,400
A copy of the statement may be obtained by contacting Tim Nogler, SBCC, P.O. Box 41449, Olympia, WA 98504-1449, phone (360) 407-9280, fax (360) 586-9088, e-mail sbcc@ga.wa.gov. SBCC is not one of the agencies identified as required to prepare a school district impact statement.
A cost-benefit analysis is not required under RCW 34.05.328. SBCC is not one of the agencies identified as required to prepare an analysis.
August 4, 2015
David F. Kokot
Council Chair
Chapter  51-52  WAC
STATE BUILDING CODE ADOPTION AND AMENDMENT OF THE ((2012)) 2015 EDITION OF THE INTERNATIONAL MECHANICAL CODE
(Formerly chapter 51-42 WAC)
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-003 International Mechanical Code.
The ((2012)) 2015 edition of the International Mechanical Code published by the International Code Conference is hereby adopted by reference with the exceptions noted in this chapter of the Washington Administrative Code (WAC).
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-008 Implementation.
The International Mechanical Code adopted by chapter 51-52 WAC shall become effective in all counties and cities of this state on July 1, ((2013)) 2016.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0101 Section 101General.
101.2 Scope. This code shall regulate the design, installation, maintenance, alteration and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. This code shall also regulate those mechanical systems, system components, equipment and appliances specifically addressed herein. The installation of fuel gas distribution piping and equipment, fuel gas-fired appliances and fuel gas-fired appliance venting systems shall be regulated by the International Fuel Gas Code.
EXCEPTIONS:
1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the International Residential Code.
 
2. The standards for liquefied petroleum gas installations shall be the ((2011)) 2014 Edition of NFPA 58 (Liquefied Petroleum Gas Code) and the ((2012)) 2015 Edition of ANSI Z223.1/NFPA 54 (National Fuel Gas Code).
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0102 Section 102Applicability.
102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to a mechanical system shall conform to that required for a new mechanical system without requiring the existing mechanical system to comply with all of the requirements of this code. Additions, alterations or repairs shall not cause an existing mechanical system to become unsafe, hazardous or overloaded.
Minor additions, alterations, renovations and repairs to existing mechanical systems shall meet the provisions for new construction, unless such work is done in the same manner and arrangement as was in the existing system, is not hazardous and is approved.
((EXCEPTION:
Additions, alterations, renovations or repairs to a mechanical system that is part of a building addition with less than 500 square feet of conditioned floor area are exempt from the requirements for whole house ventilation systems, Section 403.8.5.))
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0202 Section 202General definitions.
LOCAL EXHAUST. An exhaust system that uses one or more fans to exhaust air from a specific room or rooms within a dwelling.
PERMANENT CONSTRUCTION. Construction that, if removed, would disturb the structural integrity of the building or the fire-resistance rating of a building assembly.
WHOLE HOUSE VENTILATION SYSTEM. A mechanical ventilation system, including fans, controls, and ducts, which replaces, by direct or indirect means, air from the habitable rooms with outdoor air.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0301 Section 301General.
((301.3 Identification. Each length of pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identification of the manufacturer.
EXCEPTION:
The manufacturer identification for fittings and pipe nipples shall be on each piece or shall be printed on the fitting or nipple packaging or provided documentation.))
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0306 Section 306Access and service space.
306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 percent slope). Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall.
Permanent ladders installed to provide the required access shall comply with the following minimum design criteria:
1. The side railing shall extend above the parapet or roof edge not less than 42 inches (1067 mm).
2. Ladders shall have rung spacing not to exceed 12 inches (305 mm) on center. The uppermost rung shall be a maximum of 24 inches below the upper edge of the roof hatch, roof or parapet, as applicable.
3. Ladders shall have a toe spacing not less than 7 inches (178 mm) deep.
4. There shall be a minimum of 18 inches (457 mm) between rails.
5. Rungs shall have a minimum 0.75-inch (19 mm) diameter and be capable of withstanding a 300-pound (136.1 kg) load.
6. Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds (488.2 kg/m2) per square foot. Landing dimensions shall be not less than 18 inches and not less than the width of the ladder served. A guardrail shall be provided on all open sides of the landing.
7. Climbing clearances. The distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder shall be a minimum of 30 inches measured perpendicular to the rungs. This distance shall be maintained from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed.
8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches centered in front of the ladder.
9. Ladders shall be protected against corrosion by approved means.
10. Access to ladders shall be provided at all times.
Catwalks installed to provide the required access shall be not less than 24 inches (610 mm) wide and shall have railings as required for service platforms.
EXCEPTION:
This section shall not apply to Group R-3 occupancies.
306.6 Appliances above ceilings. Appliances that are located above the ceiling shall be accessible for inspection, service and repair without removing permanent construction. Appliances shall be accessible from an access panel or removable ceiling tile with minimum nominal dimensions of 24 inches by 24 inches (609 mm x 609 mm).
The appliance is not required to be removable or replaceable through the access panel or removable ceiling tile. The appliance may be removed or replaced by removing the ceiling or wall assemblies adjacent to the appliance as long as they are not permanent construction.
EXCEPTIONS:
1. This section shall not apply to replacement appliances installed in existing compartments and alcoves where the working space clearances are in accordance with the equipment or appliance manufacturer's installation instructions.
 
2. A smaller access panel or removable ceiling tile shall be permitted when allowed by the equipment or appliance manufacturer's installation instructions.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0307 Section 307Condensate disposal.
307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate:
1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a minimum depth of 1 1/2 inches (38 mm), shall not be less than 3 inches (76 mm) larger than the unit or the coil dimensions in width and length and shall be constructed of corrosion-resistant material. Galvanized sheet steel pans shall have a minimum thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage). Nonmetallic pans shall have a minimum thickness of not less than 0.0625 inch (1.6 mm).
2. A separate overflow drain line shall be connected to the drain pan provided with the equipment. Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a higher level than the primary drain connection.
3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a water-level detection device conforming to UL 508 that will shut off the equipment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section.
4. A water-level detection device conforming to UL 508 shall be provided that will shut off the equipment served in the event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment-supplied drain pan, located at a point higher than the primary drain line connection and below the overflow rim of such pan.
EXCEPTIONS:
1. Fuel-fired appliances that automatically shut down operation in the event of a stoppage in the condensate drainage system.
 
2. Unducted fan coil units where there is no factory option available for water-level detection devices and which are installed directly within the occupied space.
307.2.4.1 Ductless mini-split system traps. Ductless mini-split equipment that produces condensate shall be provided with an inline check valve located in the drain line, a trap, or other means of trapping in accordance with the manufacturer's instructions.
AMENDATORY SECTION (Amending WSR 10-03-099, filed 1/20/10, effective 7/1/10)
WAC 51-52-0401 Section 401General.
401.2 Ventilation required. Every occupied space other than enclosed parking garages and buildings used for repair of automobiles shall be ventilated in accordance with Section ((402.2.1 or)) 401.2.1, 401.2.2 or 401.2.3. Enclosed parking garages and buildings used for repair of automobiles shall be ventilated by mechanical means in accordance with Sections 403 and 404.
401.2.1 Group R occupancies. Ventilation in Group R occupancies shall be provided in accordance with Section 403.8.
401.2.2 Ambulatory care facilities and Group I-2 occupancies. Ambulatory care facilities and Group I-2 occupancies shall be ventilated by mechanical means in accordance with Section 407.
401.2.3 All other occupancies. Ventilation in all other occupancies shall be provided by natural means in accordance with Section 402 or by mechanical means in accordance with Sections 403.1 to 403.7.
401.3 When required. Group R occupancies shall be vented continuously or intermittently in accordance with Section 403.8. Ventilation in all other occupancies shall be provided during the periods that the room or space is occupied.
401.7 Testing and balancing. At the discretion of the building official, flow testing may be required to verify that the mechanical system(s) satisfies the requirements of this chapter. Flow testing may be performed using flow hood measuring at the intake or exhaust points of the system, in-line pitot tube, or pitot-traverse type measurement systems in the duct, short term tracer gas measurements, or other means approved by the building official.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0403 Section 403Mechanical ventilation.
403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure. The system to convey ventilation air shall be designed and installed in accordance with Chapter 6.
403.2 Outdoor air required. The minimum ((ventilation rate of)) outdoor ((air)) flow rate shall be determined in accordance with Section 403.3.
EXCEPTIONS:
1. Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding that obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
 
2. Alternate systems designed in accordance with ASHRAE Standard 62.1 Section 6.2, Ventilation Rate Procedure, shall be permitted.
403.2.1 Recirculation of air. The air required by Section 403.3 shall not be recirculated. Air in excess of that required by Section 403.3 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that:
1. Ventilation air shall not be recirculated from one dwelling to another or to dissimilar occupancies.
2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other spaces where 10 percent or more of the resulting supply airstream consists of air recirculated from these spaces.
3. Where mechanical exhaust is required by Note b in Table 403.3, recirculation of air from such spaces shall be prohibited. All air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.
(Item 4 is not adopted.)
403.3 Outdoor air and local exhaust airflow rates. Group R-2, R-3 and R-4 occupancies three stories and less in height above grade plan shall be provided with outdoor air and local exhaust in accordance with Section 403.8. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.
403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall not be less than the number determined from the estimated maximum occupant load rate indicated in Table ((403.3)) 403.3.1.1. Ventilation rates for occupancies not represented in Table ((403.3)) 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
With the exception of smoking lounges, the ventilation rates in Table ((403.3)) 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a smoking lounge, the ventilation system serving the space shall be designed to provide ventilation over and above that required by Table ((403.3)) 403.3.1.1 in accordance with accepted engineering practice.
EXCEPTION:
Where occupancy density is known and documented in the plans, the outside air rate may be based on the design occupant density. Under no circumstance shall the occupancies used result in outside air less than one-half that resulting from application of Table ((403.3)) 403.3.1.1 estimated maximum occupancy rates.
Table ((403.3)) 403.3.1.1
REQUIRED OUTDOOR VENTILATION AIR
Occupancy Classification
Occupant Density #/1000 ft2a
People Outdoor Airflow Rate in Breathing Zone Rp
cfm/Person
Area Outdoor Airflow Rate in Breathing Zone Ra
cfm/ft2a
Exhaust Airflow Rate cfm/ft2
Offices
 
 
 
 
 
Conference rooms
50
5
0.06
 
Kitchenettesk
0.30
 
Office spaces
5
5
0.06
 
Reception areas
30
5
0.06
 
Telephone/data entry
60
5
0.06
 
Main entry lobbies
10
5
0.06
Private dwellings, single and multiple
 
 
 
 
 
Garages, common for multiple unitsb
0.75
 
((Garages, separate for each dwellingb
100 cfm per car))
 
Kitchensb
25/100f
 
Living areasc
Based on the number of bedrooms. First bedroom, 2; each additional bedroom, 1
See Tables 403.8.1 and 403.8.5.1
 
Toilet rooms, bathrooms and laundry areasg, i
20/50f
Public spaces
 
 
 
 
 
Corridors serving other than Group R occupancies
0.06
 
Corridors serving Group R dwelling or sleeping units with whole house exhaust
0.12
 
Corridors serving Group R dwelling or sleeping units with other than whole house exhaust
0.06
 
Courtrooms
70
5
0.06
 
Elevator car
1
 
Elevator lobbies in parking garage
1.0
 
Legislative chambers
50
5
0.06
 
Libraries
10
5
0.12
 
Museums (children's)
40
7.5
0.12
 
Museums/galleries
40
7.5
0.06
 
Places of religious worship
120
5
0.06
 
Shower room (per showerhead)g, k
 
Smoking loungesb
70
60
 
Toilet rooms—Publicg, k
50/20f
Sports and amusement
 
 
 
 
 
Disco/dance floors
100
20
0.06
 
Bowling alleys (seating areas)
40
10
0.12
 
Game arcades
20
7.5
0.18
 
Ice arenas, without combustion enginesj
0.30
0.5
 
Gym, stadium, arena (play area)j
0.30
 
Spectator areas
150
7.5
0.06
 
Swimming pools (pool and deck area)
0.48
 
Health club/aerobics room
40
20
0.06
 
Health club/weight room
10
20
0.06
Storage
 
 
 
 
 
Janitor closets, trash rooms, recycling rooms
1.0
 
Repair garages, enclosed parking garageb, d
0.75
 
Storage rooms, chemical
1.5
 
Warehouses
0.06
Workrooms
 
 
 
 
 
Bank vaults/safe deposit
5
5
0.06
 
Darkrooms
1.0
 
Copy, printing rooms
4
5
0.06
0.5
 
Freezer and refrigerated spaces (<50°F)
0
10
0
0
 
Meat processingc
10
15
 
Pharmacy (prep. area)
10
5
0.18
 
Photo studios
10
5
0.12
 
Computer (without printing)
4
5
0.06
For SI:
 
1 cubic foot per minute = 0.0004719 m3/s, 1 ton = 908 kg, 1 cubic foot per minutes per square foot = 0.00508 m3/(s•m2), °C = [(°F) -32]/1.8, 1 square foot - 0.0929 m2.
a.
 
Based upon net occupiable floor area.
b.
 
Mechanical exhaust required and the recirculation of air from such spaces is prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited (see Section 403.2.1, Item 3).
c.
 
Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous.
d.
 
Ventilation systems in enclosed parking garages shall comply with Section 404.
e.
 
Rates are per water closet or urinal. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while occupied.
f.
 
Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while occupied.
g.
 
Mechanical exhaust is required and recirculation is prohibited.
h.
 
For nail salons, each ((nail station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station)) manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more required source capture systems operate continuously during occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon.
i.
 
A laundry area within a kitchen or bathroom is not required to have local exhaust. For the laundry area to qualify as being within the kitchen, the laundry room door must open directly into the kitchen and not into an adjacent corridor. Where there are doors that separate the laundry area from the kitchen or bathroom the door shall be louvered.
j.
 
When combustion equipment is intended to be used on the playing surface, additional dilution ventilation and/or source control shall be provided.
k.
 
Kitchenettes require exhaust when they contain a domestic cooking appliance range or oven that is installed in accordance with Table 507.2.2. Kitchenettes that only contain a microwave oven are not required to have mechanical exhaust. A kitchenette may not contain commercial cooking appliances that require Type I or Type II exhaust as these occupancies are required to be exhausted to the kitchen category in Table 403.1.1.
403.3.2 Group R-2, R-3 and R-4 occupancies. This section is not adopted. See Section 403.8.
403.3.2.1 Outdoor air for dwelling units. This section is not adopted.
403.3.2.2 Outdoor air for other spaces. This section is not adopted.
403.3.2.3 Local exhaust. This section is not adopted.
403.8 Ventilation systems for Group R occupancies. Each dwelling unit or sleeping unit shall be equipped with local exhaust and whole house ventilation systems and shall comply with Sections 403.8.1 through 403.8.11. All public corridors and other than Group R occupied spaces that support the Group R occupancy shall meet the ventilation requirements of Section 402 or Sections 403.1 to 403.7.
403.8.1 Minimum ventilation performance. Ventilation systems shall be designed and installed to satisfy the ventilation requirements of Table 403.3 or Table 403.8.1. Breathing zone ventilation rates from Table 403.3 shall be calculated per Section 403.3.1.1 and corrected per zone air distribution effectiveness requirements per Section 403.3.1.2.
Table 403.8.1
VENTILATION RATES FOR ALL GROUP R PRIVATE DWELLINGS, SINGLE AND MULTIPLE
(CONTINUOUSLY OPERATING SYSTEMS)
Floor Area
 
Bedrooms1
 
(ft2)
0-1
 
2-3
 
4-5
 
6-7
 
((˃7))
˃5
 
((<1500
 
30
 
45
 
60
 
75
 
90
 
1501 - 3000
 
45
 
60
 
75
 
90
 
105
 
3001 - 4500
 
60
 
75
 
90
 
105
 
120
 
4501 - 6000
 
75
 
90
 
105
 
120
 
135
 
6001 - 7500
 
90
 
105
 
120
 
135
 
150
 
˃7500
 
105
 
120
 
135
 
150
 
165))
 
<500
 
30
 
40
 
45
 
55
 
60
 
500 - 1000
 
45
 
55
 
60
 
70
 
75
 
1001 - 1500
 
60
 
70
 
75
 
85
 
90
 
1501 - 2000
 
75
 
85
 
90
 
100
 
105
 
2001 - 2500
 
90
 
100
 
105
 
115
 
120
 
2501 - 3000
 
105
 
115
 
120
 
130
 
135
 
3001 - 3500
 
120
 
130
 
135
 
145
 
150
 
>3500
 
135
 
145
 
150
 
160
 
165
 
1Ventilation rates in table are minimum outdoor airflow rates measured in cfm.
403.8.2 Control and operation.
1. Location of controls. Controls for all ventilation systems shall be readily accessible by the occupant.
2. Instructions. Operating instructions for whole house ventilation systems shall be provided to the occupant by the installer of the system.
3. Local exhaust ventilation systems. Local exhaust ventilation systems shall be controlled by manual switches, dehumidistats, timers, or other approved means.
4. Continuous whole house ventilation systems. Continuous whole house ventilation systems shall operate continuously((. Exhaust fans, forced-air system fans, or supply fans shall be equipped with "fan on" as override controls)) and be equipped with an override control. A "fan on" switch shall be permitted as an override control. Controls shall be capable of operating the ventilation system without energizing other energy-consuming appliances. A clearly visible label shall be affixed to the controls that reads "Whole House Ventilation (see operating instructions)."
5. Intermittent whole house ventilation systems. Intermittent whole house ventilation systems shall comply with the following:
5.1 They shall be capable of operating intermittently and continuously.
5.2 They shall have controls capable of operating the exhaust fans, forced-air system fans, or supply fans without energizing other energy-consuming appliances.
5.3 The ventilation rate shall be adjusted according to the exception in Section 403.8.5.1.
5.4 The system shall be designed so that it can operate automatically based on the type of control timer installed.
5.5 The intermittent mechanical ventilation system shall operate at least one hour out of every four.
5.6 The system shall have a manual control and automatic control, such as a 24-hour clock timer.
5.7 At the time of final inspection, the automatic control shall be set to operate the whole house fan according to the schedule used to calculate the whole house fan sizing.
5.8 A label shall be affixed to the control that reads "Whole House Ventilation (see operating instructions)."
EXCEPTION:
Engineered central ventilation systems serving dwelling units or sleeping units are not required to have individual controls for each dwelling unit or sleeping unit when designed for continuous operation and approved by the code official.
403.8.3 Outdoor air intake locations. Outdoor air intakes shall be classified as either operable openings or mechanical air intakes and shall be located per the following criteria. The intake locations for operable openings and mechanical air intakes shall comply with the following:
1. Openings for mechanical air intakes shall comply with Section 401.4. Operable openings shall comply with Section 401.4 items 2 and 4 only.
2. Intake openings shall not be located closer than 10 feet from an appliance vent outlet unless such vent outlet is 3 feet above the outdoor air inlet. The vent shall be permitted to be closer if specifically allowed by Chapter 8 or by the International Fuel Gas Code.
3. Intake openings shall be located where they will not pick up objectionable odors, fumes, or flammable vapors.
4. Intake openings shall be located where they will not take air from a hazardous or unsanitary location.
5. Intake openings shall be located where they will not take air from a room or space having a fuel-burning appliances.
6. Intake openings shall not be located closer than 10 feet from a vent opening of a plumbing drainage system unless the vent opening is at least 3 feet above the air inlet.
7. Intake openings shall not be located where they will take air from an attic, crawl space, or garage.
8. Intake openings shall not be located on asphalt roofs unless it is shown that no other location is permissible. In such cases, the inlet opening shall be located a minimum of 2 feet from the nearest surface of the asphalt roofing, measured from the intake opening.
403.8.4 Local exhaust ventilation requirements. Local exhaust ventilation systems shall exhaust at least the volume of air required for exhaust in Table 403.3. Exhaust shall be provided in each kitchen, bathroom, water closet, laundry area, indoor swimming pool, spa, and other room where water vapor or cooking odor is produced.
403.8.4.1 Local exhaust systems. Exhaust systems shall be designed and installed to meet all of the criteria below:
1. Local exhaust shall be discharged outdoors.
2. Exhaust outlets shall comply with Section 501.3.
3. Pressure equalization shall comply with Section 501.4.
4. Exhaust ducts in systems which are designed to operate intermittently shall be equipped with back-draft dampers.
5. All exhaust ducts in unconditioned spaces shall be insulated to a minimum of R-4.
6. Terminal outlet elements shall have at least the equivalent net free area of the ductwork.
7. Terminal outlet elements shall be screened or otherwise protected as required by Section 501.3.2.
8. Exhaust fans in separate dwelling units or sleeping units shall not share common exhaust ducts unless the system is engineered for this operation.
9. Where permitted by Chapter 5, multiple local exhaust ducts may be combined. If more than one of the exhaust fans in a dwelling unit or sleeping unit shares a common exhaust duct then each exhaust fan shall be equipped with a back-draft damper to prevent the recirculation of exhaust air from one room to another room via the exhaust ducting system.
403.8.4.2 Local exhaust fans. Exhaust fan construction and sizing shall meet the following criteria.
1. Exhaust fans shall be tested and rated in accordance with the airflow and sound rating procedures of the Home Ventilating Institute (HVI 915, HVI Loudness Testing and Rating Procedure, HVI 916, HVI Airflow Test Procedure, and HVI 920, HVI Product Performance Certification Procedure).
EXCEPTION:
Where a range hood or down draft exhaust fan is used for local exhaust for a kitchen, the device is not required to be rated per these standards.
2. Installation of the system or equipment shall be carried out in accordance with manufacturers' installation instructions.
3. Fan airflow rating and duct system shall be designed and installed to deliver at least the exhaust airflow required by Table 403.3. The airflows required refer to the delivered airflow of the system as installed and tested using a flow hood, flow grid, or other airflow measurement device.
EXCEPTIONS:
1. An exhaust airflow rating at a pressure of 0.25 in. w.g. may be used, provided the duct sizing meets the prescriptive requirements of Table 403.8.4.2.
 
2. Where a range hood or down draft exhaust fan is used to satisfy the local exhaust requirements for kitchens, the range hood or down draft exhaust shall not be less than 100 cfm at 0.10 in. w.g.
TABLE 403.8.4.2
PRESCRIPTIVE EXHAUST DUCT SIZING
Fan Tested cfm at 0.25 inches w.g.
Minimum Flex Diameter
Maximum Length
in Feet
Minimum Smooth Diameter
Maximum Length in Feet
Maximum Elbows1
50
 
4 inches
 
25
4 inches
 
70
3
 
50
 
5 inches
 
90
5 inches
 
100
3
 
50
 
6 inches
 
No Limit
6 inches
 
No Limit
3
 
80
 
4 inches2
 
NA
4 inches
 
20
3
 
80
 
5 inches
 
15
5 inches
 
100
3
 
80
 
6 inches
 
90
6 inches
 
No Limit
3
 
100
 
5 inches2
 
NA
5 inches
 
50
3
 
100
 
6 inches
 
45
6 inches
 
No Limit
3
 
125
 
6 inches
 
15
6 inches
 
No Limit
3
 
125
 
7 inches
 
70
7 inches
 
No Limit
3
 
1.
 
For each additional elbow, subtract 10 feet from length.
2.
 
Flex ducts of this diameter are not permitted with fans of this size.
403.8.5 Whole house ventilation requirements. Each dwelling unit or sleeping unit shall be equipped with one of the following four types of mechanical whole house ventilation systems: A system using exhaust fans (see Section 403.8.6); a system integrated with forced-air systems (see Section 403.8.7); a system using supply fans (see Section 403.8.8); or a heat or energy recovery ventilation system (see Section 403.8.9). The whole house exhaust system is permitted to be one of the local exhaust systems required by Section 403.8.4 as long as the requirements of this section, in addition to the requirements of Section 403.8.5, are met.
EXCEPTION:
Additions, alterations, renovations or repairs to a mechanical system that is part of a building addition with less than 500 square feet of conditioned floor area are exempt from the requirements for whole house ventilation systems, Section 403.8.5.
403.8.5.1 Outdoor air. Outdoor air shall be distributed to each habitable space.
Where outdoor air supply intakes are separated from exhaust vents by doors, means shall be provided to ensure airflow to all separated habitable spaces by installing distribution ducts, installed grilles, transoms, doors undercut to a minimum of 1/2-inch above the surface of the finish floor covering, or other similar means where permitted by the International Building Code.
The mechanical system shall operate continuously to supply at least the volume of outdoor air required in Table 403.3 or Table 403.8.1.
EXCEPTION:
Intermittently operating ventilation systems: The whole house mechanical ventilation system is permitted to operate intermittently where the system has controls that enable operation for not less than 25 percent of each 4-hour segment and the ventilation rate prescribed in Table 403.3 or Table 403.8.1 is multiplied by the factor determined in accordance with Table 403.8.5.1.
TABLE 403.8.5.1
INTERMITTENT WHOLE HOUSE MECHANICAL VENTILATION RATE FACTORSa, b
RUN-TIME PERCENTAGE IN EACH 4-HOUR SEGMENT
25%
33%
50%
66%
75%
100%
Factora
4
3
2
1.5
1.3
1.0
 
a For ventilation system run-time values between those given, the factors are permitted to be determined by interpolation.
 
b Extrapolation beyond the table is prohibited.
403.8.5.2 Whole house supply system general requirements. Whole house ventilation systems integrated with a forced-air system, systems using supply fans and systems using a heat or energy recovery ventilation system shall comply with the following.
1. Outdoor air louvers shall be adequately sized for the required airflow and shall comply with Section 401.5. Outdoor air intake locations shall comply with mechanical air intakes requirements of Section 403.8.3.
2. Outdoor air ducts for dedicated or central supply systems and exhaust ducts for heat or energy recovery systems shall be provided with a means for balancing the system to the required airflow via balance dampers or other devices.
3. Outdoor air ducts for dedicated or central systems shall be provided with motorized dampers.
EXCEPTIONS:
1. Outdoor air ducts at heat or energy recovery ventilation systems are not required to have motorized dampers.
 
2. Outdoor air ducts at continuous ventilation systems are not required to have motorized dampers.
4. Outdoor air ducts in the conditioned space shall be insulated to a minimum of R-4. In heat or energy recovery ventilation systems, ducts upstream of the heat exchanger shall also be insulated to at least R-4.
5. All outdoor air ducts shall be designed and installed to deliver at least the outdoor airflow required by Section 403.8.5.1. The airflows required refer to the delivered airflow of the system as installed and tested using a flow hood, flow grid, or other airflow measurement device.
EXCEPTION:
The outdoor air duct for supply fan systems and heat or energy recovery systems may be prescriptively sized per Table 403.8.5.2 for dedicated outdoor air ducts upstream of the supply fan. Supply fans shall have the capacity to provide the amount of outdoor air required by Section 403.8.5.1 at 0.40 in. w.g. as per HVI 916 (April 1995). When prescriptively sized the system shall be tested and balanced using a flow hood, flow-grid, or other airflow measurement device.
6. Whole house ventilation controls for intermittent operation shall allow concurrent operation of the forced-air fan and the associated outdoor air motorized damper.
7. Whole house ventilation controls for continuous operation shall be provided at the forced-air fan.
EXCEPTION:
Engineered central ventilation systems serving dwelling units or sleeping units are not required to have individual controls for each dwelling or sleeping unit when designed for continuous operation and approved by the code official.
TABLE 403.8.5.2
PRESCRIPTIVE SUPPLY FAN DUCT SIZING
Supply Fan Tested cfm at 0.40" w.g.
Specified Volume from Table 408.1
Minimum Smooth Duct Diameter
Minimum Flexible Duct Diameter
50 - 90 cfm
4 inch
 
5 inch
 
90 - 150 cfm
5 inch
 
6 inch
 
150 - 250 cfm
6 inch
 
7 inch
 
250 - 400 cfm
7 inch
 
8 inch
 
403.8.6 Whole house ventilation with exhaust fan systems. This section establishes minimum requirements for mechanical whole house ventilation systems using exhaust fans.
403.8.6.1 Outdoor air. Exhaust fan only ventilation systems shall provide outdoor air to each occupiable space through one of the following methods:
1. Outdoor air may be drawn through air inlets installed in exterior walls or windows. The air inlets shall comply with all of the following:
1.1. Inlets shall have controllable, secure openings and shall be designed to not compromise the thermal properties of the building envelope.
1.2. Inlets shall be accessible to occupants, including compliance with Section 1109.13 of the International Building Code for designated accessible units, Type A units and Type B units.
1.3. Inlets shall be screened or otherwise protected from entry by insects, leaves, or other material.
1.4. Inlets shall provide not less than 4 square inches of net free area of opening for each 10 cfm of outdoor air required in Table 403.3 or Table 403.8.1.
1.5. Any inlet or combination of inlets which provide 10 cfm at 10 Pascals as determined by the Home Ventilation Institute Air Flow Test Standard (HVI 901 (November 1996)) are deemed equivalent to 4 square inches of net free area.
1.6. Each occupiable space shall have a minimum of one air inlet that has a minimum of 4 square inches of net free area.
2. ((In high-rise buildings,)) Outdoor air may be drawn in through ((operable windows, doors, louvers or other)) operable openings to the outdoors. ((Exterior spaces shall have a minimum openable area of 4 percent of the total floor area being ventilated.)) Each habitable space shall be provided with operable openings with an openable area of not less than 4 square inches of net free area of opening for each 10 cfm of outdoor air required by Table 403.3.1.1 or Table 403.8.1. Doors exiting to a corridor, court or public way shall not be used to provide outdoor air. The operable openings shall comply with the following:
2.1. Openings shall be controllable, securable, and shall be designed to not compromise the thermal properties of the building envelope.
2.2. Openings shall be accessible to occupants, including compliance with Section 1109.13 of the International Building Code for designated accessible units, Type A units and Type B units.
2.3 Openings shall be screened or otherwise protected from entry by leaves or other material.
3. For interior adjoining spaces without outdoor air openings, one of the following two options shall be used to ventilate the interior adjoining space:
3.1. Provide a whole house transfer fan at the interior adjoining space sized to provide a minimum of the ventilation rate required per Section 403.8.5.1. The transfer fan shall circulate air between the interior room or space and the adjacent habitable space. The transfer fan may operate continuously or intermittently using controls per Section 403.8.2.
3.2. Provide a permanent opening to the interior adjoining space. Opening shall be unobstructed and shall have an area of not less than 8 percent of the floor area of the interior adjoining space, but not less than 25 square feet.
403.8.6.2 Outside air intake locations. All outside air intake opening types described in Section 403.8.6.1 shall be classified operable openings and shall not be classified as mechanical air intakes. The intake locations shall comply with Section 403.8.3.
403.8.6.3 Whole house exhaust system. Whole house exhaust system shall be designed and installed to meet all of the applicable criteria below:
1. Whole house ventilation exhaust shall be discharged outdoors.
2. Exhaust outlets shall comply with Section 501.2.
3. Exhaust ducts in systems which are designed to operate intermittently shall be equipped with back-draft dampers.
4. All exhaust ducts in unconditioned spaces shall be insulated to a minimum of R-4.5. Terminal outlet elements shall have at least the equivalent net free area of the ductwork.
5. Terminal outlet elements shall be screened or otherwise protected as required by Section 501.2.2.
6. One of the required local exhaust fans for the laundry room or bathroom may be designated as the whole house exhaust fan.
7. Exhaust fans in separate dwelling units or sleeping units shall not share common exhaust ducts unless the system is engineered for this operation.
8. Where permitted by Chapter 5 whole house exhaust ducts may be combined with other local exhaust ducts. If more than one of the exhaust fans in a dwelling unit or sleeping unit shares a common exhaust duct then each exhaust fan shall be equipped with a back-draft damper to prevent the recirculation of exhaust air from one room to another room via the exhaust ducting system.
403.8.6.4 Whole house exhaust and transfer fans. Exhaust fan construction and sizing shall meet the following criteria.
1. Exhaust and transfer fans shall be tested and rated in accordance with the airflow and sound rating procedures of the Home Ventilating Institute (HVI 915, HVI Loudness Testing and Rating Procedure, HVI 916, HVI Airflow Test Procedure, and HVI 920, HVI Product Performance Certification Procedure).
2. Installation of system or equipment shall be carried out in accordance with manufacturers' design requirements and installation instructions.
3. Fan airflow rating and duct system shall be designed and installed to deliver at least the outdoor airflow required by Table 403.3 or Table 403.8.1. The airflows required refer to the delivered airflow of the system as installed and tested using a flow hood, flow grid, or other airflow measurement device.
EXCEPTION:
An airflow rating at a pressure of 0.25 in. w.g. may be used, provided the duct sizing meets the prescriptive requirements of Table 403.8.5.2.
403.8.6.5 Fan noise. Whole house exhaust and transfer fans located 4 feet or less from the interior grille shall have a sone rating of 1.0 or less measured at 0.10 inches water gauge. Manufacturer's noise ratings shall be determined as per HVI 915. Remotely mounted fans shall be acoustically isolated from the structural elements of the building and from attached ductwork using insulated flexible duct or other approved material.
403.8.7 Whole house ventilation integrated with forced-air systems. This section establishes minimum requirements for mechanical whole house ventilation systems using forced-air system fans.
403.8.7.1 Outdoor air. Forced-air system fan ventilation systems shall provide outdoor air through one of the following methods:
1. A dedicated outdoor air louver and outdoor air duct for each dwelling unit or sleeping unit shall supply outdoor air to the return side of the forced-air system fan; or
2. A central outdoor air delivery system that supplies multiple dwelling units or sleeping units shall supply outdoor air to the return side of the forced air system fan.
3. For interior adjoining spaces without outdoor air openings, one of the following two options shall be used to ventilate the interior adjoining space:
3.1. Provide a whole house transfer fan at the interior adjoining space sized to provide a minimum of the ventilation rate required per Section 403.8.5.1. The transfer fan shall circulate air between the interior room or space and the adjacent habitable space. The transfer fan may operate continuously or intermittently using controls per Section 403.8.2.
3.2. Provide a permanent opening to the interior adjoining space. Opening shall be unobstructed and shall have an area of not less than 8 percent of the floor area of the interior adjoining space, but not less than 25 square feet.
403.8.7.2 Whole house forced-air system. Where outdoor air is provided to each habitable dwelling unit or sleeping unit by a forced-air system, the outdoor air duct shall be connected to the return air stream at a point within 4 feet upstream of the forced-air unit. It shall not be connected directly to the forced-air unit cabinet in order to prevent thermal shock to the heat exchanger. At a minimum, filtration of the outdoor air shall be provided at the forced-air unit. The filter shall be accessible for regular maintenance and replacement. The filter shall have a Minimum Efficiency Rating Value (MERV) of at least 6.
Each habitable space in the dwelling or sleeping unit shall be served by a forced-air system with outdoor air connection.
403.8.8 Whole house ventilation with supply fan systems. This section establishes minimum requirements for mechanical whole house ventilation systems using supply fan systems.
403.8.8.1 Outdoor air. Supply fan ventilation systems shall provide outdoor air through one of the following methods:
1. A dedicated outdoor air louver and outdoor air duct for each dwelling unit or sleeping unit shall supply outdoor air to a supply fan; or
2. A central outdoor air supply fan system shall distribute unconditioned or conditioned air to multiple dwelling units or sleeping units.
3. For interior adjoining spaces without outdoor air openings, one of the following two options shall be used to ventilate the interior adjoining space:
3.1. Provide a whole house transfer fan at the interior adjoining space sized to provide a minimum of the ventilation rate required per Section 403.8.5.1. The transfer fan shall circulate air between the interior room or space and the adjacent habitable space. The transfer fan may operate continuously or intermittently using controls per Section 403.8.2.
3.2. Provide a permanent opening to the interior adjoining space. Opening shall be unobstructed and shall have an area of not less than 8 percent of the floor area of the interior adjoining space, but not less than 25 square feet.
403.8.8.2 Whole house supply system. Where outdoor air is provided to each habitable dwelling unit or sleeping unit by supply fan systems the outdoor air shall be filtered.
The system filter may be located at the intake device or inline with the fan. The filter shall be accessible for regular maintenance and replacement. The filter shall have a Minimum Efficiency Rating Value (MERV) of at least 6.
403.8.9 Whole house ventilation with heat recovery or energy recovery ventilation systems. This section establishes minimum requirements for mechanical whole house ventilation systems using heat recovery or energy recovery ventilation systems.
403.8.9.1 Outdoor air. Heat recovery or energy recovery ventilation systems shall provide outdoor air through one of the following methods:
1. A dedicated outdoor air louver and outdoor air duct for each dwelling unit or sleeping unit shall supply outdoor air to the heat recovery or energy recovery ventilator; or
2. A central outdoor air heat recovery or energy recovery unit shall distribute conditioned air to multiple dwelling units or sleeping units.
3. For interior adjoining spaces without outdoor air openings, one of the following two options shall be used to ventilate the interior adjoining space:
3.1. Provide a whole house transfer fan at the interior adjoining space sized to provide a minimum of the ventilation rate required per Section 403.8.5.1. The transfer fan shall circulate air between the interior room or space and the adjacent habitable space. The transfer fan may operate continuously or intermittently using controls per Section 403.8.2.
3.2. Provide a permanent opening to the interior adjoining space. Opening shall be unobstructed and shall have an area of not less than 8 percent of the floor area of the interior adjoining space, but not less than 25 square feet.
403.8.9.2 Whole house heat recovery ventilator system. Where outdoor air is provided to each habitable dwelling unit or sleeping unit by heat recovery or energy recovery ventilator the outdoor air shall be filtered. The filter shall be located on the upstream side of the heat exchanger in both the intake and exhaust airstreams with a Minimum Efficiency Rating Value (MERV) of at least 6. The system filter may be located at the intake device or inline with the fan. The filter shall be accessible for regular maintenance and replacement.
Each habitable space in the dwelling or sleeping unit shall be served by a heat recovery ventilator with outdoor air connection.
403.8.10 Local exhaust ventilation and whole house ventilation alternate performance or design requirements. In lieu of complying with Sections 403.8.4 or 403.8.5 compliance with the section shall be demonstrated through engineering calculations by an engineer licensed to practice in the state of Washington or by performance testing. Documentation of calculations or performance test results shall be submitted to and approved by the building official. Performance testing shall be conducted in accordance with approved test methods.
403.8.11 Alternate systems. When approved by the code official, systems designed in accordance with ASHRAE Standard 62.2 shall be permitted.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
NEW SECTION
WAC 51-52-0407 Section 407Ambulatory care facilities and Group I-2 occupancies.
407.1 General. Mechanical ventilation for health care facilities licensed by Washington state shall be designed and installed in accordance with this code and the following provisions of the Washington Administrative Code (WAC):
1. Mechanical ventilation in ambulatory care facilities shall comply with chapter 246-330 WAC.
2. Mechanical ventilation for acute care hospitals shall comply with chapter 246-320 WAC.
3. Mechanical ventilation for nursing homes shall comply with chapter 388-97 WAC.
Mechanical ventilation for unlicensed ambulatory care facilities shall be designed and installed in accordance with this code and ASHRAE 170.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0504 Section 504Clothes dryer exhaust.
((504.6.4.1 Specified length. The maximum length of the exhaust duct shall be 35 feet (10668 mm) from the connection to the transition duct from the dryer to the outlet terminal. Where fittings are used, the maximum length of the exhaust duct shall be reduced in accordance with Table 504.6.4.1.
The maximum length of the duct may be increased in an engineered exhaust system when a listed and labeled exhaust booster fan is installed in accordance with the manufacturer's installation instructions.
504.7.1 Protection required. Protective shield plates shall be provided in accordance with Section 504.6.7.
504.8)) 504.4 Exhaust installation. Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper located where the duct terminates. Dryer exhaust ducts may terminate at exterior wall louvers with openings spaced not less than 1/2-inch in any direction.
Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the exhaust flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent or chimney. Clothes dryer exhaust ducts shall not extend into or through ducts or plenums.
Domestic dryer exhaust ducts may terminate at a common exhaust transition piece where each duct has an independent back-draft damper.
504.10 Common exhaust systems for clothes dryers located in multistory structures. Where a common multistory duct system is designed and installed to convey exhaust from multiple clothes dryers, the construction of the system shall be in accordance with all of the following:
1. The shaft in which the duct is installed shall be constructed and fire-resistance rated as required by the International Building Code.
2. Dampers shall be prohibited in the exhaust duct. Penetrations of the shaft and ductwork shall be protected in accordance with Section 607.5.5, Exception 2.
3. Rigid metal ductwork shall be installed within the shaft to convey the exhaust. The ductwork shall be constructed of sheet steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) and in accordance with SMACNA Duct Construction Standards.
4. The ductwork within the shaft shall be designed and installed without offsets.
5. The exhaust fan motor design shall be in accordance with Section 503.2.
6. The exhaust fan motor shall be located outside of the airstream.
7. The exhaust fan shall run continuously, and shall be connected to a standby power source.
8. Exhaust fan operation shall be monitored in an approved location and shall initiate an audible or visual signal when the fan is not in operation.
9. Makeup air shall be provided for the exhaust system to maintain the minimum flow for the exhaust fan when the dryers are not operating. Additionally, makeup air shall be provided when required by Section 504.5.
10. A cleanout opening shall be located at the base of the shaft to provide access to the duct to allow for cleaning and inspection. The finished opening shall be not less than 12 inches by 12 inches (305 mm by 305 mm).
11. Screens shall not be installed at the termination.
12. The common multistory duct system shall serve only clothes dryers and shall be independent of other exhaust systems.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0505 Section 505Domestic kitchen exhaust equipment.
505.1 Domestic systems. Where domestic range hoods and domestic appliances equipped with downdraft exhaust are ((located within dwelling units)) provided, such hoods and appliances shall discharge to the outdoors through sheet metal ducts constructed of galvanized steel, stainless steel, aluminum or copper. Such ducts shall have smooth inner walls, shall be air tight, shall be equipped with a backdraft damper and shall be independent of all other exhaust systems.
Domestic kitchen exhaust ducts may terminate with other domestic dryer exhaust and residential local exhaust ducts at a common exhaust transition piece where each duct has an independent back-draft damper.
Listed and labeled exhaust booster fans shall be permitted when installed in accordance with the manufacturer's installation instructions.
EXCEPTIONS:
1. In other than Group I-1 and I-2, where installed in accordance with the manufacturer's installation instructions and where mechanical ventilation is otherwise provided in accordance with Chapter 4, listed and labeled ductless range hoods shall not be required to discharge to the outdoors.
 
2. Ducts for domestic kitchen cooking appliances equipped with downdraft exhaust systems shall be permitted to be constructed of Schedule 40 PVC pipe and fittings provided that the installation complies with all of the following:
 
2.1. The duct shall be installed under a concrete slab poured on grade.
 
2.2. The underfloor trench in which the duct is installed shall be completely backfilled with sand or gravel.
 
2.3. The PVC duct shall extend not more than 1 inch (25 mm) above the indoor concrete floor surface.
 
2.4. The PVC duct shall extend not more than 1 inch (25 mm) above grade outside of the building.
 
2.5. The PVC ducts shall be solvent cemented.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0506 Section 506Commercial kitchen hood ventilation system ducts and exhaust equipment.
506.3.9 Grease duct cleanout location, spacing and installation.
506.3.9.1 Grease duct horizontal cleanout. Cleanouts located on horizontal sections of ducts shall:
1. Be spaced not more than 20 feet (6096 mm) apart.
2. Be located not more than 10 feet (3048 mm) from changes in direction that are greater than 45 degrees (0.79 rad).
3. Be located on the bottom only where other locations are not available and shall be provided with internal damming of the opening such that grease will flow past the opening without pooling. Bottom cleanouts and openings shall be approved for the application and installed liquid-tight.
4. Not be closer than 1 inch (25.4 mm) from the edges of the duct.
5. Have dimensions of not less than 12 inches by 12 inches (305 mm by 305 mm). Where such dimensions preclude installation, the openings shall be not less than 12 inches (305 mm) on one side and shall be large enough to provide access for cleaning and maintenance.
6. Shall be located at grease reservoirs.
506.3.9.2 Grease duct vertical cleanouts. Where ducts pass vertically through floors, cleanouts shall be provided. A minimum of one cleanout shall be provided on each floor. Cleanout openings shall be not less than 1 1/2 inches (38 mm) from all outside edges of the duct or welded seams.
506.3.11 Grease duct enclosures. A commercial kitchen grease duct serving a Type I hood that penetrates a ceiling, wall, floor or any concealed spaces shall be enclosed from the point of penetration to the outlet terminal. In-line exhaust fans not located outdoors shall be enclosed as required for grease ducts. A duct shall penetrate exterior walls only at locations where unprotected openings are permitted by the International Building Code. The duct enclosure shall serve a single grease duct and shall not contain other ducts, piping or wiring systems. Duct enclosures shall be ((either)) a shaft enclosure in accordance with Section 506.3.11.1, a field-applied enclosure assembly in accordance with Section 506.11.2 or a factory-built enclosure assembly in accordance with Section 506.3.11.3. Duct enclosures shall have a fire-resistance rating of not less than that of the assembly penetrated. The duct enclosure need not exceed 2 hours but shall not be less than 1 hour. ((Duct enclosures shall be as prescribed by Section 506.3.11.1, 506.3.11.2 or 506.3.11.3.)) Fire dampers and smoke dampers shall not be installed in grease ducts.
EXCEPTION:
A duct enclosure shall not be required for a grease duct that penetrates only a nonfire-resistance-rated roof/ceiling assembly.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0507 Section 507Commercial kitchen hoods.
((507.2.1 Type I hoods. Type I hoods shall be installed where cooking appliances produce grease or smoke. Type I hoods shall be installed over medium-duty, heavy-duty and extra-heavy-duty cooking appliances. Type I hoods shall be installed over light-duty cooking appliances that produce grease or smoke.
EXCEPTIONS:
1. A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm in accordance with Section 17 of UL 710B.
 
2. A Type I hood shall not be required in an R-2 type occupancy with not more than 16 residents.
507.2.3)) 507.1.2 Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I, Type II or residential hoods as required for the type of appliances and processes in accordance with Table ((507.2.2)) 507.1.2 and Sections 507.2((, 507.2.1 and 507.2.2.)) and 507.3. Domestic cooking appliances utilized for domestic purposes shall comply with Section 505.
TABLE ((507.2.2)) 507.1.2
TYPE OF HOOD REQUIRED FOR DOMESTIC COOKING APPLIANCES
IN THE FOLLOWING SPACESa, b
Type of Space
Type of Cooking
Type of Hood
Church
1. Boiling, steaming and warming precooked food
Type II hood
 
2. Roasting, pan frying and deep frying
Type I hood
Community or party room in apartment and condominium
1. Boiling, steaming and warming precooked food
Residential hoodc or Type II hoodd
 
2. Roasting, pan frying and deep frying
Type I hood
Day care
1. Boiling, steaming and warming precooked food
Residential hoodc or Type II hoodd
 
2. Roasting, pan frying and deep frying
Type I hood
Dormitory, boarding home, nursing home
1. Boiling, steaming and warming precooked food
Type II hood
 
2. Roasting, pan frying and deep frying
Type I hood
Office lunch room
1. Boiling, steaming and warming precooked food
Residential hoodc or Type II hoodd
 
2. Roasting, pan frying and deep frying
Type I hood
 
a Commercial cooking appliances shall comply with Section 507.2.
 
b Requirements in this table apply to electric or gas fuel appliances only. Solid fuel appliances or charbroilers require Type I hoods.
 
c Residential hood shall ventilate to the outside.
 
d Type II hood required when more than one appliance is used.
507.2 Type I hoods. Type I hoods shall be installed where cooking appliances produce grease or smoke as a result of the cooking process. Type I hoods shall be installed over medium-duty, heavy-duty and extra-heavy-duty cooking appliances.
EXCEPTIONS:
1. A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm in accordance with Section 17 of UL 710B.
 
2. A Type I hood shall not be required in an R-2 type occupancy with not more than 16 residents.
NEW SECTION
WAC 51-52-0515 Section 515Waste or linen chute venting.
515.1 General. Waste or linen chutes shall be gravity vented per NFPA 82.
EXCEPTION:
Waste or linen chutes may be mechanically ventilated by an exhaust fan. The exhaust fan shall be located outside the building at the top of the chute.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0601 Section 601General.
601.2 Air movement in egress elements. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts.
EXCEPTIONS:
1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor closets, shall be permitted provided that each such corridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor.
 
2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited.
 
3. Where located within tenant spaces of one thousand square feet (93 m2) or less in area, utilization of corridors for conveying return air is permitted.
 
4. Incidental air movement from pressurized rooms within health care facilities, provided that the corridor is not the primary source of supply or return to the room.
 
5. Where such air is part of an engineered smoke control system.
 
6. Air supplied to corridors serving residential occupancies shall not be considered as providing ventilation air to the dwelling units and sleeping units subject to the following:
 
6.1 The air supplied to the corridor is one hundred percent outside air; and
 
6.2 The units served by the corridor have conforming ventilation air independent of the air supplied to the corridor; and
 
6.3 For other than high-rise buildings, the supply fan will automatically shut off upon activation of corridor smoke detectors which shall be spaced at no more than thirty feet (9,144 mm) on center along the corridor; or
 
6.4 For high-rise buildings, corridor smoke detector activation will close required smoke/fire dampers at the supply inlet to the corridor at the floor receiving the alarm.
NEW SECTION
WAC 51-52-0602 Section 602Duct construction and installation.
602.1 General. Supply, return, exhaust, relief and ventilation air plenums shall be limited to uninhabited crawl spaces, areas above a ceiling or below the floor, attic spaces and mechanical equipment rooms. Plenums shall be limited to one fire area. Air systems that serve multiple fire areas shall be ducted from the boundary of the fire area served directly to the air-handling equipment. Fuel-fired appliances shall not be installed within a plenum.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0605 Section 605Air filters.
605.1 General. Heating and air-conditioning systems shall be provided with approved air filters. Filters shall be installed such that all return air, outdoor air and makeup air is filtered upstream from any heat exchanger or coil. Filters shall be installed in an approved convenient location. Liquid adhesive coatings used on filters shall have a flash point not lower than 325°F (163°C).
EXCEPTION:
Chilled beams that are designed to operate above the space dew point temperature do not require filtration at the terminal device.
605.4 Particulate matter removal. Particulate matter filters or air cleaners having a minimum efficiency reporting value (MERV) of not less than 6 for ducted air handlers and not less than 4 for ((unducted air handlers)) ductless mini-split systems shall be provided upstream of all cooling coils or other devices with wetted surfaces through which air is supplied to an occupiable space.
AMENDATORY SECTION (Amending WSR 10-03-099, filed 1/20/10, effective 7/1/10)
WAC 51-52-0606 Section 606Smoke detection systems control.
606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm (0.9 m3/s), in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances.
EXCEPTIONS:
1. Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4.
 
2. Smoke detectors are not required in the return air system where all of the return air is exhausted and not recirculated back to any portion of the building. Additionally, smoke detectors are not required in the supply system that provides the make-up air for the exhaust system.
606.2.2 Common supply and return air systems. Where multiple air-handling systems share common supply or return air ducts or plenums with a combined design capacity greater than 2,000 cfm (0.9 m3/s), the return air system shall be provided with smoke detectors in accordance with Section 606.2.1.
EXCEPTION:
Individual smoke detectors shall not be required for each fan-powered terminal unit, provided that such units do not have an individual design capacity greater than 2,000 cfm (0.9 m3/s) and will be shut down by activation of one of the following:
 
1. Smoke detectors required by Sections 606.2.1 and 606.2.3.
 
2. An approved area smoke detector system located in the return air plenum serving such units.
 
3. An area smoke detector system as prescribed in the exception to Section 606.2.1.
In all cases, the smoke detectors shall comply with Sections 606.4 and 606.4.1.
The shut down of fan-powered terminal units may be performed by a building automation system upon activation of smoke detection as described in Section 606.2.2, Exception Items 1, 2, or 3. The building automation system is not required to be listed as a smoke control system and is not required to comply with UL Standard 864: Standard for Control Units and Accessories for Fire Alarm Systems.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-0928 Section 928Evaporative cooling equipment.
((928.1 General. Evaporative cooling equipment shall:
1. Be installed in accordance with the manufacturer's instructions.
2. Be installed on level platforms in accordance with Section 304.10.
3. Have openings in exterior walls or roofs flashed in accordance with the International Building Code.
4. Be provided with potable water backflow protection in accordance with backflow requirements in the plumbing code.
5. Have air intake opening locations in accordance with Section 401.4.))
NEW SECTION
WAC 51-52-1107 Section 1107Refrigerant piping.
1107.2 Piping location. Refrigerant piping that crosses an open space that affords passageway in any building shall be not less than 7 feet 3 inches (2210 mm) above the floor unless the piping is located against the ceiling of such space. Refrigerant piping shall not be placed in the following locations:
1. A fire-resistance-rated exit access corridor.
2. An interior exit stairway or ramp.
3. An exit passageway.
4. Any elevator, dumbwaiter, or other shaft containing a moving object.
5. A shaft that has openings to a dwelling unit or sleeping unit.
6. A shaft that has openings to a fire-resistance-rated exit access corridor, interior exit stairway or ramp, or exit passageway.
NEW SECTION
WAC 51-52-1200 Chapter 12Hydronic piping.
1209.5.1 Slab-on-grade installation. Radiant piping utilized in slab-on-grade applications shall be provided with insulating materials installed beneath the piping as required by the Washington State Energy Code.
1210.7.6 Expansion tanks. Shutoff valves shall be installed at connections to expansion tanks. A method of draining the expansion tank downstream of the shutoff valve shall be provided.
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-1500 Chapter 15Referenced standards.
The following referenced standards are added to Chapter 15.
ASHRAE
((62.2-2010)) 62.2-2013 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-21101 Section 101General.
101.2 Scope. This code shall apply to the installation of fuel gas piping systems, fuel gas utilization equipment, gaseous hydrogen systems and regulated accessories in accordance with Section 101.2.1 through 101.2.5.
EXCEPTIONS:
1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the International Residential Code.
 
2. The standards for liquefied petroleum gas installations shall be the ((2011)) 2014 Edition of NFPA 58 (Liquefied Petroleum Gas Code) and the ((2012)) 2015 Edition of ANSI Z223.1/NFPA 54 (National Fuel Gas Code).
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-21401 Chapter 4Gas piping installations.
((401.9 Identification. Each length of pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identification of the manufacturer.
EXCEPTION:
The manufacturer identification for fittings and pipe nipples shall be on each piece or shall be printed on the fitting or nipple packaging or provided documentation.))
AMENDATORY SECTION (Amending WSR 13-04-053, filed 2/1/13, effective 7/1/13)
WAC 51-52-21601 Chapter 6Specific appliances.
((614.7.1 Protection required. Protective shield plates shall be provided in accordance with Section 614.6.3.))