WSR 16-16-027
PROPOSED RULES
BUILDING CODE COUNCIL
[Filed July 22, 2016, 4:38 p.m.]
Original Notice.
Preproposal statement of inquiry was filed as WSR 16-11-115.
Title of Rule and Other Identifying Information: Amendments to chapter 51-11C WAC, the Washington State Energy Code, commercial provisions.
Hearing Location(s): Fire Department Training Center, 1618 South Rebecca Street, Spokane, WA, on September 9, 2016, at 10 a.m.; and at the DES Presentation Room, 1500 Jefferson S.E., Olympia, WA 98504, on October 14, 2016, at 10 a.m.
Date of Intended Adoption: November 18, 2016.
Submit Written Comments to: Steve Simpson, P.O. Box 41449, Olympia, WA 98504-1449, e-mail sbcc@ga.wa.gov, fax (360) 586-9088, by October 21, 2016.
Assistance for Persons with Disabilities: Contact Peggy Bryden by August 25, 2014 [2016], (360) 407-9280.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: 1. Section C103.6.2 – replaces item 5 into the list of materials to be provided in operating manuals. This item was unintentionally left out when the list moved from Section C408 to Section C103.
2. Section C104.2.4 – specifies duct and pipe systems in the requirements for mechanical inspections. Insulation and air leakage requirements in C403 only apply to ductwork, dampers and piping.
3. Definition for Certified Commissioning Professional – the list of organizations was revised to reflect those currently accredited. The language regarding the ability of the engineer of record to perform commissioning services was revised to provide clarity of intent and enforcement.
4. New definitions for Doors – add definitions for swinging and nonswinging doors, corresponding with the categories in Tables C402.1.3 and C402.1.4.
5. Definition for Luminaire-Level Lighting Control – the definition was modified to clarify the system design and control requirements.
6. Section C401.2.1 – this section was added as a pointer to the new chapter for existing buildings.
7. Section C402.1 – a pointer was added to item 2 to clarify that windows were included in the component performance option.
8. Section C402.1.1.1 – editorial change to clarify that the section contained requirements for semi-heated spaces in addition to those found in other parts of this section.
9. Table C402.1.3 – footnotes b and d were revised. Footnote b adds back in the specifications for thermal spacer blocks and footnote d removes term "below grade walls" since F-factors do not apply to walls.
10. Section C402.1.4.4 – the title of the section was revised to clarify that it applies to walls with steel studs.
11. Table C402.1.4 – footnote b was revised as noted in item 9, above.
12. Section C402.1.5 – equations 4-2 and 4-3 were cleaned up to correct references and terms.
13. Section C402.4.2 – clarifications to the minimum skylight fenestration area specifications.
14. Section C402.4.4 – added clarification that nonopaque doors are intended to be included in the fenestration calculation in the same manner as vertical fenestration.
15. Section C403.2.4.1 – exception 2 was reworded to provide clarity of intent.
16. Section 405.11 – a section is added as a pointer to the commissioning requirements for electrical and lighting systems.
17. Section C406.5 – revisions to the option for on-site renewable energy production to clarify it is based on annual energy production.
18. Section C406.7 – clarification that the section is dealing with water heating energy use.
19. Table C407.5.1(1) – (a) Cooling System: "Same as proposed" is struck after Economizer to eliminate confusion. (b) Fan System: The last sentence regarding DOAS systems is deleted to eliminate confusion.
20. Table C407.5.1(2) – the column for residential systems was eliminated, along with footnote c since these systems are not governed by Section C403.6 as scoped in the title of the table.
21. Sections C408.1/C408.2 – refrigeration systems were inadvertently left out of the commissioning scoping section when they were moved from C403 to C410.
22. Section C410.1 - a sentence is added to allow use of the component performance option. This link was inadvertently omitted when the refrigeration section moved from C403 to C410.
23. Section[s] C410.2/C410.2.1 – these two redundant sections were consolidated into one section.
24. Section C503.6 – correction to references in the lighting section and a backwards phrase.
Reasons Supporting Proposal: RCW 19.27A.025 and 19.27A.045.
Statutory Authority for Adoption: RCW 19.27A.025, 19.27A.045.
Statute Being Implemented: Chapters 19.27, 19.27A, and 34.05 RCW.
Rule is not necessitated by federal law, federal or state court decision.
Name of Proponent: State building code council, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Krista Braaksma, P.O. Box 41011, Olympia, WA 98504-1449, (360) 407-9278; and Enforcement: Local jurisdictions.
No small business economic impact statement has been prepared under chapter 19.85 RCW. The changes being made are intended to provide clarification of existing rules and do not impose or change any technical requirements in the code.
A cost-benefit analysis is not required under RCW 34.05.328. There are no technical changes being made; editorial changes to existing rules are proposed to clarify those rules.
July 22, 2016
Steve K. Simpson
Council Chair
AMENDATORY SECTION (Amending WSR 16-13-089, filed 6/15/16, effective 7/16/16)
WAC 51-11C-10300 Section C103Construction documents.
C103.1 General. Construction documents and other supporting data shall be submitted in one or more sets with each application for a permit. The construction documents shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. Where special conditions exist, the code official is authorized to require necessary construction documents to be prepared by a registered design professional.
EXCEPTION:
The code official is authorized to waive the requirements for construction documents or other supporting data if the code official determines they are not necessary to confirm compliance with this code.
C103.2 Information on construction documents. Construction documents shall be drawn to scale upon suitable material. Electronic media documents are permitted to be submitted when approved by the code official. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed, and show in sufficient detail pertinent data and features of the building, systems and equipment as herein governed. Details shall include, but are not limited to, as applicable:
1. Insulation materials and their R-values.
2. Fenestration U-factors and SHGCs.
3. Area-weighted U-factor and SHGC calculations.
4. Mechanical system design criteria.
5. Mechanical and service water heating system and equipment types, sizes and efficiencies.
6. Economizer description.
7. Equipment and systems controls.
8. Fan motor horsepower (hp) and controls.
9. Duct sealing, duct and pipe insulation and location.
10. Lighting fixture schedule with wattage and control narrative.
11. Location of daylight zones on floor plan.
12. Air barrier details including all air barrier boundaries and associated square foot calculations on all six sides of the air barrier as applicable.
C103.2.1 Building thermal envelope depiction. The building's thermal envelope shall be represented on the construction documents.
C103.3 Examination of documents. The code official shall examine or cause to be examined the accompanying construction documents and shall ascertain whether the construction indicated and described is in accordance with the requirements of this code and other pertinent laws or ordinances.
C103.3.1 Approval of construction documents. When the code official issues a permit where construction documents are required, the construction documents shall be endorsed in writing and stamped "Reviewed for Code Compliance." Such approved construction documents shall not be changed, modified or altered without authorization from the code official. Work shall be done in accordance with the approved construction documents.
One set of construction documents so reviewed shall be retained by the code official. The other set shall be returned to the applicant, kept at the site of work and shall be open to inspection by the code official or a duly authorized representative.
C103.3.2 Previous approvals. This code shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit has been heretofore issued or otherwise lawfully authorized, and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned.
C103.3.3 Phased approval. The code official shall have the authority to issue a permit for the construction of part of an energy conservation system before the construction documents for the entire system have been submitted or approved, provided adequate information and detailed statements have been filed complying with all pertinent requirements of this code. The holders of such permit shall proceed at their own risk without assurance that the permit for the entire energy conservation system will be granted.
C103.4 Amended construction documents. Changes made during construction that are not in compliance with the approved construction documents shall be resubmitted for approval as an amended set of construction documents.
C103.5 Retention of construction documents. One set of approved construction documents shall be retained by the code official for a period of not less than 180 days from date of completion of the permitted work, or as required by state or local laws.
C103.6 Building documentation and close out submittal requirements. The construction documents shall specify that the documents described in this section be provided to the building owner or owner's authorized agent within 180 days of the date of receipt of the certificate of occupancy.
C103.6.1 Record documents. Construction documents shall be updated to convey a record of the completed work. Such updates shall include mechanical, electrical and control drawings red-lined, or redrawn if specified, that show all changes to size, type and locations of components, equipment and assemblies.
C103.6.2 Manuals. An operating and maintenance manual shall be provided for each component, device, piece of equipment, and system ((required to be commissioned)) governed by this code. The manual shall include all of the following:
1. Submittal data indicating all selected options for each piece of equipment.
2. Manufacturer's operation manuals and maintenance manuals for each device, piece of equipment, and system requiring maintenance, except equipment not furnished as part of the project. Required routine maintenance actions, cleaning and recommended relamping shall be clearly identified.
3. Name and address of at least one service agency.
4. Controls system inspection schedule, maintenance and calibration information, wiring diagrams, schematics, and control sequence descriptions. Desired or field-determined setpoints shall be permanently recorded on control drawings at control devices or, for digital control systems, on the graphic where settings may be changed.
5. A narrative of how each system is intended to operate, including recommended setpoints.
C103.6.3 Compliance documentation. All energy code compliance forms and calculations shall be delivered in one document to the building owner as part of the project record documents, manuals, or as a standalone document. This document shall include the specific energy code year utilized for compliance determination for each system. NFRC certificates for the installed windows, list total area for each NFRC certificate, the interior lighting power compliance path (building area, space-by-space) used to calculate the lighting power allowance.
For projects complying with Section C401.2 Item 1, the documentation shall include:
1. The envelop insulation compliance path (prescriptive or component performance).
2. All completed code compliance forms, and all compliance calculations including, but not limited to, those required by sections C402.1.5, C403.2.12.1, C405.4, and C405.5.
For projects complying with Section C401.2 Item 2, the documentation shall include:
1. A list of all proposed envelope component types, areas and U-values.
2. A list of all lighting area types with areas, lighting power allowance, and installed lighting power density.
3. A list of each HVAC system modeled with the assigned and proposed system type.
4. Electronic copies of the baseline and proposed model input and output file. The input files shall be in a format suitable for rerunning the model and shall not consist solely of formatted reports of the inputs.
C103.6.4 Systems operation training. Training of the maintenance staff for equipment included in the manuals required by Section C103.6.2 shall include at a minimum:
1. Review of manuals and permanent certificate.
2. Hands-on demonstration of all normal maintenance procedures, normal operating modes, and all emergency shutdown and start-up procedures.
3. Training completion report.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-10400 Section C104Inspections.
C104.1 General. Construction or work for which a permit is required shall be subject to inspection by the code official or his designated agent, and such construction or work shall remain accessible and exposed for inspection purposes until approved. It shall be the duty of the permit applicant to cause the work to remain accessible and exposed for inspection purposes. Neither the code official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of any material, product, system or building component required to allow inspection to validate compliance with this code.
C104.2 Required inspections. The code official or his designated agent, upon notification, shall make the inspections set forth in Sections C104.2.1 through C104.2.6.
C104.2.1 Footing and foundation inspection. Inspections associated with footings and foundations shall verify compliance with the code as to R-value, location, thickness, depth of burial and protection of insulation as required by the code and approved plans and specifications.
C104.2.2 Insulation and fenestration inspection. Inspections shall be made before application of interior finish and shall verify compliance with the code as to types of insulation and corresponding R-values and their correct location and proper installation; fenestration properties (U-factor, SHGC and VT) and proper installation; and air leakage controls as required by the code and approved plans and specifications.
C104.2.3 Plumbing inspection. Inspections verify compliance as required by the code and approved plans and specifications as to types of insulation and corresponding R-values and protection, required controls and required heat traps.
C104.2.4 Mechanical inspection. Inspections shall verify compliance as required by the code and approved plans and specifications as to installed HVAC equipment type and size, required controls, duct and piping system insulation and corresponding R-value, duct system and damper air leakage and required energy recovery and/or economizers.
C104.2.5 Electrical and lighting inspection. Inspections shall verify compliance as required by the code and approved plans and specifications as to installed lighting systems, components and controls; motors and installation of an electric meter for each dwelling unit.
C104.2.6 Final inspection. The building shall have a final inspection and not be occupied until approved.
C104.3 Reinspection. A building shall be reinspected when determined necessary by the code official.
C104.4 Approved inspection agencies. The code official is authorized to accept reports of approved inspection agencies, provided such agencies satisfy the requirements as to qualifications and reliability relevant to the building components and systems they are inspecting.
C104.5 Inspection requests. It shall be the duty of the holder of the permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code.
C104.6 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the code official for inspection and testing.
C104.7 Approval. After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued by the code official.
C104.7.1 Revocation. The code official is authorized to, in writing, suspend or revoke a notice of approval issued under the provisions of this code wherever the certificate is issued in error, or on the basis of incorrect information supplied, or where it is determined that the building or structure, premise, or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-20203 Section C202.3C.
C-FACTOR (THERMAL CONDUCTANCE). The coefficient of heat transmission (surface to surface) through a building component or assembly, equal to the time rate of heat flow per unit area and the unit temperature difference between the warm side and cold side surfaces (Btu/h ft2 x °F) [W/(m2 x K)].
CERTIFIED COMMISSIONING PROFESSIONAL. An individual who is certified by an ANSI/ISO/IEC 17024:2012 accredited organization to lead, plan, coordinate and manage commissioning teams and implement commissioning processes. The individual's accredited certification required by the referenced standard provides a measured level of experience and competence with the various whole building commissioning processes and ability to deliver quality service. Accredited organizations include, but are not limited to, ((AABC, BCA)) ACG, BCCB, and NEBB. The engineer of record for the project may be ((considered)) approved by the jurisdiction to perform the certified commissioning professional services if ((she/he is qualified to perform)) the individual demonstrates previous experience performing commissioning services for the entire commissioning process.
CIRCULATING HOT WATER SYSTEM. A specifically designed water distribution system where one or more pumps are operated in the service hot water piping to circulate heated water from the water-heating equipment to the fixture supply and back to the water-heating equipment.
CLERESTORY FENESTRATION. See "FENESTRATION."
CLIMATE ZONE. A geographical region based on climatic criteria as specified in this code.
CODE OFFICIAL. The officer or other designated authority charged with the administration and enforcement of this code, or a duly authorized representative.
COEFFICIENT OF PERFORMANCE (COP) - COOLING. The ratio of the rate of heat removal to the rate of energy input, in consistent units, for a complete refrigerating system or some specific portion of that system under designated operating conditions.
COEFFICIENT OF PERFORMANCE (COP) - HEATING. The ratio of the rate of heat removal to the rate of heat delivered to the rate of energy input, in consistent units, for a complete heat pump system, including the compressor and, if applicable, auxiliary heat, under designated operating conditions.
COMMERCIAL BUILDING. For this code, all buildings that are not included in the definition of "Residential buildings."
COMPUTER ROOM. A room whose primary function is to house equipment for the processing and storage of electronic data and that has a design electronic data equipment power density exceeding 20 watts per square foot of conditioned area.
CONDENSING UNIT. A factory-made assembly of refrigeration components designed to compress and liquefy a specific refrigerant. The unit consists of one or more refrigerant compressors, refrigerant condensers (air-cooled, evaporatively cooled, or water-cooled), condenser fans and motors (where used) and factory-supplied accessories.
CONDITIONED FLOOR AREA. The horizontal projection of the floors associated with the conditioned space.
CONDITIONED SPACE. An area, room or space that is enclosed within the building thermal envelope and that is directly heated or cooled or that is indirectly heated or cooled. Spaces are indirectly heated or cooled where they communicate through openings with conditioned spaces, where they are separated from conditioned spaces by uninsulated walls, floors or ceilings, or where they contain uninsulated ducts, piping or other sources of heating or cooling.
CONTINUOUS AIR BARRIER. A combination of materials and assemblies that restrict or prevent the passage of air through the building thermal envelope.
CONTINUOUS INSULATION (CI). Insulating material that is continuous across all structural members without thermal bridges other than fasteners and service openings. It is installed on the interior or exterior or is integral to any opaque surface of the building envelope.
CONTROLLED PLANT GROWTH ENVIRONMENT. Group F and U buildings or spaces that are specifically controlled to facilitate and enhance plant growth and production by manipulating various indoor environment conditions. Technologies include indoor agriculture, cannabis growing, hydroponics, aquaculture and aquaponics. Controlled indoor environment variables include, but are not limited to, temperature, air quality, humidity, and carbon dioxide.
CURTAIN WALL. Fenestration products used to create an external nonload-bearing wall that is designed to separate the exterior and interior environments.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-20204 Section C202.4D.
DATA ACQUISITION SYSTEM. An electronic system managed by the building owner to collect, tabulate and display metering information.
DAYLIGHT RESPONSIVE CONTROL. A device or system that provides automatic control of electric light levels based on the amount of daylight in a space.
DAYLIGHT ZONE. The portion of the building interior floor area that is illuminated by natural daylight through sidelight and toplight fenestration.
DEMAND CONTROL VENTILATION (DCV). A ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy.
DEMAND RECIRCULATION WATER SYSTEM. A water distribution system where pumps prime the service hot water piping with heated water upon demand for hot water.
DOOR, NONSWINGING. Roll-up, tilt-up, metal coiling and sliding doors, access hatches, and all other doors that are not swinging doors.
DOOR, SWINGING. Doors that are hinged on one side and revolving doors.
DUCT. A tube or conduit utilized for conveying air. The air passages of self-contained systems are not to be construed as air ducts.
DUCT SYSTEM. A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings, dampers, plenums, fans and accessory air-handling equipment and appliances.
DWELLING UNIT. A single unit providing complete independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation.
DYNAMIC GLAZING. Any fenestration product that has the fully reversible ability to change its performance properties, including U-factor, SHGC, or VT.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-20212 Section C202.12L.
LABELED. Equipment, materials or products to which have been affixed a label, seal, symbol or other identifying mark of a nationally recognized testing laboratory, inspection agency or other organization concerned with product evaluation that maintains periodic inspection of the production of the above-labeled items and whose labeling indicates either that the equipment, material or product meets identified standards or has been tested and found suitable for a specified purpose.
LINER SYSTEM (LS). A system that includes the following:
1. A continuous vapor barrier liner membrane that is installed below the purlins and that is uninterrupted by framing members.
2. An uncompressed, unfaced insulation resting on top of the liner membrane and located between the purlins.
For multilayer installations, the last rated R-value of insulation is for unfaced insulation draped over purlins and then compressed when the metal roof panels are attached.
LISTED. Equipment, materials, products or services included in a list published by an organization acceptable to the code official and concerned with evaluation of products or services that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services and whose listing states either that the equipment, material, product or service meets identified standards or has been tested and found suitable for a specified purpose.
LOW-SLOPED ROOF. A roof having a slope less than 2 units vertical in 12 units horizontal.
LOW-VOLTAGE DRY-TYPE DISTRIBUTION TRANSFORMER. A transformer that is air-cooled, does not use oil as a coolant, has an input voltage less than or equal to 600.
LOW-VOLTAGE LIGHTING. A lighting system consisting of an isolating power supply, the low voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply operate at 30 volts (42.4 volts peak) or less under all load conditions.
LUMINAIRE. A complete lighting unit consisting of a lamp or lamps together with the housing designed to distribute the light, position and protect the lamps, and connect the lamps to the power supply.
LUMINAIRE-LEVEL LIGHTING CONTROL. A lighting system consisting of one or more luminaire(s) each with embedded lighting control logic, occupancy and ambient light sensors, local or central wireless networking capabilities, and local override switching capability.
AMENDATORY SECTION (Amending WSR 16-13-089, filed 6/15/16, effective 7/16/16)
WAC 51-11C-40100 Section C401General.
C401.1 Scope. The provisions in this chapter are applicable to commercial buildings and their building sites.
C401.2 Application. Commercial buildings shall comply with one of the following:
1. The requirements of Sections C402, C403, C404, C405, C406, C408, C409 and C410.
2. The requirements of Section C407, C408, C409, C410, C402.5, C403.2, C404, C405.2, C405.3, C405.4, C405.6 and C405.7. The building energy consumption shall be equal to or less than 87, 90, or 93 percent of the standard reference design building, depending on the option selected per Section C407.3.
C401.2.1 Application to existing buildings. Work on existing buildings shall comply with Chapter 5 in addition to the applicable provisions of Chapter 4.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40210 Section C402.1General (Prescriptive).
C402.1 General (Prescriptive). Building thermal envelope assemblies for buildings that are intended to comply with the code on a prescriptive basis, in accordance with the compliance path described in Item 1 of Section C401.2, shall comply with the following:
1. The opaque portions of the building thermal envelope shall comply with the specific insulation requirements of Section C402.2 and the thermal requirements of either the R-value based method of Section C402.1.3, the U-, C- and F-factor based method of Section C402.1.4, or the component performance alternative of Section C402.1.5.
2. Fenestration in building envelope assemblies shall comply with Section C402.4, or the component performance alternative of Section C402.1.5.
3. Air leakage of building envelope assemblies shall comply with Section C402.5.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40211 Section C402.1.1Low energy buildings.
C402.1.1 Low energy buildings. The following buildings, or portions thereof, separated from the remainder of the building by building thermal envelope assemblies complying with this code shall be exempt from all thermal envelope provision of this code:
1. Those that are heated and/or cooled with a peak design rate of energy usage less than 3.4 Btu/hx ft2 (10.7 W/m2) or 1.0 watt/ft2 (10.7 W/m2) of floor area for space conditioning purposes.
2. Those that do not contain conditioned space.
3. Greenhouses where cooling does not include a condensing unit and that are isolated from any other conditioned space.
4. Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities.
C402.1.1.1 Semi-heated buildings and spaces. The building envelope of semi-heated buildings, or portions thereof, shall comply with the same requirements as that for conditioned spaces in Section C402, except as modified by this section. Building envelope assemblies separating conditioned space from semi-heated space shall comply with exterior envelope insulation requirements. Semi-heated spaces heated by mechanical systems that do not include electric resistance heating equipment are not required to comply with the opaque wall insulation provisions of Section C402.2.3 for walls that separate semi-heated spaces from the exterior or low energy spaces. Semi-heated spaces shall be calculated separately from other conditioned spaces for compliance purposes. Opaque walls in semi-heated spaces shall be calculated as fully code compliant opaque walls for both the target and proposed for the Target UA calculations for Component Performance compliance per Section C402.1.5, and for the Standard Reference Design for Total Building Performance compliance per Section C407.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-402121 Table C402.1.3Opaque thermal envelope assembly R-value requirements.
Table C402.1.3
Opaque Thermal Envelope Insulation Component
Minimum Requirements, R-value Methoda,g
CLIMATE ZONE
5 AND MARINE 4
 
All Other
Group R
Roofs
Insulation entirely above deck
R-38ci
R-38ci
Metal buildingsb
R-25 + 
R-11 LS
R-25 + 
R-11 LS
Attic and other
R-49
R-49
Walls, Above Grade
Mass
R-9.5cic
R-13.3ci
Metal buildings
R-19ci
R-19ci
Steel framed
R-13 + 
R-10ci
R-19 + 
R-8.5ci
Wood framed and other
R-21 int
R-21 int
Walls, Below Grade
Below-grade walld
Same as above grade
Same as above grade
Floors
Massf
R-30ci
R-30ci
Joist/framing
R-30e
R-30e
Slab-on-Grade Floors
Unheated slabs
R-10 for 24" below
R-10 for 24" below
Heated slabs
R-10 perimeter & under entire slab
R-10 perimeter & under entire slab
Opaque Doors
Nonswinging
R-4.75
R-4.75
For SI:
1 inch = 25.4 mm. ci = Continuous insulation. NR = No requirement.
LS = 
Liner systemA continuous membrane installed below the purlins and uninterrupted by framing members. Uncompressed, unfaced insulation rests on top of the membrane between the purlins.
a
Assembly descriptions can be found in Chapter 2 and Appendix A.
b
Where using R-value compliance method, a thermal spacer block with minimum thickness of 1/2-inch and minimum R-value of R-3.5 shall be provided, otherwise use the U-factor compliance method in Table C402.1.4.
c
Exception: Integral insulated concrete block walls complying with ASTM C90 with all cores filled and meeting both of the following:
 
1. At least 50 percent of cores must be filled with vermiculite or equivalent fill insulation; and
 
2. The building thermal envelope encloses one or more of the following uses: Warehouse (storage and retail), gymnasium, auditorium, church chapel, arena, kennel, manufacturing plant, indoor swimming pool, pump station, water and waste water treatment facility, storage facility, storage area, motor vehicle service facility. Where additional uses not listed (such as office, retail, etc.) are contained within the building, the exterior walls that enclose these areas may not utilize this exception and must comply with the appropriate mass wall R-value from Table C402.1.3/U-factor from Table C402.1.4.
d
Where heated slabs are below grade, ((below-grade walls)) they shall comply with the ((exterior)) insulation requirements for heated slabs.
e
Steel floor joist systems shall be insulated to R-38 + R-10ci.
f
"Mass floors" shall include floors weighing not less than:
1. 35 pounds per square foot of floor surface area; or
2. 25 pounds per square foot of floor surface area where the material weight is not more than 120 pounds per cubic foot.
g
For roof, wall or floor assemblies where the proposed assembly would not be continuous insulation, an alternate nominal R-value compliance option for assemblies with isolated metal penetrations of otherwise continuous insulation is:
Assemblies with continuous
insulation (see definition)
Alternate option for assemblies with metal penetrations, greater than 0.04% but less than 0.08%
Alternate option for assemblies with metal penetrations, greater than or equal to 0.08% but less than 0.12%
R-9.5ci
R-11.9ci
R-13ci
R-11.4ci
R-14.3ci
R-15.7ci
R-13.3ci
R-16.6ci
R-18.3ci
R-15.2ci
R-19.0ci
R-21ci
R-30ci
R-38ci
R-42ci
R-38ci
R-48ci
R-53ci
R-13 + R-7.5ci
R-13 + R-9.4ci
R-13 + R-10.3ci
R-13 + R-10ci
R-13 + R-12.5ci
R-13 + R-13.8ci
R-13 + R-12.5ci
R-13 + R-15.6ci
R-13 + R-17.2ci
R-13 + R-13ci
R-13 + R-16.3ci
R-13 + R-17.9ci
R-19 + R-8.5ci
R-19 + R-10.6ci
R-19 + R-11.7ci
R-19 + R-14ci
R-19 + R-17.5ci
R-19 + R-19.2ci
R-19 + R-16ci
R-19 + R-20ci
R-19 + R-22ci
R-20 + R-3.8ci
R-20 + R-4.8ci
R-20 + R-5.3ci
R-21 + R-5ci
R-21 + R-6.3ci
R-21 + R-6.9ci
This alternate nominal R-value compliance option is allowed for projects complying with all of the following:
1.
The ratio of the cross-sectional area, as measured in the plane of the surface, of metal penetrations of otherwise continuous insulation to the opaque surface area of the assembly is greater than 0.0004 (0.04%), but less than 0.0012 (0.12%).
2.
The metal penetrations of otherwise continuous insulation are isolated or discontinuous (e.g., brick ties or other discontinuous metal attachments, offset brackets supporting shelf angles that allow insulation to go between the shelf angle and the primary portions of the wall structure). No continuous metal elements (e.g., metal studs, z-girts, z-channels, shelf angles) penetrate the otherwise continuous portion of the insulation.
3.
Building permit drawings shall contain details showing the locations and dimensions of all the metal penetrations (e.g., brick ties or other discontinuous metal attachments, offset brackets, etc.) of otherwise continuous insulation. In addition, calculations shall be provided showing the ratio of the cross-sectional area of metal penetrations of otherwise continuous insulation to the overall opaque wall area.
For other cases where the proposed assembly is not continuous insulation, see Section C402.1.4 for determination of U-factors for assemblies that include metal other than screws and nails.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40214 Section C402.1.4Assembly U-factor, C-factor, or F-factor-based method.
C402.1.4 Assembly U-factor, C-factor, or F-factor-based method. Building thermal envelope opaque assemblies intended to comply on an assembly U-, C-, or F-factor basis shall have a U-, C-, or F-factor not greater than that specified in Table C402.1.4. Commercial buildings or portions of commercial buildings enclosing Group R occupancies shall use the U-, C-, or F-factor from the "Group R" column of Table C402.1.4. Commercial buildings or portions of commercial buildings enclosing occupancies other than Group R shall use the U-, C-, or F-factor from the "All other" column of Table C402.1.4. The C-factor for the below-grade exterior walls of the building envelope, as required in accordance with Table C402.1.4, shall extend to the level of the lowest conditioned floor. Opaque swinging doors shall comply with Table C402.1.4 and opaque nonswinging doors shall comply with Table C402.1.3 or C402.1.4. The U-factors for typical construction assemblies are included in Appendix A. These values shall be used for all calculations. Where proposed construction assemblies are not represented in Appendix A, values shall be calculated in accordance with the ASHRAE HandbookFundamentals using the framing factors listed in Appendix A where applicable and shall include the thermal bridging effects of framing materials.
C402.1.4.1 Thermal resistance of cold-formed steel stud walls. U-factors of walls with cold-formed steel studs shall be permitted to be determined in accordance with Equation 4-1:
Equation 4-1:
U = 1/[Rs + (ER)]
Where:
Rs
=
The cumulative R-value of the wall components along the path of heat transfer, excluding the cavity insulation and steel studs.
ER
=
The effective R-value of the cavity insulation with steel studs.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-402141 Table C402.1.4Opaque thermal envelope requirements, U-factor method.
Table C402.1.4
Opaque Thermal Envelope Requirementsa,f
CLIMATE ZONE
5 AND MARINE 4
 
All Other
Group R
Roofs
Insulation entirely above deck
U-0.027
U-0.027
Metal buildings
U-0.031
U-0.031
Attic and other
U-0.021
U-0.021
Joist or single rafter
U-0.027
U-0.027
Walls, Above Grade
Mass
U-0.104d
U-0.078
Mass transfer deck slab edge
U-0.20
U-0.20
Metal building
U-0.052
U-0.052
Steel framed
U-0.055
U-0.055
Wood framed and other
U-0.054
U-0.054
Walls, Below Grade
Below-grade wallb
Same as above grade
Same as above grade
Floors
Masse
U-0.031
U-0.031
Joist/framing
U-0.029
U-0.029
Slab-on-Grade Floors
Unheated slabs
F-0.54
F-0.54
Heated slabsc
F-0.55
F-0.55
Opaque Doors
Swinging
U-0.37
U-0.37
Nonswinging
U-0.34
U-0.34
a
Use of opaque assembly U-factors, C-factors, and F-factors from Appendix A is required unless otherwise allowed by Section C402.1.4.
b
Where heated slabs are below grade, ((below-grade walls)) they shall comply with the F-factor requirements for heated slabs.
c
Heated slab F-factors shall be determined specifically for heated slabs. Unheated slab factors shall not be used.
d
Exception: Integral insulated concrete block walls complying with ASTM C90 with all cores filled and meeting both of the following:
 
1. At least 50 percent of cores must be filled with vermiculite or equivalent fill insulation; and
 
2. The building thermal envelope encloses one or more of the following uses: Warehouse (storage and retail), gymnasium, auditorium, church chapel, arena, kennel, manufacturing plant, indoor swimming pool, pump station, water and waste water treatment facility, storage facility, storage area, motor vehicle service facility. Where additional uses not listed (such as office, retail, etc.) are contained within the building, the exterior walls that enclose these areas may not utilize this exception and must comply with the appropriate mass wall R-value from Table C402.1.3/U-factor from Table C402.1.4.
e
"Mass floors" shall include floors weighing not less than:
1. 35 pounds per square foot of floor surface area; or
2. 25 pounds per square foot of floor surface area where the material weight is not more than 120 pounds per cubic foot.
f
Opaque assembly U-factors based on designs tested in accordance with ASTM C1363 shall be permitted. The R-value of continuous insulation shall be permitted to be added or substracted from the original test design.
AMENDATORY SECTION (Amending WSR 16-13-089, filed 6/15/16, effective 7/16/16)
WAC 51-11C-40215 Section C402.1.5Component performance alternative.
C402.1.5 Component performance alternative. Building envelope values and fenestration areas determined in accordance with Equation 4-2 shall be permitted in lieu of compliance with the U-factors and F-factors in Table C402.1.4 and C402.4 and the maximum allowable fenestration areas in Section C402.4.1.
Equation 4-2
A + B + C + D = ≤ Zero
Where:
A =
Sum of the (UA Dif) values for each distinct assembly type of the building thermal envelope, other than slabs on grade ((and below-grade walls))
 
UA Dif
=
UA Proposed – UA Table
 
UA Proposed
=
Proposed U-value x Area
 
UA Table
=
(U-factor from Table C402.1.4 or C402.4 ((or Section C402.1.3))) x Area
B =
Sum of the (FL Dif) values for each distinct slab on grade perimeter condition of the building thermal envelope
 
FL Dif
=
FL Proposed – FL Table
 
FL Proposed
=
Proposed F-value x Perimeter length
 
FL Table
=
(F-factor specified in Table C402.1.4) x Perimeter length
The maximum allowed prescriptive vertical fenestration area, identified as "Vertical Fenestration Area allowed" in factor CA below, as a percent of the gross above-grade wall area ratio is either:
 
1.
30%
 
2.
40% if the building complies with Section C402.4.1.1 or Section C402.1.4.1; or
 
3.
40% if the U-values used in calculating A for vertical fenestration are taken from Section C402.4.1.3 rather than Table C402.4
Where the proposed vertical fenestration area is less than or equal to the maximum allowed prescriptive vertical fenestration area, the value of C (Excess Vertical Glazing Value) shall be zero. Otherwise:
C =
(CA x UV) – (CA x UWall), but not less than zero
 
CA
=
(Proposed Vertical Fenestration Area) – (Vertical Fenestration Area allowed)
 
UA Wall
=
Sum of the (UA Proposed) values for each opaque assembly of the exterior wall
 
UAW
=
Sum of the (UA proposed) values for each above-grade wall assembly
 
UWall
=
UAW/sum of wall area (excludes vertical fenestration area)
 
UAV
=
Sum of the (UA Proposed) values for each vertical fenestration assembly
 
UV
=
UAV/total vertical fenestration area
Where the proposed skylight area is less than or equal to the skylight area allowed by Section C402.4.1, the value of D (Excess Skylight Value) shall be zero. Otherwise:
D =
(DA x US) – (DA x URoof), but not less than zero
 
DA
=
(Proposed Skylight Area) – (Allowable Skylight Area from Section C402.4.1)
 
UAR
=
Sum of the (UA Proposed) values for each roof assembly
 
URoof
=
UAR/sum of roof area (excludes skylight area)
 
UAS
=
Sum of the (UA Proposed) values for each skylight assembly
 
US
=
UAS/total skylight area
C402.1.5.1 Component U-factors. The U-factors for typical construction assemblies are included in Chapter 3 and Appendix A. These values shall be used for all calculations. Where proposed construction assemblies are not represented in Chapter 3 or Appendix A, values shall be calculated in accordance with the ASHRAE HandbookFundamentals, using the framing factors listed in Appendix A.
For envelope assemblies containing metal framing, the U-factor shall be determined by one of the following methods:
1. Results of laboratory measurements according to acceptable methods of test.
2. ASHRAE HandbookFundamentals where the metal framing is bonded on one or both sides to a metal skin or covering.
3. The zone method as provided in ASHRAE HandbookFundamentals.
4. Effective framing/cavity R-values as provided in Appendix A.
When return air ceiling plenums are employed, the roof/ceiling assembly shall:
a. For thermal transmittance purposes, not include the ceiling proper nor the plenum space as part of the assembly; and
b. For gross area purposes, be based upon the interior face of the upper plenum surface.
5. Tables in ASHRAE 90.1-2010 Normative Appendix A.
C402.1.5.2 SHGC rate calculations. Solar heat gain coefficient shall comply with Table C402.4. The target SHGCAt and the proposed SHGCAp shall be calculated using Equations 4-3 and 4-4 and the corresponding areas and SHGCs from Table C402.4.
Equation 4-3Target SHGCAt
Equation C402-3
Target SHGCAt
SHGCAt
 
SHGCogt(Aogt) + SHGCvgt (Avgt + Avgmt + Avgmot + Avgdt)
Where:
SHGCAt
=
The target combined solar heat gain of the target fenestration area.
SHGCogt
=
The solar heat gain coefficient for skylight fenestration found in Table ((C402.3)) C402.4.
Aogt
=
The proposed skylight area.
SHGCvgt
=
The solar heat gain coefficient for vertical fenestration found in Table ((C402.3. Buildings utilizing Section C402.3.1.3 shall use the SHGC value specified there. The SHGC may be adjusted for projection factors per the requirements of Section C402.3)) C402.4 which corresponds to the proposed total fenestration area as a percentage of gross exterior wall.
Avgt
=
The proposed vertical fenestration area with nonmetal framing.
Avgmt
=
The proposed vertical fenestration area with fixed metal framing.
Avgmot
=
The proposed vertical fenestration area with operable metal framing.
Avgdt
=
The proposed vertical fenestration area of entrance doors.
NOTE:
The vertical fenestration area does not include opaque doors and opaque spandrel panels.
Equation 4-4
Proposed SHGCAp
SHGCAp
=
SHGCogAog + SHGCvgAvg
Where:
SHGCAt
=
The combined proposed solar heat gain of the proposed fenestration area.
SHGCog
=
The solar heat gain coefficient of the skylights.
Aog
=
The skylight area.
SHGCvg
=
The solar heat gain coefficient of the vertical fenestration.
Avg
=
The vertical fenestration area.
NOTE:
The vertical fenestration area does not include opaque doors and opaque spandrel panels.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40220 Section C402.2Specific insulation requirements.
C402.2 Specific building thermal envelope insulation requirements (Prescriptive). Insulation in building thermal envelope opaque assemblies shall comply with Sections C402.2.1 through C402.2.6 and Table C402.1.3.
Where this section refers to installing insulation levels as specified in Section C402.1.3, assemblies complying with Section C402.1.4 and buildings complying with Section C402.1.5 are allowed to install alternate levels of insulation so long as the U-factor of the insulated assembly is less than or equal to the U-factor required by the respective path.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40232 Section C402.4.2Minimum skylight fenestration area.
C402.4.2 Minimum skylight fenestration area. For single story buildings only, in an enclosed space greater than 2,500 square feet (232 m2) in floor area, directly under a roof with not less than 75 percent of the ceiling area with a ceiling height greater than 15 feet (4572 mm), and used as an office, lobby, atrium, concourse, corridor, gymnasium/exercise center, convention center, automotive service, manufacturing, nonrefrigerated warehouse, retail store, distribution/sorting area, transportation, or workshop, skylights are required to provide a total toplight daylight zone area not less than half the floor area and shall provide one of the following:
1. A minimum ratio of skylight area to toplight daylight zone area under skylights of not less than 3 percent where all skylights have a VT of at least 0.40 as determined in accordance with Section C303.1.3.
2. A minimum skylight effective aperture of at least 1 percent determined in accordance with Equation 4-5.
 
Skylight Effective Aperture
=
(0.85 x Skylight Area x Skylight VT x WF)/Daylight zone under skylight
 
(Equation 4-5)
Where:
 
Skylight area
=
Total fenestration area of skylights.
Skylight VT
=
Area weighted average visible transmittance of skylights.
WF
=
Area weighted average well factor, where well factor is 0.9 if light well depth is less than 2 feet (610 mm), or 0.7 if light well depth is 2 feet (610 mm) or greater.
Light well depth
=
Measure vertically from the underside of the lowest point of the skylight glazing to the ceiling plane under the skylight.
EXCEPTION:
Skylights above daylight zones of enclosed spaces are not required in:
 
1. Reserved.
 
2. Spaces where the designed general lighting power densities are less than 0.5 W/ft2 (5.4 W/m2).
 
3. Areas where it is documented that existing structures or natural objects block direct beam sunlight on at least half of the roof over the enclosed area for more than 1,500 daytime hours per year between 8 a.m. and 4 p.m.
 
4. Spaces where the daylight zone under rooftop monitors is greater than 50 percent of the enclosed space floor area.
 
5. Spaces where the total floor area minus the sidelight daylight zone area is less than 2,500 square feet (232 m2), and where the lighting in the daylight zone is controlled in accordance with Section C405.2.3.1.
C402.4.2.1 Lighting controls in daylight zones under skylights. Daylight responsive controls complying with Section C405.2.4.1 shall be provided to control all electric lights within daylight zones.
C402.4.2.2 Haze factor. Skylights in office, storage, automotive service, manufacturing, nonrefrigerated warehouse, retail store, and distribution/sorting area spaces shall have a glazing material or diffuser with a haze factor greater than 90 percent when tested in accordance with ASTM D 1003.
EXCEPTION:
Skylights designed and installed to exclude direct sunlight entering the occupied space by the use of fixed or automated baffles, or the geometry of skylight and light well.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40234 Section C402.4.4Doors.
C402.4.4 Doors. Opaque doors shall comply with the applicable requirements for doors as specified in Tables C402.1.3 and C402.1.4 and be considered part of the gross area of above grade walls that are part of the building thermal envelope. Other doors shall comply with the provisions of Section C402.4.3 for vertical fenestration and the entire door area, including the frame, shall be considered part of the fenestration area of the building thermal envelope.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-403241 Section C403.2.4.1Thermostatic controls.
C403.2.4.1 Thermostatic controls. The supply of heating and cooling energy to each zone shall be controlled by individual thermostatic controls capable of responding to temperature within the zone. Controls in the same zone or in neighboring zones connected by openings larger than 10 percent of the floor area of either zone shall not allow for simultaneous heating and cooling. At a minimum, each floor of a building shall be considered as a separate zone. Controls on systems required to have economizers and serving single zones shall have multiple cooling stage capability and activate the economizer when appropriate as the first stage of cooling. See Section C403.3.1 for further economizer requirements. Where humidification or dehumidification or both is provided, at least one humidity control device shall be provided for each humidity control system.
EXCEPTIONS:
1. Independent perimeter systems that are designed to offset only building envelope heat losses or gains or both serving one or more perimeter zones also served by an interior system provided:
 
1.1. The perimeter system includes at least one thermostatic control zone for each building exposure having exterior walls facing only one orientation (within +/-45 degrees) (0.8 rad) for more than 50 contiguous feet (15,240 mm);
 
1.2. The perimeter system heating and cooling supply is controlled by a thermostat located within the zones served by the system; and
 
1.3. Controls are configured to prevent the perimeter system from operating in a different heating or cooling mode from the other equipment within the zones or from neighboring zones connected by openings larger than 10 percent of the floor area of either zone.
 
2. ((Any nonperimeter zones not separated from perimeter zones by an interior wall with openings no larger than 10 percent of the perimeter floor zone area shall have setpoints and deadbands coordinated so that cooling in adjacent zones shall not operate until the adjacent zone temperature is 5°F (2.8°C) higher than the perimeter zone temperature.)) Any interior zone open to a perimeter zone shall have setpoints and deadbands coordinated to that cooling in the interior zone shall not operate while the perimeter zone is in heating until the interior zone temperature is 5°F (2.8°C) higher than the perimeter zone temperature, unless the interior and perimeter zones are separated by a partition whose permanent openings are smaller than 10 percent of the perimeter zone floor area.
C403.2.4.1.1 Heat pump supplementary heat. Unitary air cooled heat pumps shall include microprocessor controls that minimize supplemental heat usage during start-up, set-up, and defrost conditions. These controls shall anticipate need for heat and use compression heating as the first stage of heat. Controls shall indicate when supplemental heating is being used through visual means (e.g., LED indicators). Heat pumps equipped with supplementary heaters shall be installed with controls that prevent supplemental heater operation above 40°F.
EXCEPTION:
Packaged terminal heat pumps (PTHPs) of less than 2 tons (24,000 Btu/hr) cooling capacity provided with controls that prevent supplementary heater operation above 40°F.
C403.2.4.1.2 Deadband. Where used to control both heating and cooling, zone thermostatic controls shall be configured to provide a temperature range or deadband of at least 5°F (2.8°C) within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
EXCEPTIONS:
1. Thermostats requiring manual changeover between heating and cooling modes.
 
2. Occupancies or applications requiring precision in indoor temperature control as approved by the code official.
C403.2.4.1.3 Setpoint overlap restriction. Where a zone has a separate heating and a separate cooling thermostatic control located within the zone, a limit switch, mechanical stop or direct digital control system with software programming shall be configured to prevent the heating set point from exceeding the cooling setpoint and to maintain a deadband in accordance with Section C403.2.4.1.2.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40511 ((Reserved.)) Electrical power and lighting systems commissioning and completion requirements.
Electrical power and lighting systems shall be commissioned and completed in accordance with Section C408.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40605 Section C406.5On-site renewable energy option.
C406.5 On-site renewable energy. Buildings shall be provided with on-site renewable energy systems with ((a total system rating)) an annual energy production per square foot of conditioned floor area of the building of not less than the value specified in Table C406.5.
Table C406.5
On-Site Renewable Energy System Rating
(per square foot)
Building Area Type
((kBTU))
kBtu/year
kWh/year
Assembly
1.8
0.53
Dining
10.7
3.14
Hospital
3.6
1.06
Hotel/Motel
2.0
0.59
Multifamily residential
0.50
0.15
Office
0.82
0.24
Other
2.02
0.59
Retail
1.31
0.38
School/University
1.17
0.34
Supermarket
5.0
1.47
Warehouse
0.43
0.13
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40607 Section C406.7Service water heating option.
C406.7 Reduced energy use in service water heating. Buildings shall comply with Sections C406.7.1 and C406.7.2.
C406.7.1 Building type. Not less than 90 percent of the conditioned floor area shall be of the following types:
1. Group R-1: Boarding houses, hotels or motels.
2. Group I-2: Hospitals, psychiatric hospitals and nursing homes.
3. Group A-2: Restaurants and banquet halls or buildings containing food preparation areas.
4. Group F: Laundries.
5. Group R-2: Buildings with residential occupancies.
6. Group A-3: Health clubs and spas.
7. Buildings with a service hot water load of 10 percent or more of total building energy loads, as shown with an energy analysis as described in Section C407.
C406.7.2 Load fraction. Not less than 60 percent of the annual building service hot water heating energy use, or not less than 100 percent of the annual building service hot water heating energy use in buildings subject to the requirements of Section C403.5.4, shall be provided by one or more of the following:
1. Service hot water system delivering heating requirements using heat pump technology with a minimum COP of 3.0.
2. Waste heat recovery from service hot water, heat recovery chillers, building equipment, process equipment, a combined heat and power system, or other approved system.
3. Solar water-heating systems.
AMENDATORY SECTION (Amending WSR 16-13-089, filed 6/15/16, effective 7/16/16)
WAC 51-11C-407051 Table C407.5.1(1)Specifications for the standard reference and proposed design.
Table C407.5.1(1)
Specifications for the Standard Reference and Proposed Designs
Building Component Characteristics
Standard Reference Design
Proposed Design
Space use classification
Same as proposed
The space use classification shall be chosen in accordance with Table C405.4.2 for all areas of the building covered by this permit. Where the space use classification for a building is not known, the building shall be categorized as an office building.
Roofs
Type: Insulation entirely above deck
As proposed
 
Gross area: Same as proposed
As proposed
 
U-factor: From Table C402.1.4
As proposed
 
Solar absorptance: 0.75
As proposed
 
Emittance: 0.90
As proposed
Walls, above-grade
Type: Mass wall if proposed wall is mass; otherwise steel-framed wall
As proposed
 
Gross area: Same as proposed
As proposed
 
U-factor: From Table C402.1.4
As proposed
 
Solar absorptance: 0.75
As proposed
 
Emittance: 0.90
As proposed
Walls, below-grade
Type: Mass wall
As proposed
 
Gross area: Same as proposed
As proposed
 
U-Factor: From Table C402.1.4 with insulation layer on interior side of walls
As proposed
Floors, above-grade
Type: Joist/framed floor
As proposed
 
Gross area: Same as proposed
As proposed
 
U-factor: From Table C402.1.4
As proposed
Floors, slab-on-grade
Type: Unheated
As proposed
 
F-factor: From Table C402.1.4
As proposed
Opaque Doors
Type: Swinging
As proposed
 
Area: Same as proposed
As proposed
 
U-factor: From Table C402.1.4
As proposed
Vertical Fenestration
Other than opaque doors
Area
As proposed
 
 
1. The proposed vertical fenestration area; where the proposed vertical fenestration area is less than 30 percent of above-grade wall area.
 
 
 
2. 30 percent of above-grade wall area; where the proposed vertical fenestration area is 30 percent or more of the above-grade wall area.
 
 
U-factor: From Table C402.4 for the same framing material as proposed
As proposed
 
SHGC: From Table C402.4 except that for climates with no requirement (NR) SHGC = 0.40 shall be used
As proposed
 
External shading and PF: None
As proposed
Skylights
Area
As proposed
 
 
1. The proposed skylight area; where the proposed skylight area is less than 3 percent of gross area of roof assembly.
 
 
 
2. 3 percent of gross area of roof assembly; where the proposed skylight area is 3 percent or more of gross area of roof assembly.
 
 
U-factor: From Table C402.4
As proposed
 
SHGC: From Table C402.4 except that for climates with no requirement (NR) SHGC = 0.40 shall be used
As proposed
Air leakage
For infiltration, the air leakage rate as determined below shall be modeled at 100% when the building fan system is off, and at 25% when the building fan system is on, unless otherwise approved by the building official for unusually pressurized buildings. Per PNNL Report 18898, Infiltration Modeling Guidelines for Commercial Building Energy Analysis, the building air leakage rates as determined in accordance with Section C402.5.1.2 at 0.30 in. w.g. (75 Pa) shall be converted for modeling in annual energy analysis programs by being multiplied by 0.112 unless other multipliers are approved by the building official (e.g., a tested air leakage of 0.40 cfm/ft2 of total building envelope area at 0.30 in. w.g. (75 Pa) would be calculated at 0.045 cfm/ft2 of building envelope area). The calculated infiltration rate shall be normalized to the input required by the modeling software.
The Proposed Design air-leakage rate shall be the same as the Standard Design.
Lighting, interior
The interior lighting power shall be determined in accordance with Table C405.4.2. As proposed when the occupancy of the space is not known.
As proposed; where the occupancy of the space is not known, the lighting power density shall be based on the space classification as offices in Table C405.4.2(1).
 
Automatic lighting controls (e.g., programmable controls or automatic controls for daylight utilization) shall be modeled in the standard reference design as required by Section C405.
 
Lighting, exterior
The lighting power shall be determined in accordance with Table C405.5.2(2). Areas and dimensions of tradable and nontradable surfaces shall be the same as proposed.
As proposed
Internal gains
Same as proposed
Receptacle, motor and process loads shall be modeled and estimated based on the space use classification. All end-use load components within and associated with the building shall be modeled to include, but not be limited to, the following: Exhaust fans, parking garage ventilation fans, exterior building lighting, swimming pool heaters and pumps, elevators, escalators, refrigeration equipment and cooking equipment.
Schedules
Same as proposed
Operating schedules shall include hourly profiles for daily operation and shall account for variations between weekdays, weekends, holidays and any seasonal operation. Schedules shall model the time-dependent variations in occupancy, illumination, receptacle loads, thermostat settings, mechanical ventilation, HVAC equipment availability, service hot water usage and any process loads. The schedules shall be typical of the proposed building type as determined by the designer and approved by the jurisdiction.
Outdoor airflow rates
Same as proposed, or no higher than those allowed by Section C403.2.6 (without exception 1), whichever is less.
As proposed, in accordance with Section C403.2.6.
Demand control ventilation: Shall be modeled as required by Section C403.6 including reduction to the minimum ventilation rate when unoccupied.
As proposed
Heating systems
Fuel type: Same as proposed design
As proposed
 
Equipment typea: From Tables C407.5.1(2), C407.5.1(3), and C407.5.1(4)
As proposed
 
Efficiency: From Tables C403.2.3(2), C403.2.3(3), C403.2.3(4) and C403.2.3(5)
As proposed
 
Preheat coils: For HVAC system numbers 1 through 4, a preheat coil shall be modeled controlled to a fixed setpoint 20°F less than the design room heating temperature setpoint.
 
 
Capacityb: Sized proportionally to the capacities in the proposed design based on sizing runs, i.e., the ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and standard reference design, and shall be established such that no smaller number of unmet heating load hours and no larger heating capacity safety factors are provided than in the proposed design.
As proposed
 
Weather conditions used in sizing runs to determine standard reference design equipment capacities may be based either on hourly historical weather files containing typical peak conditions or on design days developed using 99.6% heating design temperatures and 1% dry-bulb and 1% wet-bulb cooling design temperatures.
 
Cooling systems
Fuel type: Same as proposed design
As proposed
 
Equipment typec: From Tables C407.5.1(2), C407.5.1(3), and C407.5.1(4)
As proposed
 
Efficiency: From Tables C403.2.3(1), C403.2.3(2) and C403.2.3(3). Chillers shall use Path A efficiency.
As proposed
 
Capacityb: Sized proportionally to the capacities in the proposed design based on sizing runs, i.e., the ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and standard reference design, and shall be established such that no smaller number of unmet cooling load hours and no larger cooling capacity safety factors are provided than in the proposed design.
As proposed
 
Economizerd: ((Same as proposed,)) In accordance with Section C403.3. The high-limit shutoff shall be a dry-bulb switch with a setpoint as determined by Table C403.3.3.3.
As proposed
Energy recovery
Standard reference design systems shall be modeled where required in Section C403.5.
As proposed
Fan systems
Airflow rate: System design supply airflow rates for the standard reference design shall be based on a supply-air-to-room-air temperature difference of 20°F or the required ventilation air or makeup air, whichever is greater. If return or relief fans are specified in the proposed design, the standard reference design shall also be modeled with fans serving the same functions and sized for the standard reference design system supply fan air quantity less the minimum outdoor air, or 90% of the supply fan air quantity, whichever is larger.
As proposed
 
Motor brake horsepower: System fan electrical power for supply, return, exhaust, and relief (excluding power to fan-powered VAV boxes) shall be calculated using the following formulas:
For systems 5, 7, 8 and 10 in Table C407.5.1(4),
Pfan = CFMs × 0.3
For all other systems, including DOAS,
Pfan = bhp × 746/Fan Motor Efficiency
Where:
Pfan = Electric power to fan motor (watts)
bhp = Brake horsepower of standard reference design fan motor from Table C403.2.12.1(1) – Option 2
Fan motor = The efficiency from Tables C405.8(1) through C405.8(4) for the efficiency next motor size greater than the bhp using the enclosed motor at 1800 rpm
CFMs = The standard reference design system maximum design supply fan airflow rate in cfm ((DOAS fan power shall be calculated separately from the brake horsepower allowance)).
As proposed
On-site renewable energy
No on-site renewable energy shall be modeled in the standard reference design.
As proposed.
Shading from adjacent structures/terrain
Same as proposed.
For the standard reference design and the proposed building, shading by permanent structures and terrain shall be taken into account for computing energy consumption whether or not these features are located on the building site. A permanent fixture is one that is likely to remain for the life of the proposed design.
Service water heating
Fuel type: Same as proposed
As proposed
 
Efficiency: From Table C404.2 and per Section C404.2.1
As proposed
 
Capacity: Same as proposed
 
 
Demand: Same as proposed
Service hot-water energy consumption shall be calculated explicitly based upon the volume of service hot water required and the entering makeup water and the leaving service hot water temperatures. Entering water temperatures shall be estimated based upon the location. Leaving temperatures shall be based upon the end-use requirements.
Service water loads and usage shall be the same for both the standard reference design and the proposed design and shall be documented by the calculation procedures recommended by the manufacturer's specifications or generally accepted engineering methods.
 
Where no service water hot water system exists or is specified in the proposed design, no service hot water heating shall be modeled.
As proposed
 
Drain water heat recovery: Not required.
As proposed
Drain water heat recovery modeling shall take into account manufacturer's rated efficiencies per C404.9, quantity of connected drains, the proportional flow rates between the waste stream and the preheated stream. Reductions in service water heating energy use for drain water heat recovery shall be demonstrated by calculations.
a
Where no heating system exists or has been specified, the heating system shall be modeled as fossil fuel. The system characteristics shall be identical in both the standard reference design and proposed design.
b
The ratio between the capacities used in the annual simulations and the capacities determined by sizing runs shall be the same for both the standard reference design and proposed design.
c
Where no cooling system exists or no cooling system has been specified, the cooling system shall be modeled as an air-cooled single-zone system, one unit per thermal zone. The system characteristics shall be identical in both the standard reference design and proposed design.
d
If an economizer is required in accordance with Section C403.3 and where no economizer exists or is specified in the proposed design, then an air economizer shall be provided in the standard reference design in accordance with Section C403.3.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-407052 Table C407.5.1(2)/(3)HVAC systems map.
Table C407.5.1(2)
HVAC Systems Map for Buildings Governed by Section C403.6d
((Condenser Cooling Sourcea
Heating System Classificationb
Standard Reference Design HVAC System Typec
Single-Zone
Residential System
All Other
 
Electric resistance
System 5
System 5
Water/ground
Heat pump
System 6
System 6
 
Fossil fuel
System 7
System 7
 
Electric resistance
System 8
System 9
Air/none
Heat pump
System 8
System 9
 
Fossil fuel
System 10
System 11))
Condenser Cooling Sourcea
Heating System Classificationb
Standard Reference Design HVAC System Type
 
Electric resistance
System 5
Water/ground
Heat pump
System 6
 
Fossil fuel
System 7
 
Electric resistance
System 9
Air/none
Heat pump
System 9
 
Fossil fuel
System 11
a
Select "water/ground" if the proposed design system condenser is water or evaporatively cooled; select "air/none" if the condenser is air cooled. Closed-circuit dry coolers shall be considered air cooled. Systems utilizing district cooling shall be treated as if the condenser water type were "water." If no mechanical cooling is specified or the mechanical cooling system in the proposed design does not require heat rejection, the system shall be treated as if the condenser water type were "Air." For proposed designs with ground-source or groundwater-source heat pumps, the standard reference design HVAC system shall be water-source heat pump (System 6).
b
Systems utilizing district heating (steam or hot water) or district cooling and systems with no heating capability shall be treated as if the heating system type were "fossil fuel" for the purpose of Standard Reference Design HVAC system selection. Otherwise, select the path that corresponds to the proposed design heat source: Electric resistance, heat pump (including air source and water source), or fuel fired. For systems with mixed fuel heating sources, the system or systems that use the secondary heating source type (the one with the smallest total installed output capacity for the spaces served by the system) shall be modeled identically in the standard reference design and the primary heating source type shall be used to determine standard reference design HVAC system type.
c
((Select the standard reference design HVAC system category: The system under "single-zone residential system" shall be selected if the HVAC system in the proposed design is a single-zone system and serves a residential space. The system under "all other" shall be selected for all other cases.)) Reserved.
d
This table covers those building types required by Section C403.6 to install Dedicated Outdoor Air Systems: Office, retail, education, libraries and fire stations.
Table C407.5.1(3)
HVAC Systems Map for All Other Buildings
 
 
Standard Reference Design HVAC System Typec
Condenser Cooling Sourcea
Heating System Classificationb
Single-Zone
Residential System
Single-Zone
Nonresidential System
All Other
 
Electric resistance
System 5
System 5
System 1
Water/ground
Heat pump
System 6
System 6
System 6
 
Fossil fuel
System 7
System 7
System 2
 
Electric resistance
System 8
System 9
System 3
Air/none
Heat pump
System 8
System 9
System 3
 
Fossil fuel
System 10
System 11
System 4
a
Select "water/ground" if the proposed design system condenser is water or evaporatively cooled; select "air/none" if the condenser is air cooled. Closed-circuit dry coolers shall be considered air cooled. Systems utilizing district cooling shall be treated as if the condenser water type were "water." If no mechanical cooling is specified or the mechanical cooling system in the proposed design does not require heat rejection, the system shall be treated as if the condenser water type were "Air." For proposed designs with ground-source or groundwater-source heat pumps, the standard reference design HVAC system shall be water-source heat pump (System 6).
b
Systems utilizing district heating (steam or hot water) or district cooling and systems with no heating capability shall be treated as if the heating system type were "fossil fuel" for the purpose of Standard Reference Design HVAC system selection. Otherwise, select the path that corresponds to the proposed design heat source: Electric resistance, heat pump (including air source and water source), or fuel fired. For systems with mixed fuel heating sources, the system or systems that use the secondary heating source type (the one with the smallest total installed output capacity for the spaces served by the system) shall be modeled identically in the standard reference design and the primary heating source type shall be used to determine standard reference design HVAC system type.
c
Select the standard reference design HVAC system category: The system under "single-zone Group R system" shall be selected if the HVAC system in the proposed design is a single-zone system and serves a residential space. The system under "single-zone other than Group R system" shall be selected if the HVAC system in the proposed design is a single-zone system and serves other than Group R spaces. The system under "all other" shall be selected for all other cases.
AMENDATORY SECTION (Amending WSR 16-13-089, filed 6/15/16, effective 7/16/16)
WAC 51-11C-40801 Section C408.1General.
C408.1 General. A building commissioning process led by a certified commissioning professional shall be completed for mechanical and refrigeration systems in Sections C403 and C410, service water heating systems in Section C404, electrical power and lighting systems in Section C405 and energy metering in Section C409.
EXCEPTION:
Buildings, or portions thereof, which are exempt from Sections C408.2 through C408.6 may be excluded from the commissioning process.
C408.1.1 Commissioning in construction documents. Construction document notes shall clearly indicate provisions for commissioning and completion requirements in accordance with this section and are permitted to refer to specifications for further requirements.
C408.1.2 Commissioning plan. A commissioning plan shall be developed by the project's certified commissioning professional and shall outline the organization, schedule, allocation of resources, and documentation requirements of the commissioning process. Items 1 through 4 shall be included with the construction documents, and items 5 through 8 shall be submitted prior to the first mechanical inspection. For projects where no mechanical inspection is required, items 5 through 8 shall be submitted prior to the first electrical inspection.
1. A narrative description of the activities that will be accomplished during each phase of commissioning, including the personnel intended to accomplish each of the activities.
2. Roles and responsibilities of the commissioning team, including statement of qualifications of the commissioning professional.
3. A schedule of activities including systems testing and balancing, functional performance testing, and verification of the building documentation requirements in Section C103.6.
4. Where the certified commissioning professional is an employee of one of the registered design professionals of record or an employee or subcontractor of the project contractor, an In-House Commissioning Disclosure and Conflict Management Plan shall be submitted with the commissioning plan. This plan shall disclose the certified commissioning professional's contractual relationship with other team members and provide a conflict management plan demonstrating that the certified commissioning professional is free to identify any issues discovered and report directly to the owner.
5. A listing of the specific equipment, appliances or systems to be tested and a description of the tests to be performed.
6. Functions to be tested.
7. Conditions under which the test will be performed.
8. Measurable criteria for performance.
C408.1.3 Final commissioning report. A final commissioning report shall be completed and certified by the certified commissioning professional and delivered to the building owner or owner's authorized agent. The report shall be organized with mechanical, lighting, service water heating and metering findings in separate sections to allow independent review. The report shall record the activities and results of the commissioning process and be developed from the final commissioning plan with all of its attached appendices. The report shall include:
1. Results of functional performance tests.
2. Disposition of deficiencies found during testing, including details of corrective measures used or proposed.
3. Functional performance test procedures used during the commissioning process including measurable criteria for test acceptance, provided herein for repeatability.
EXCEPTION:
Deferred tests which cannot be performed at the time of report preparation due to climatic conditions.
C408.1.4. Commissioning process completion requirements. Prior to the final mechanical, plumbing and electrical inspections or obtaining a certificate of occupancy, the certified commissioning professional or approved agency shall provide evidence of systems commissioning and completion in accordance with the provisions of this section.
Copies of all documentation shall be given to the owner and made available to the code official upon request in accordance with Section C408.1.4.3.
C408.1.4.1 Commissioning progress report for code compliance. A preliminary report of commissioning test procedures and results shall be completed and certified by the certified commissioning professional or approved agency and provided to the building owner or owner's authorized agent. The report shall be organized with mechanical, lighting, service water heating and metering findings in separate sections to allow independent review. The report shall be identified as "Preliminary Commissioning Report" and shall identify:
1. Itemization of deficiencies found during testing required by this code that have not been corrected at the time of report preparation.
2. Deferred tests that cannot be performed at the time of report preparation because of climatic conditions, with anticipated date of completion.
3. Climatic conditions required for performance of the deferred tests.
4. Status of the project's record documents, manuals and systems operation training with respect to requirements in Section C103.6.
C408.1.4.2 Acceptance of report. Buildings, or portions thereof, shall not be considered acceptable for a final inspection pursuant to Section C104.2 until the code official has received a letter of transmittal from the building owner acknowledging that the building owner or owner's authorized agent has received the Preliminary Commissioning Report. Completion of the Commissioning Compliance Checklist (Figure C408.1.4.2) is deemed to satisfy this requirement.
C408.1.4.3 Copy of report. The code official shall be permitted to require that a copy of the Preliminary Commissioning Report be made available for review by the code official.
AMENDATORY SECTION (Amending WSR 16-03-072, filed 1/19/16, effective 7/1/16)
WAC 51-11C-40802 Section C408.2Mechanical systems commissioning.
C408.2 Mechanical and refrigeration systems commissioning. Mechanical and refrigeration equipment and controls subject to Sections C403 and C410 shall be included in the commissioning process required by Section C408.1. The commissioning process shall minimally include all energy code requirements for which the code states that equipment or controls shall "be capable of" or "configured to" perform specific functions.
EXCEPTION:
Mechanical systems are exempt from the commissioning process where the building's total mechanical equipment capacity is less than 240,000 Btu/h cooling capacity and less than 300,000 Btu/h heating capacity.
C408.2.1 Reserved.
C408.2.2 Systems adjusting and balancing. HVAC systems shall be balanced in accordance with generally accepted engineering standards. Air and water flow rates shall be measured and adjusted to deliver final flow rates within the tolerances provided in the project specifications. Test and balance activities shall include air system and hydronic system balancing.
C408.2.2.1 Air systems balancing. Each supply air outlet and zone terminal device shall be equipped with means for air balancing in accordance with the requirements of Chapter 6 of the International Mechanical Code. Discharge dampers used for air system balancing are prohibited on constant volume fans and variable volume fans with motors 10 hp (18.6 kW) and larger. Air systems shall be balanced in a manner to first minimize throttling losses then, for fans with system power of greater than 1 hp (0.74 kW), fan speed shall be adjusted to meet design flow conditions.
EXCEPTION:
Fans with fan motors of 1 hp (0.74 kW) or less.
C408.2.2.2 Hydronic systems balancing. Individual hydronic heating and cooling coils shall be equipped with means for balancing and measuring flow. Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses, then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions. Each hydronic system shall have either the capability to measure pressure across the pump, or test ports at each side of each pump.
EXCEPTION:
The following equipment is not required to be equipped with means for balancing or measuring flow:
 
1. Pumps with pump motors of 5 hp (3.7 kW) or less.
 
2. Where throttling results in no greater than five percent of the nameplate horsepower draw above that required if the impeller were trimmed.
C408.2.3 Functional performance testing. Functional performance testing specified in Sections C408.2.3.1 through C408.2.3.3 shall be conducted. Written procedures which clearly describe the individual systematic test procedures, the expected systems' response or acceptance criteria for each procedure, the actual response or findings, and any pertinent discussion shall be followed. Testing shall affirm operation during actual or simulated winter and summer design conditions and during full outside air conditions.
C408.2.3.1 Equipment. Equipment functional performance testing shall demonstrate the installation and operation of components, systems, and system-to-system interfacing relationships in accordance with approved plans and specifications such that operation, function, and maintenance serviceability for each of the commissioned systems is confirmed. Testing shall include all modes and sequence of operation, including under full-load, part-load and the following emergency conditions:
1. All modes as described in the sequence of operation;
2. Redundant or automatic back-up mode;
3. Performance of alarms; and
4. Mode of operation upon a loss of power and restoration of power.
C408.2.3.2 Controls. HVAC control systems shall be tested to document that control devices, components, equipment, and systems are calibrated and adjusted and operate in accordance with approved plans and specifications. Sequences of operation shall be functionally tested to document they operate in accordance with approved plans and specifications.
C408.2.3.3 Economizers. Air economizers shall undergo a functional test to determine that they operate in accordance with manufacturer's specifications.
AMENDATORY SECTION (Amending WSR 16-13-089, filed 6/15/16, effective 7/16/16)
WAC 51-11C-41000 Section C410Refrigeration system requirements.
C410.1 General (prescriptive). Walk-in coolers, walk-in freezers, refrigerated warehouse coolers, refrigerated warehouse freezers, and refrigerated display cases shall comply with this Section.
Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with Section C402. Section C402.1.5 Component performance alternative, may be used if granted prior approval by the jurisdiction.
C410.1.1 Refrigeration equipment performance. Refrigeration equipment shall have an energy use in kWh/day not greater than the values of Tables C410.2(1) and C410.2(2) when tested and rated in accordance with AHRI Standard 1200. The energy use shall be verified through certification under an approved certification program or, where a certification program does not exist, the energy use shall be supported by data furnished by the equipment manufacturer.
Table C410.1.1(1)
Minimum Efficiency Requirements: Commercial Refrigeration
EQUIPMENT TYPE
APPLICATION
ENERGY USE LIMITS
(kWh per day)a
TEST PROCEDURE
Refrigerator with solid doors
Holding Temperature
0.10 x V + 2.04
AHRI 1200
Refrigerator with transparent doors
0.12 x V + 3.34
Freezers with solid doors
0.40 x V + 1.38
Freezers with transparent doors
0.75 x V + 4.10
Refrigerator/freezers with solid doors
The greater of 0.12 x V + 3.34 or 0.70
Commercial refrigerators
Pulldown
0.126 x V + 3.51
a V = Volume of the chiller for frozen compartment as defined in AHAM-HRF-1.
Table C410.1.1(2)
Minimum Efficiency Requirements: Commercial Refrigerators and Freezers
EQUIPMENT TYPE
ENERGY USE LIMITS
(kWh per day)a,b
TEST PROCEDURE
Equipment Classc
Family Code
Operating Mode
Rating Temperature
VOP.RC.M
Vertical open
Remote condensing
Medium
0.82 x TDA + 4.07
AHRI 1200
SVO.RC.M
Semivertical open
Remote condensing
Medium
0.83 x TDA + 3.18
 
HZO.RC.M
Horizontal open
Remote condensing
Medium
0.35 x TDA + 2.88
 
VOP.RC.L
Vertical open
Remote condensing
Low
2.27 x TDA + 6.85
 
HZO.RC.L
Horizontal open
Remote condensing
Low
0.57 x TDA + 6.88
 
VCT.RC.M
Vertical transparent door
Remote condensing
Medium
0.22 x TDA + 1.95
 
VCT.RC.L
Vertical transparent door
Remote condensing
Low
0.56 x TDA + 2.61
 
SOC.RC.M
Service over counter
Remote condensing
Medium
0.51 x TDA + 0.11
 
VOP.SC.M
Vertical open
Self-contained
Medium
1.74 x TDA + 4.71
 
SVO.SC.M
Semivertical open
Self-contained
Medium
1.73 x TDA + 4.59
 
HZO.SC.M
Horizontal open
Self-contained
Medium
0.77 x TDA + 5.55
 
HZO.SC.L
Horizontal open
Self-contained
Low
1.92 x TDA + 7.08
 
VCT.SC.I
Vertical transparent door
Self-contained
Ice cream
0.67 x TDA + 3.29
 
VCS.SC.I
Vertical solid door
Self-contained
Ice cream
0.38 x V + 0.88
 
HCT.SC.I
Horizontal transparent door
Self-contained
Ice cream
0.56 x TDA + 0.43
 
SVO.RC.L
Semivertical open
Remote condensing
Low
2.27 x TDA + 6.85
 
VOP.RC.I
Vertical open
Remote condensing
Ice cream
2.89 x TDA + 8.7
 
SVO.RC.I
Semivertical open
Remote condensing
Ice cream
2.89 x TDA + 8.7
 
HZO.RC.I
Horizontal open
Remote condensing
Ice cream
0.72 x TDA + 8.74
 
VCT.RC.I
Vertical transparent door
Remote condensing
Ice cream
0.66 x TDA + 3.05
 
HCT.RC.M
Horizontal transparent door
Remote condensing
Medium
0.16 x TDA + 0.13
 
HCT.RC.L
Horizontal transparent door
Remote condensing
Low
0.34 x TDA + 0.26
 
HCT.RC.I
Horizontal transparent door
Remote condensing
Ice cream
0.4 x TDA + 0.31
 
VCS.RC.M
Vertical solid door
Remote condensing
Medium
0.11 x V + 0.26
 
VCS.RC.L
Vertical solid door
Remote condensing
Low
0.23 x V + 0.54
 
VCS.RC.I
Vertical solid door
Remote condensing
Ice cream
0.27 x V + 0.63
 
HCS.RC.M
Horizontal solid door
Remote condensing
Medium
0.11 x V + 0.26
 
HCS.RC.L
Horizontal solid door
Remote condensing
Low
0.23 x V + 0.54
 
HCS.RC.I
Horizontal solid door
Remote condensing
Ice cream
0.27 x V + 0.63
 
SOC.RC.L
Service over counter
Remote condensing
Low
1.08 x TDA + 0.22
 
SOC.RC.I
Service over counter
Remote condensing
Ice cream
1.26 x TDA + 0.26
 
VOP.SC.L
Vertical open
Self-contained
Low
4.37 x TDA + 11.82
 
VOP.SC.I
Vertical open
Self-contained
Ice cream
5.55 x TDA + 15.02
 
SVO.SC.L
Semivertical open
Self-contained
Low
4.34 x TDA + 11.51
 
SVO.SC.I
Semivertical open
Self-contained
Ice cream
5.52 x TDA + 14.63
 
HZO.SC.I
Horizontal open
Self-contained
Ice cream
2.44 x TDA + 9.0
 
SOC.SC.I
Service over counter
Self-contained
Ice cream
1.76 x TDA + 0.36
 
HCS.SC.I
Horizontal solid door
Self-contained
Ice cream
0.38 x V + 0.88
 
a
V = Volume of the case, as measured in accordance with Appendix C of AHRI 1200.
b
TDA = Total display area of the case, as measured in accordance with Appendix D of AHRI 1200.
c
Equipment class designations consist of a combination [(in sequential order separated by periods (AAA).(BB).(C))] of:
 
 
(AAA) An equipment family code where:
 
 
 
VOP = Vertical open
 
 
 
SVO = Semi-vertical open
 
 
 
HZO = Horizontal open
 
 
 
VCT = Vertical transparent doors
 
 
 
VCS = Vertical solid doors
 
 
 
HCT = Horizontal transparent doors
 
 
 
HCS = Horizontal solid doors
 
 
 
SOC = Service over counter
 
 
(BB) An operating mode code:
 
 
 
RC = Remote condensing
 
 
 
SC = Self-contained
 
 
(C) A rating temperature code:
 
 
 
M = Medium temperature (38°F)
 
 
 
L = Low temperature (0°F)
 
 
 
I = Ice cream temperature (15°F)
 
 
For example, "VOP.RC.M" refers to the "vertical-open, remote-condensing, medium-temperature" equipment class.
C410.2 Walk-in coolers, walk-in freezers, refrigerated warehouse coolers and refrigerated warehouse freezers. Refrigerated warehouse coolers ((and)), refrigerated warehouse freezers ((shall comply with this section. Walk-in coolers and walk-in freezers that are not either site assembled or site constructed)), and all walk-in coolers and walk-in freezers including site assembled, site constructed and prefabricated units shall comply with the following:
1. ((Be equipped with)) Automatic door-closers shall be provided that ((firmly)) fully close walk-in doors that have been closed to within 1 inch (25 mm) of full closure.
EXCEPTION:
Automatic closers are not required for doors more than 45 inches (1143 mm) in width or more than 7 feet (2134 mm) in height.
2. Doorways shall ((have)) be provided with strip doors, curtains, spring-hinged doors or other method of minimizing infiltration when doors are open.
3. Walk-in coolers and refrigerated warehouse coolers shall ((contain)) be provided with wall, ceiling, and door insulation of not less than R-25 or have wall, ceiling and door assembly U-factors no greater than U-0.039. Walk-in freezers and refrigerated warehouse freezers shall ((contain)) be provided with wall, ceiling and door insulation of not less than R-32 or have wall, ceiling and door assembly U-factors no greater than U-0.030.
EXCEPTION:
((Glazed portions of doors or structural members need not be insulated.)) Insulation is not required for glazed portions of doors or at structural members associated with the walls, ceiling or door frame.
4. The floor of walk-in freezers shall ((contain)) be provided with floor insulation of not less than R-28 or have a floor assembly U-factor no greater than U-0.035.
5. Transparent reach-in doors for walk-in freezers and windows in walk-in freezer doors shall be ((of)) provided with triple-pane glass, ((either)) with the interstitial spaces filled with inert gas or be provided with heat-reflective treated glass.
6. ((Windows and)) Transparent reach-in doors for walk-in coolers and windows for walk-in coolers doors shall be ((of)) provided with double-pane or triple-pane((,)) glass, with interstitial space filled with inert ((gas-filled,)) gas, or be provided with heat-reflective treated glass.
7. Evaporator fan motors that are less than 1 hp (0.746 kW) and less than 460 volts shall ((use)) be provided with electronically commutated motors, brushless direct-current motors, or 3-phase motors.
8. Condenser fan motors that are less than 1 hp (0.746 kW) shall use electronically commutated motors, permanent split capacitor-type motors or 3-phase motors.
9. ((Where)) Antisweat heaters ((without)) that are not provided with antisweat heater controls ((are provided, they)) shall have a total door rail, glass and frame heater power draw of not ((more)) greater than 7.1 W/ft2 (76 W/m2) of door opening for walk-in freezers and not greater than 3.0 W/ft2 (32 W/m2) of door opening for walk-in coolers.
10. Where antisweat heater controls are provided, they shall ((reduce)) be capable of reducing the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
11. Lights in walk-in coolers, walk-in freezers, refrigerated warehouse coolers and refrigerated warehouse freezers shall either ((use)) be provided with light sources with an efficacy of not less than 40 lumens per watt, including ballast losses, or shall ((use light sources with an efficacy of not less than 40 lumens per watt, including ballast losses, in conjunction)) be provided with a device that automatically turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer space is not occupied.
C410.2.1 ((Walk-in coolers and walk-in freezers. Site-assembled or site-constructed walk-in coolers and walk-in freezers shall comply with the following:
1. Automatic door closers shall be provided that fully close walk-in doors that have been closed to within 1 inch (25 mm) of full closure.
EXCEPTION:
Closers are not required for doors more than 45 inches (1143 mm) in width or more than 7 feet (2134 mm) in height.
2. Doorways shall be provided with strip doors, curtains, spring-hinged doors or other method of minimizing infiltration when the doors are open.
3. Walk-in cooler walls, ceilings and doors shall be provided with insulation having a thermal resistance of not less than R-25 or have wall, ceiling and door assembly U-factors no greater than U-0.039. Walk-in freezers walls, ceilings and doors shall be provided with insulation having a thermal resistance of not less than R-32 or have wall, ceiling, door and slab assembly U-factors no greater than U-0.030.
EXCEPTION:
Insulation is not required for glazed portions of doors or at structural members associated with the walls, ceiling or door frame.
4. The floor of walk-in freezers shall be provided with insulation having a thermal resistance of not less than R-28 or have a floor assembly U-factor no greater than U-0.035.
5. Transparent reach-in doors for and windows in opaque walk-in freezer doors shall be provided with triple-pane glass having the interstitial spaces filled with inert gas or provided with heat-reflective treated glass.
6. Transparent reach-in doors and windows in opaque walk-in cooler doors shall be double-pane heat-reflective treated glass having the interstitial space gas filled.
7. Evaporator fan motors that are less than 1 hp (0.746 kW) and less than 460 volts shall be electronically commutated motors or 3-phase motors.
8. Condenser fan motors that are less than 1 hp (0.746 kW) in capacity shall be of the electronically commutated or permanent split capacitor-type or shall be 3-phase motors.
EXCEPTION:
Fan motors in walk-in coolers and walk-in freezers combined in a single enclosure greater than 3,000 square feet (279 m2) in floor area are exempt.
9. Antisweat heaters that are not provided with antisweat heater controls shall have a total door rail, glass and frame heater power draw not greater than 7.1 W/ft2 (76 W/m2) of door opening for walk-in freezers, and not greater than 3.0 W/ft2 (32 W/m2) of door opening for walk-in coolers.
10. Antisweat heater controls shall be capable of reducing the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
11. Light sources shall have an efficacy of not less than 40 lumens per watt, including any ballast losses, or shall be provided with a device that automatically turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer was last occupied.)) Reserved.
C410.2.2 Refrigerated display cases. Site-assembled or site-constructed refrigerated display cases shall comply with the following:
1. Lighting and glass doors in refrigerated display cases shall be controlled by one of the following:
1.1. Time switch controls to turn off lights during nonbusiness hours. Timed overrides for display cases shall turn the lights on for up to 1 hour and shall automatically time out to turn the lights off.
1.2. Motion sensor controls on each display case section that reduce lighting power by at least 50 percent within 3 minutes after the area within the sensor range is vacated.
2. Low-temperature display cases shall incorporate temperature-based defrost termination control with a time-limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second upon a time limit breach.
3. Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
C410.3 Refrigeration systems. Refrigerated display cases, walk-in coolers or walk-in freezers that are served by remote compressor and remote condensers not located in a condensing unit, shall comply with Sections C410.4.1 ((and)), C410.4.2, and C403.5.3.
EXCEPTION:
Systems where the working fluid in the refrigeration cycle goes through both subcritical and supercritical states (transcritical) or that use ammonia refrigerant are exempt.
C410.3.1 Condensers serving refrigeration systems. Fan-powered condensers shall comply with the following:
1. The design saturated condensing temperatures for air-cooled condensers shall not exceed the design dry-bulb temperature plus 10°F (5.6°C) for low-temperature refrigeration systems, and the design dry-bulb temperature plus 15°F (8°C) for medium temperature refrigeration systems where the saturated condensing temperature for blend refrigerants shall be determined using the average of liquid and vapor temperatures as converted from the condenser drain pressure.
2. Condenser fan motors that are less than 1 hp (0.75 kW) shall use electronically commutated motors, permanent split-capacitor-type motors or 3-phase motors.
3. Condenser fans for air-cooled condensers, evaporatively cooled condensers, air- or water-cooled fluid coolers or cooling towers shall reduce fan motor demand to not more than 30 percent of design wattage at 50 percent of design air volume, and incorporate one of the following continuous variable speed fan control approaches:
3.1. Refrigeration system condenser control for air-cooled condensers shall use variable setpoint control logic to reset the condensing temperature setpoint in response to ambient dry-bulb temperature.
3.2. Refrigeration system condenser control for evaporatively cooled condensers shall use variable setpoint control logic to reset the condensing temperature setpoint in response to ambient wet-bulb temperature.
4. Multiple fan condensers shall be controlled in unison.
5. The minimum condensing temperature setpoint shall be not greater than 70°F (21°C).
C410.3.2 Compressor systems. Refrigeration compressor systems shall comply with the following:
1. Compressors and multiple-compressor system suction groups shall include control systems that use floating suction pressure control logic to reset the target suction pressure temperature based on the temperature requirements of the attached refrigeration display cases or walk-ins.
EXCEPTION:
Controls are not required for the following:
 
1. Single-compressor systems that do not have variable capacity capability.
 
2. Suction groups that have a design saturated suction temperature of 30°F (-1.1°C) or higher, suction groups that comprise the high stage of a two-stage or cascade system, or suction groups that primarily serve chillers for secondary cooling fluids.
2. Liquid subcooling shall be provided for all low-temperature compressor systems with a design cooling capacity equal to or greater than 100,000 Btu/hr (29.3 kW) with a design-saturated suction temperature of -10°F (-23°C) or lower. The subcooled liquid temperature shall be controlled at a maximum temperature setpoint of 50°F (10°C) at the exit of the subcooler using either compressor economizer (interstage) ports or a separate compressor suction group operating at a saturated suction temperature of 18°F (-7.8°C) or higher.
2.1. Insulation for liquid lines with a fluid operating temperature less than 60°F (15.6°C) shall comply with Table C403.2.10.
3. Compressors that incorporate internal or external crankcase heaters shall provide a means to cycle the heaters off during compressor operation.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION (Amending WSR 16-13-089, filed 6/15/16, effective 7/16/16)
WAC 51-11C-50300 Section C503Alterations.
C503.1 General. Alterations to any building or structure shall comply with the requirements of the code for new construction. Alterations shall be such that the existing building or structure is no less conforming with the provisions of this code than the existing building or structure was prior to the alteration. Alterations to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portions of the existing building or building system to comply with this code. Alterations shall not create an unsafe or hazardous condition or overload existing building systems.
EXCEPTION:
The following alterations need not comply with the requirements for new construction provided the energy use of the building is not increased:
 
1. Storm windows installed over existing fenestration.
 
2. Surface applied window film installed on existing single pane fenestration assemblies to reduce solar heat gain provided the code does not require the glazing fenestration to be replaced.
 
3. Existing ceiling, wall or floor cavities exposed during construction provided that these cavities are insulated to full depth with insulation having a minimum nominal value of R-3.0 per inch installed per Section C402.
 
4. Construction where the existing roof, wall or floor cavity is not exposed.
 
5. Roof recover.
 
6. Air barriers shall not be required for roof recover and roof replacement where the alterations or renovations to the building do not include alterations, renovations or repairs to the remainder of the building envelope.
 
7. Replacement of existing doors that separate conditioned space from the exterior shall not require the installation of a vestibule or revolving door, provided however that an existing vestibule that separates a conditioned space from the exterior shall not be removed.
C503.2 Change in space conditioning. Any nonconditioned space that is altered to become conditioned space or semi-heated space shall be required to be brought into full compliance with this code. Any semi-heated space that is altered to become conditioned space shall be required to be brought into full compliance with this code.
EXCEPTION:
Where the component performance building envelope option in Section C402.1.5 is used to comply with this Section, the Proposed UA is allowed to be up to 110 percent of the Target UA. Where the total building performance option in Section C407 is used to comply with this section, the annual energy consumption of the proposed design is allowed to be 110 percent of the annual energy consumption otherwise allowed by Section C407.3.
C503.3 Building envelope. New building envelope assemblies that are part of the alteration shall comply with Sections C402.1 through C402.5 as applicable.
EXCEPTION:
Air leakage testing is not required for alterations and repairs, unless the project includes a change in space conditioning according to Section C503.2 or a change of occupancy or use according to Section C505.1.
C503.3.1 Roof replacement. Roof replacements shall comply with Table C402.1.3 or C402.1.4 where the existing roof assembly is part of the building thermal envelope and contains insulation entirely above the roof deck.
C503.3.2 Vertical fenestration. The addition of vertical fenestration that results in a total building vertical fenestration area less than or equal to that specified in Section C402.4.1 shall comply with Section C402.4. Alterations that result in a total building vertical fenestration area greater than specified in Section C402.4.1 shall comply with one of the following:
1. Vertical fenestration alternate per Section C402.1.3 for the new vertical fenestration added.
2. Vertical fenestration alternate per Section C402.4.1.1 for the area adjacent to the new vertical fenestration added.
3. Component performance option with target area adjustment per Section C402.1.5 or the total building performance option in Section C407 for the whole building.
C503.3.2.1 Application to replacement fenestration products. Where some or all of an existing fenestration unit is replaced with a new fenestration product, including sash and glazing, the replacement fenestration unit shall meet the applicable requirements for U-factor and SHGC in Table C402.4.
EXCEPTION:
An area-weighted average of the U-factor of replacement fenestration products being installed in the building for each fenestration product category listed in Table C402.4 shall be permitted to satisfy the U-factor requirements for each fenestration product category listed in Table C402.4. Individual fenestration products from different product categories listed in Table C402.4 shall not be combined in calculating the area-weighted average U-factor.
C503.3.3 Skylight area. The addition of skylights that results in a total building skylight area less than or equal to that specified in Section C402.4.1 shall comply with Section C402.4. Alterations that result in a total building skylight area greater than that specified in Section C402.4.1 shall comply with the component performance option with target area adjustment per Section C402.1.5 or the total building performance option in Section C407 for the whole building.
C503.4 Mechanical systems. Those parts of systems which are altered or replaced shall comply with Section C403. Additions or alterations shall not be made to an existing mechanical system that will cause the existing mechanical system to become out of compliance.
EXCEPTION:
Existing mechanical systems which are altered or where parts of the systems are replaced are not required to be modified to comply with Section C403.6 as long as mechanical cooling is not added to the system.
All new systems in existing buildings, including packaged unitary equipment and packaged split systems, shall comply with Section C403.
Where mechanical cooling is added to a space that was not previously cooled, the mechanical system shall comply with either Section C403.6 or C403.3.
EXCEPTIONS:
1. Alternate designs that are not in full compliance with this code may be approved when the code official determines that existing building constraints including, but not limited to, available mechanical space, limitations of the existing structure, or proximity to adjacent air intakes/exhausts make full compliance impractical. Alternate designs shall provide alternate energy savings strategies including, but not limited to, Demand Control Ventilation or increased mechanical cooling or heating efficiency above that required by Tables C403.2.3(1) through C403.2.3(10).
 
2. Qualifying small equipment: This exception shall not be used for unitary cooling equipment installed outdoors or in a mechanical room adjacent to the outdoors. This exception is allowed to be used for other cooling units and split systems serving one zone with a total cooling capacity rated in accordance with Section C403.2.3 of less than 33,000 Btu/h (hereafter referred to as qualifying small systems) provided that these are high-efficiency cooling equipment with SEER and EER values more than 15 percent higher than minimum efficiencies listed in Tables C403.2.3 (1) through (3), in the appropriate size category, using the same test procedures. Equipment shall be listed in the appropriate certification program to qualify for this exception. The total capacity of all qualifying small equipment without economizers shall not exceed 72,000 Btu/h per building, or 5 percent of its air economizer capacity, whichever is greater. That portion of the equipment serving Group R occupancies is not included in determining the total capacity of all units without economizers in a building. Redundant units are not counted in the capacity limitations. This exception shall not be used for the shell-and-core permit or for the initial tenant improvement or for Total Building Performance.
 
3. Chilled water terminal units connected to systems with chilled water generation equipment with IPLV values more than 25 percent higher than minimum part load efficiencies listed in Table C403.2.3(7), in the appropriate size category, using the same test procedures. Equipment shall be listed in the appropriate certification program to qualify for this exception. The total capacity of all systems without economizers shall not exceed 480,000 Btu/h per building, or 20 percent of its air economizer capacity, whichever is greater. That portion of the equipment serving Group R occupancy is not included in determining the total capacity of all units without economizers in a building. This exception shall not be used for the initial permit (this includes any initial permit for the space including, but not limited to, the shell-and-core permit, built-to-suit permit, and tenant improvement permit) or for Total Building Performance Method.
Alterations to existing mechanical cooling systems shall not decrease economizer capacity unless the system complies with either Section C403.2.6 or C403.3. In addition, for existing mechanical cooling systems that do not comply with either Section C403.2.6 or C403.3, including both the individual unit size limits and the total building capacity limits on units without economizer; other alterations shall comply with Table C503.4.
When space cooling equipment is replaced, controls shall comply with all requirements under Section C403.6 and related subsections or provide for integrated operation with economizer in accordance with Section C403.3.1.
Existing equipment currently in use may be relocated within the same floor or same tenant space if removed and reinstalled within the same permit.
Table C503.4
Economizer Compliance Options for Mechanical Alterations
 
Option A
Option B
(alternate to A)
Option C
(alternate to A)
Option D
(alternate to A)
Unit Type
Any alteration with new or replacement equipment
Replacement unit of the same type with the same or smaller output capacity
Replacement unit of the same type with a larger output capacity
New equipment added to existing system or replacement unit of a different type
1. Packaged Units
Efficiency: min.1
Economizer: C403.32
Efficiency: min.1
Economizer: C403.32,3
Efficiency: min.1
Economizer: C403.32,3
Efficiency: min.1
Economizer: C403.32,4
2. Split Systems
Efficiency: min.1
Economizer: C403.32
Efficiency: + 10/5%5
Economizer: shall not decrease existing economizer capability
Only for new units
< 54,000 Btuh replacing unit installed prior to 1991 (one of two):
Efficiency: + 10/5%5
Economizer: 50%6
Efficiency: min.1
Economizer: C403.32,4
For units > 54,000 Btuh or any units installed after 1991:
Option A
3. Water Source Heat Pump
Efficiency: min.1
Economizer: C403.32
(two of three):
Efficiency: + 10/5%5
Flow control valve7
Economizer: 50%6
(three of three):
Efficiency: + 10/5%5
Flow control valve7
Economizer: 50%6 (except for certain pre-1991 systems8)
Efficiency: min.1
Economizer: C403.32,4
(except for certain pre-1991 systems8)
4. Hydronic Economizer using Air-Cooled Heat Rejection Equipment (Dry Cooler)
Efficiency: min.1
Economizer: 14332
Efficiency: + 10/5%5
Economizer: shall not decrease existing economizer capacity
Option A
Efficiency: min.1
Economizer: C403.32,4
5. Air-Handling Unit (including fan coil units)
where the system has an air-cooled chiller
Efficiency: min.1
Economizer: C403.32
Economizer: shall not decrease existing economizer capacity
Option A
(except for certain pre-1991 systems8)
Option A
(except for certain pre-1991 systems8)
6. Air-Handling Unit (including fan coil units) and Water-cooled Process Equipment, where the system has a water-cooled chiller10
Efficiency: min.1
Economizer: C403.32
Economizer: shall not decrease existing economizer capacity
Option A
(except for certain pre-1991 systems8 and certain 1991-2004 systems9)
Efficiency: min.1
Economizer: C403.32,4
(except for certain pre-1991 systems8 and certain 1991-2015 systems9)
7. Cooling Tower
Efficiency: min.1
Economizer: C403.32
No requirements
Option A
Option A
8. Air-Cooled Chiller
Efficiency: min.1
Economizer: C403.32
Efficiency: + 5%11
Economizer: shall not decrease existing economizer capacity
Efficiency
(two of two):
(1) + 10%12 and
(2) multistage
Economizer: shall not decrease existing economizer capacity
Efficiency: min.1
Economizer: C403.32,4
9. Water-Cooled Chiller
Efficiency: min.1
Economizer: C403.32
Efficiency
(one of two):
(1) + 10%13 or
(2) plate frame heat exchanger15
Economizer: shall not decrease existing economizer capacity
Efficiency
(two of two):
(1) + 15%14 and
(2) plate-frame heat exchanger15
Economizer: shall not decrease existing economizer capacity
Efficiency: min.1
Economizer: C403.32,4
10. Boiler
Efficiency: min.1
Economizer: C403.32
Efficiency: + 8%16
Economizer: shall not decrease existing economizer capacity
Efficiency: + 8%16
Economizer: shall not decrease existing economizer capacity
Efficiency: min.1
Economizer: C403.32,4
1
Minimum equipment efficiency shall comply with Section C403.2.3 and Tables C403.2.3(1) through C403.2.3(10).
2
System and building shall comply with Section C403.3 (including both the individual unit size limits and the total building capacity limits on units without economizer). It is acceptable to comply using one of the exceptions to Section C403.3 or C504.3.4.
3
All equipment replaced in an existing building shall have air economizer complying with Section C403.3 unless both the individual unit size and the total capacity of units without air economizer in the building is less than that allowed in Exception 2 to Section C503.4.
4
All separate new equipment added to an existing building shall have air economizer complying with Section C403.3 unless both the individual unit size and the total capacity of units without air economizer in the building is less than that allowed in Exception 3 to Section C503.4.
5
Equipment shall have a capacity-weighted average cooling system efficiency:
a.
For units with a cooling capacity below 54,000 Btuh, a minimum of 10% greater than the requirements in Tables C403.2.3(1) and C403.2.3(2).
b.
For units with a cooling capacity of 54,000 Btuh and greater, a minimum of 5% greater than the requirements in Tables C403.2.3(1) and C403.2.3(2).
6
Minimum of 50% air economizer that is ducted in a fully enclosed path directly to every heat pump unit in each zone, except that ducts may terminate within 12 inches of the intake to an HVAC unit provided that they are physically fastened so that the outside air duct is directed into the unit intake. If this is an increase in the amount of outside air supplied to this unit, the outside air supply system shall be configured to provide this additional outside air and equipped with economizer control.
7
Have flow control valve to eliminate flow through the heat pumps that are not in operation with variable speed pumping control complying with Section C403.4.2 for that heat pump.
 
 
- When the total capacity of all units with flow control valves exceeds 15% of the total system capacity, a variable frequency drive shall be installed on the main loop pump.
 
 
- As an alternate to this requirement, have a capacity-weighted average cooling system efficiency that is 5% greater than the requirements in note 5 (i.e., a minimum of 15%/10% greater than the requirements in Tables C403.2.3(1) and C403.2.3(2)).
8
Systems installed prior to 1991 without fully utilized capacity are allowed to comply with Option B, provided that the individual unit cooling capacity does not exceed 90,000 Btuh.
9
Economizer not required for systems installed with water economizer plate and frame heat exchanger complying with previous codes between 1991 and June 2016, provided that the total fan coil load does not exceed the existing or added capacity of the heat exchangers.
10
For water-cooled process equipment where the manufacturers specifications require colder temperatures than available with waterside economizer, that portion of the load is exempt from the economizer requirements.
11
The air-cooled chiller shall have an IPLV efficiency that is a minimum of 5% greater than the IPLV requirements in Table C403.2.3(7).
12
The air-cooled chiller shall:
a.
Have an IPLV efficiency that is a minimum of 10% greater than the IPLV requirements in Table C403.2.3(7); and
b.
Be multistage with a minimum of two compressors.
13
The water-cooled chiller shall have an IPLV efficiency that is a minimum of 10% greater than the IPLV requirements in Table C403.2.3(7).
14
The water-cooled chiller shall have an IPLV efficiency that is a minimum of 15% greater than the IPLV requirements in Table C403.2.3(7).
15
Economizer cooling shall be provided by adding a plate-frame heat exchanger on the waterside with a capacity that is a minimum of 20% of the chiller capacity at standard AHRI rating conditions.
16
The replacement boiler shall have an efficiency that is a minimum of 8% higher than the value in Table C403.2.3(5), except for electric boilers.
C503.5 Service hot water systems. New service hot water systems that are part of the alteration shall comply with Section C404.
C503.6 Lighting and motors. Alterations that replace 50 percent or more of the luminaires in a space enclosed by walls or ceiling-height partitions, replace 50 percent or more of parking garage luminaires, or replace 50 percent or more of the total installed wattage of exterior luminaires shall comply with Sections C405.4 and C405.5. Where less than 50 percent of the fixtures in an interior space enclosed by walls or ceiling-height partitions or parking garage are new, or less than 50 percent ((or more)) of the installed exterior wattage is altered, the installed lighting wattage shall be maintained or reduced.
Where new wiring is being installed to serve added fixtures and/or fixtures are being relocated to a new circuit, controls shall comply with Sections C405.2.1, C405.2.3, C405.2.4, C405.2.5, C405.2.7, C405.3, and as applicable C408.3. In addition, office areas less than 300 ft2 enclosed by walls or ceiling-height partitions, and all meeting and conference rooms, and all school classrooms, shall be equipped with occupancy sensors that comply with Section C405.2.1 and C408.3. Where a new lighting panel (or a moved lighting panel) with all new raceway and conductor wiring from the panel to the fixtures is being installed, controls shall also comply with the other requirements in Sections C405.2 and C408.3.
Where new walls or ceiling-height partitions are added to an existing space and create a new enclosed space, but the lighting fixtures are not being changed, other than being relocated, the new enclosed space shall have controls that comply with Sections C405.2.1, C405.2.2, C405.2.3, C405.2.4, C405.2.5 and C408.3.
Those motors which are altered or replaced shall comply with Section C405.8.
C503.7 Refrigeration systems. Those parts of systems which are altered or replaced shall comply with Section C410. Additions or alterations shall not be made to an existing refrigerated space or system that will cause the existing mechanical system to become out of compliance. All new refrigerated spaces or systems in existing buildings, including refrigerated display cases, shall comply with Section C410.