Minimum Efficiency | |||||
Equipment Type | Size Category (Input) | Subcategory or Rating Condition | Test Procedurea | ||
PTAC (cooling mode) new construction | All Capacities | 95°F db outdoor air | 14.0 - (0.300 × Cap/1000) EER | AHRI 310/380 | |
PTAC (cooling mode) replacementsb | All Capacities | 95°F db outdoor air | 10.9 - (0.213 × Cap/1000) EER | ||
PTHP (cooling mode) new construction | All Capacities | 95°F db outdoor air | 14.0 - (0.300 × Cap/1000) EER | ||
PTHP (cooling mode) replacementsb | All Capacities | 95°F db outdoor air | 10.8 - (0.213 × Cap/1000) EER | ||
PTHP (heating mode) new construction | All Capacities | — | 3.7 - (0.052 × Cap/1000) COP | ||
PTHP (heating mode) replacementsb | All Capacities | — | 2.9 - (0.026 × Cap/1000) COP | ||
SPVAC (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor air | 11.0 EER | AHRI 390 | |
≥ 65,000 Btu/h and < 135,000 Btu/h | 95°F db/75°F wb outdoor air | ((11.0))10.0 EER | |||
≥ 135,000 Btu/h and < 240,000 Btu/h | 95°F db/75°F wb outdoor air | ((11.0))10.0 EER | |||
SPVHP (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor air | 11.0 EER | ||
≥ 65,000 Btu/h and < 135,000 Btu/h | 95°F db/75°F wb outdoor air | ((11.0))10.0 EER | |||
≥ 135,000 Btu/h and < 240,000 Btu/h | 95°F db/75°F wb outdoor air | ((11.0))10.0 EER | |||
SPVHP (heating mode) | <65,000 Btu/h | 47°F db/43°F wb outdoor air | 3.3 COP | AHRI 390 | |
≥ 65,000 Btu/h and < 135,000 Btu/h | 47°F db/43°F wb outdoor air | ((3.3))3.0 COP | |||
≥ 135,000 Btu/h and < 240,000 Btu/h | 47°F db/43°F wb outdoor air | ((3.3))3.0 COP | |||
Room air conditioners, with louvered sides | < 6,000 Btu/h | — | 11.0 CEER | ANSI/AHA-MRAC-1 | |
≥ 6,000 Btu/h and < 8,000 Btu/h | — | 11.0 CEER | |||
≥ 8,000 Btu/h and < 14,000 Btu/h | — | 10.9 CEER | |||
≥ 14,000 Btu/h and < 20,000 Btu/h | — | 10.7 CEER | |||
≥ 20,000 Btu/h and < 25,000 Btu/h | — | 9.4 CEER | |||
≥ 25,000 Btu/h | — | 9.0 CEER | |||
Room air conditioners, without louvered sides | < 6,000 Btu/h | — | 10.0 CEER | ||
≥ 6,000 Btu/h and < 8,000 Btu/h | — | 10.0 CEER | |||
≥ 8,000 Btu/h and < 11,000 Btu/h | — | 9.6 CEER | |||
≥ 11,000 Btu/h and < 14,000 Btu/h | — | 9.5 CEER | |||
≥ 14,000 Btu/h and < 20,000 Btu/h | — | 9.3 CEER | |||
≥ 20,000 Btu/h | — | 9.4 CEER | |||
Room air-conditioner heat pumps with louvered sides | < 20,000 Btu/h | — | 9.8 CEER | ||
≥ 20,000 Btu/h | — | 9.3 CEER | |||
Room air-conditioner heat pumps without louvered sides | < 14,000 Btu/h | — | 9.3 CEER | ||
≥ 14,000 Btu/h | — | 8.7 CEER | |||
Room air conditioner casement only | All capacities | — | 9.5 CEER | ||
Room air conditioner casement-slider | All capacities | — | 10.4 CEER |
For SI: | 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8. |
"Cap" = The rated cooling capacity of the product in Btu/h. If the unit's capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculations. | |
a | Chapter 12 of the referenced standard contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. |
b | Replacement unit shall be factory labeled as follows: "manufactured for nonstandard size applications only; not to be installed in new standard projects" or "manufactured for replacement applications only: not to be installed in new construction projects." Replacement efficiencies apply only to units with existing sleeves less than 16 inches (406 mm) in height and less than 42 inches (1067 mm) in width. |