WAC | Section | Change | Rationale/Discussion |
51-51-003 | IRC | Modifies the text, replaces Appendix U with Appendix WU. | Currently, there is a model code Appendix U and Washington state Appendix U. This modification is necessary to avoid confusion. |
51-51-008 | Implementation | Changes the implementation date from "July 1, 2023" to "October 29, 2023." | Change made to correlate with filing which changed the implementation date. |
51-51-01010 | R101.2 | In the exceptions, replaces Appendix U with Appendix WU. | Currently, there is a model code Appendix U and Washington state Appendix U. This modification is necessary to avoid confusion. |
51-51-0102 | R102.5 | • In the exceptions, replaces Appendix U with Appendix WU. • Adds Appendix T to Exception 1. • Adds Appendices Y and Z to Exception 1. | • Currently, there is a model code Appendix U and Washington state Appendix U. This modification is necessary to avoid confusion. • Corrects an oversight; the title (solar-ready zone) was included, but Appendix T was omitted. • Appendices Y and Z were adopted by the state building code council (SBCC) in the 2021 IRC; they are not mandatory unless specifically referenced in the adopting ordinance. Nevertheless, Appendices Y and Z were not added to Exception 1 in Section R102.5, as intended. |
51-51-0301 | R301.2 | Changes table reference from "R301.2(1)" to "R301.2." | Editorial correction with no change in regulatory effect. |
Table R301.5 | On the handrail row, relocates "200h" from the "Uniform Load" column to the "Concentrated Load" column. On the "Passenger vehicle garages" row, changes the concentrated load value footnote from "h" to "a." | Editorial correction with no change in regulatory effect. These values were corrected with the International Code Council errata. | |
Table R301.5 Footnote g.2. | Changes the word "inches" to "units." | Editorial correction with no change in regulatory effect; intended to align the state amendment with the model code language. | |
51-51-0302 | R302.3.1 Exception 1. | Changes reference from "NFPA 13D" to "Section 2904." | Editorial correction with no change in regulatory effect; intended to align the state amendment with the model code language. SBCC adopts Section 2904, which allows residential sprinkler systems to be designed and installed in accordance with NFPA 13D or Section P2904. IRC technical advisory group recommended replacing NFPA 13D with Section P2904; however, this recommendation was inadvertently omitted. |
R302.3.4 Exception. | Adds the word "NFPA" before "13D." | Editorial correction with no change in regulatory effect. | |
R302.13 Exception 1. | Changes reference to Appendix "U" to "WU." | Currently, there is a model code Appendix U and Washington state Appendix U. This modification is necessary to avoid confusion. | |
R302.13 Exception 4. | Changes the word "dimensional" to "dimension." | Editorial correction with no change in regulatory effect; intended to align the state amendment with the model code language. | |
51-51-0303 | R303.10 | Changes Table reference from "R301.2(1)" to "R301.2." | Editorial correction with no change in regulatory effect; intended to provide the correct reference. Table R301.2(1) does not exist. |
51-51-0311 | R311.4 | Adds "a" between the words "by" and "ramp." | Editorial correction with no change in regulatory effect. |
R311.7.12 | Adds a metric measurement (508 mm) for 20 inches. | Editorial correction with no change in regulatory effect. | |
51-51-0312 | R312.1.1 | Adds the term "floors" to the first sentence. | Editorial modification for consistency with the model code language. |
51-51-0314 | R314.4 | Changes reference "R314.2" to "R314.3." | Editorial correction with no change in regulatory effect. |
51-51-03240 | R324.3 | Changes the word "alternate" with "alternative." | Editorial correction with no change in regulatory effect; intended to align the state amendment with the model code language. |
R324.4 Exceptions. | Adds metric dimensions in Exceptions 2, 3, 4, and 5. | Editorial correction with no change in regulatory effect. | |
51-51-0326 | R326.1 | Adds "s" after the word "attic" in the title and changes reference from "R326" to "R326.1." | Editorial corrections with no change in regulatory effect. |
51-51-0330 | R330.3 | Adds the word "section" before reference to "R330.9" in items 2 and 3. | Editorial correction with no change in regulatory effect. |
R330.8.1 R330.8.2 R330.8.3 R330.8.3.1 R330.8.3.2 R330.8.4.1 R330.8.4.2 R330.8.5.1 R330.8.5.2 R330.11 | Adds metric measurements. | Editorial correction with no change in regulatory effect. | |
51-51-0331 | R331 | Replaces the term "fire-resistive" with "fire-resistant" in the last sentence and last exception. | Editorial modification with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-0333 | R333.5.1 | Adds metric measurement (914) for three feet. | Editorial modification with no change in regulatory effect. |
51-51-0403 | Figure R403.1.1 (1), R403.1.1 (2), R403.1.1 (3), R403.1.1 (4) footnote c. | Spells out feet. | Editorial modifications with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-0408 | R408.1 | Replaces the word "six" with the number "6" and adds a metric measurement (152 mm) for six inches. | Editorial modifications with no change in regulatory effect; intended to align the state amendment with the model code language. |
R408.1 Exception | Replaces the word "two" with the number "2" and adds a metric measurement (51 mm) for two inches. | ||
51-51-0507 | Table 507.3.1 | • Identifying the applicable cells for the footnotes. • Editorial modifications. | Editorial modifications with no change in regulatory effect; intended to align the state amendment with the model code language. |
Table 507.4 | Reformatting Table 507.4. | ||
R507.5 | Modifications to the second and third sentence. | ||
Table 507.6 | Identifying the applicable cells for the footnotes. | ||
Table 507.9.1.3 (2) | The table number is corrected from R507.9.1 to R507.9.1.3(2). | ||
Table 507.9.1.3 (2) footnote a. | Replaces the reference to Figure 507.2.1(1) with reference to Figure R507.9.1.3(1). | ||
Table 507.9.1.3 (2) footnote d. | Adds the words "or bolts" to the text and replaces the reference to Figure 507.2.1(1) with reference to Figure R507.9.1.3(1). | ||
Table R507.9.3(1) | Deletes entire table. | Table R507.9.3(1) is not referenced anywhere and it is not needed; it duplicates the values in Table 507.9.1.3(1). | |
51-51-1001 | R1001.7.1 #2 | Adds metric measurement (3870 mm2) for six square inches. | Editorial modification with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-1002 | R1002.2.1 #2 | Replaces "5%" with "5 percent." | Editorial modification with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-1006 | R1006.6 | Replaces the phrase "as per" with the phrase "in accordance with" and adds metric measurements for four inches and 20 feet. | Editorial modification with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-1413 | M1413.1 | Replaces "of" with "or"; replaces the reference to Section M1305.1.4.1 with Section M1305.1.3.1. | Editorial modification with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-1505 | M1505.4.1 | Replaces the phrase "as per" with the phrase "in accordance with." | Editorial modifications with no change in regulatory effect; intended to align the state amendment with the model code language. |
M1505.4.1.3 | Spells out the International Mechanical Code. | ||
M1505.4.2 #3 | Replaces the phrase "as per" with the phrase "in accordance with." | ||
51-51-1600 | M1601.1.1 #7.4 | • Replaces the reference to Section R602.8 with Section R302.11. • Adds a new sentence. | Editorial modifications with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-2000 | M2005.1 | Replaces the reference to Section M1305.1.3 with Section M1305.1.2. | Editorial modification with no change in regulatory effect; intended to align the state amendment with the model code language. |
51-51-2300 | M2301.4 | Replaces "liquids" with "fluids" in the first sentence. | Editorial modification for consistency with the model code language. |
51-51-2904 | P2904.1.1 | Adds exceptions 3 and 4. | Editorial modification for consistency with the model code and the Washington Appendix U. Exceptions 3 and 4 are part of the model code and Appendix WU. |
51-51-4400 | ASTM E2556/E2556M | Corrects the adopted version of the standard. | Incorporates an errata item from the model code. There is no change in the referenced standard; only the title is corrected. |
51-51-4500 | R4502.5.3 R4502.5.5 | Replaces the phrase "as per" with the phrase "in accordance with." | Editorial modification with no change in regulatory effect; intended to align the state amendment with the model code language and format. |
R4502.6 | Replaces the reference to Section R301.3(1) with R301.2. | Editorial modification with no change in regulatory effect; corrects an oversight. | |
1-51-60103 | AF103.1 | Replaces the reference to AF103 with AF103.1. | Editorial modification with no change in regulatory effect; corrects an oversight. |
51-51-60104 | AQ102 | Deletes existing state amendments and refers to Chapter 2 for the new definition of "loft." | SBCC adopted new requirements for lofts in Section R333, defined the term "loft" in Chapter 2, and repealed the defined term "sleeping loft." Nevertheless, the existing amendments in WAC 51-51-60104 were inadvertently readopted, which created a conflict with the new amendments. This proposal corrects the oversight. |
AQ103.1 Exception | Replaces the term "sleeping lofts," which is no longer used in the 2021 IRC, with the newly adopted term "loft." Replaces the reference to Section R326 with a reference to Section R333. | Corrects an oversight; there is no intended change in regulatory effect. | |
AQ104.1 | In the first sentence, replaces "feet" with "square foot." | Corrects a typo. | |
AQ106 | Adds text clarifying that Section AQ106 is not adopted. | The modification is necessary to correct an oversight. | |
51-51-60105 | Appendix WU | Replaces Appendix "U" with Appendix "WU" in the title. | Currently, there is a model code Appendix U and Washington state Appendix U. This modification is necessary to avoid confusion. |
51-51-60106 | AT102.1 | Adds Section AT102.1. | Editorial modification for consistency with the model code language and format. |
51-51-60107 | Appendix WV | Replaces Appendix "V" with Appendix "WV" in the title and in Section AV107.1. The section number is also corrected to include W – WAV107.1. | Currently, there is a model code Appendix V and Washington state Appendix V. This modification is necessary to avoid confusion. |
51-51-60108 | Appendix WY | Replaces Appendix "Y" with Appendix "WY" in the title. The section numbers are also corrected to include W. | Appendix Y is a Washington state amendment adopted by SBCC. Currently, there is no model code Appendix Y. However, the letter "W" is added to the title and the section numbers to clarify that Appendix Y is a state amendment, and to avoid confusions if the model code adds Appendix Y in the future. |
AY101.2 | Adds metric measurement (69.68m2) for 750 square feet. | Editorial modification for consistency with the model code language and format. | |
AY102.1 | Adds Section "AY102.1 General." | ||
51-51-60109 | Appendix WZ | Replaces Appendix "Z" with Appendix "WZ" in the title. The section numbers are also corrected to include W. | Appendix Z is a Washington state amendment adopted by SBCC. Currently, there is no model code Appendix Z. However, the letter "W" is added to the title and the section numbers to clarify that Appendix Z is a state amendment, and to avoid confusions if the model code adds Appendix Z in the future. |
AZ101.2 | Adds metric measurement (69.68 m2) for 750 square feet. | Editorial. No change in regulatory effect. | |
AZ101.2 Exception 3 | Deletes the words "building official." | Editorial modification; corrects an oversight. |
EXCEPTIONS: | 1. Live/work units located in townhouses and complying with the requirements of Section 508.5 of the International Building Code shall be permitted to be constructed in accordance with the International Residential Code for One- and Two-Family Dwellings. An automatic sprinkler system required by Section 508.5.7 of the International Building Code where constructed under the International Residential Code for One- and Two-Family Dwellings shall conform to Appendix WU. |
2. Owner-occupied lodging houses with one or two guestrooms shall be permitted to be constructed in accordance with the International Residential Code forOne- and Two-Family Dwellings. | |
3. Owner-occupied lodging homes with three to five guestrooms shall be permitted to be constructed in accordance with the International Residential Code for One- and Two-Family Dwellings where equipped with an automatic fire sprinkler system in accordance with Appendix WU. | |
4. A care facility with five or fewer persons receiving custodial care within a dwelling unit shall be permitted to be constructed in accordance with the International Residential Code for One- and Two-Family Dwellings where equipped with an automatic fire sprinkler system in accordance with Appendix WU. | |
5. A care facility with five or fewer persons receiving medical care within a dwelling unit shall be permitted to be constructed in accordance with the International Residential Code for One- and Two-Family Dwellings where equipped with an automatic fire sprinkler system in accordance with Appendix WU. | |
6. A care facility with five or fewer persons receiving care that are within a single-family dwelling shall be permitted to be constructed in accordance with the International Residential Code for One- and Two-Family Dwellings where equipped with an automatic fire sprinkler system in accordance with Appendix WU. |
EXCEPTIONS: | 1. The state building code council has determined that a local ordinance providing specifications for light straw-clay or strawbale construction, ((or)) requiring a solar-ready zone, ((or)) requiring fire sprinklers, or addressing construction and demolition material management or building deconstruction in accordance with Appendix R, S, ((or V))T, WV, WY, or WZ of this ((chapter))code may be adopted by any local government upon notification of the council. |
2. Appendix F, Radon Control Methods, Appendix Q, Tiny Homes, and Appendix WU, Dwelling Unit Fire Sprinkler Systems, are included in adoption of the International Residential Code. |
EXCEPTIONS: | 1. Additions with less than 500 square feet of conditioned floor area are exempt from the requirements for Whole-House Ventilation Systems, Section M1505.4. |
2. Additions or alterations to existing buildings which do not require the construction of foundations, crawlspaces, slabs or basements shall not be required to meet the requirements for radon protection in Section R332.1 and Appendix F. |
EXCEPTION: | Group R-3 buildings or structures are not required to comply if: |
1. The original occupancy classification is not changed; and | |
2. The original building is not substantially remodeled or rehabilitated. For the purposes of this section a building shall be considered to be substantially remodeled when the costs of remodeling exceed 60 percent of the value of the building exclusive of the costs relating to preparation, construction, demolition or renovation of foundations. |
Use | Uniform Load (psf) | Concentrated Load (lb) | ||
Uninhabitable attics without storageb | 10 | - | ||
Uninhabitable attics with limited storageb, g | 20 | - | ||
Habitable attics and attics served with fixed stairs | 30 | - | ||
Balconies (exterior) and deckse | 60j | - | ||
Fire escapes | 40 | - | ||
Guards | - | 200h,i | ||
Guard in-fill componentsf | - | 50h | ||
Handraild | ((200h))- | ((-))200h | ||
Passenger vehicle garagesa | 50a | 2,000((h))a | ||
Areas other than sleeping areas | 40 | - | ||
Sleeping areas | 30 | - | ||
Stairs | 40c | 300c |
For SI: 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm, 1 pound = 4.45 N | |
a. | Elevated garage floors shall be capable of supporting the uniformly distributed live load or a 2,000-pound concentrated load applied on an area of 4-1/2 inches by 4-1/2 inches, whichever produces the greater stresses. |
b. | Uninhabitable attics without storage are those where the clear height between joists and rafters is not more than 42 inches, or where there are not two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This live load need not be assumed to act concurrently with any other live load requirements. |
c. | Individual stair treads shall be capable of supporting the uniformly distributed live load or a 300-pound concentrated load applied on an area of 2 inches by 2 inches, whichever produces the greater stresses. |
d. | A single concentrated load applied in any direction at any point along the top. For a guard not required to serve as a handrail, the load need not be applied to the top element of the guard in a direction parallel to such element. |
e. | See Section R507.1 for decks attached to exterior walls. |
f. | Guard in-fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement. |
g. | Uninhabitable attics with limited storage are those where the clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met: |
g.1. | The attic area is accessed from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is not less than 30 inches. |
g.2. | The slopes of the joists or truss bottom chords are not greater than 2 ((inches))units vertical to 12 units horizontal. |
g.3. | Required insulation depth is less than the joist or truss bottom chord member depth. The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot. |
h. | Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to occur with any other live load. |
i. | Where the top of a guard system is not required to serve as a handrail, the single concentrated load shall be applied at any point along the top, in the vertical downward direction and in the horizontal direction away from the walking surface. Where the top of a guard is also serving as the handrail, a single concentrated load shall be applied in any direction at any point along the top. Concentrated loads shall not be applied concurrently. |
j. | Where structural tables in Section R507 only specify snow loads, the values corresponding to 70 psf snow loads shall be used. |
EXCEPTION: | Common walls are permitted to extend to and be tight against the interior side of the exterior walls if the cavity between the end of the common wall and the exterior sheathing is filled with a minimum of 2-inch nominal thickness wood studs. |
![]() |
EXCEPTION: | A parapet is not required in the preceding two cases where the roof covering complies with a minimum Class C rating as tested in accordance with ASTM E108 or UL 790 and the roof decking or sheathing is of noncombustible materials or fire retardant-treated wood for a distance of 4 feet (1219 mm) on each side of the wall or walls, or one layer of 5/8-inch (15.9 mm) Type X gypsum board is installed directly beneath the roof decking or sheathing, supported by not less than nominal 2-inch (51 mm) ledgers attached to the sides of the roof framing members, for a distance of not less than 4 feet (1219 mm) on each side of the wall or walls and any openings or penetrations in the roof are not within 4 feet (1219 mm) of the common walls. Fire retardant-treated wood shall meet the requirements of Sections R802.1.5 and R803.2.1.2. |
a | The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the eave overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing. |
b | The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the rake overhang where ventilation openings are not installed in the rake overhang or in walls that are common to attic areas. |
a | For residential subdivisions where all dwellings are equipped throughout with an automatic sprinkler system installed in accordance with Section P2904, the fire separation distance for exterior walls not fire-resistance-rated and for fire-resistance-rated projections shall be permitted to be reduced to 0 feet, and unlimited unprotected openings and penetrations shall be permitted, where the adjoining lot provides an open setback yard that is 6 feet or more in width on the opposite side of the property line. |
b | The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the eave overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing. |
c | The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the rake overhang where ventilation openings are not installed in the rake overhang or in walls that are common to attic areas. |
EXCEPTIONS: | 1. A fire-resistance rating of 1/2 hour shall be permitted in buildings equipped throughout with an automatic sprinkler system installed in accordance with ((NFPA 13D))Section 2904. |
2. Where an accessory dwelling unit is added within an existing single-family residence to create a two-family dwelling, fire-rated separation between the accessory dwelling unit and the primary dwelling unit is not required when all required smoke alarms are interconnected in such a manner that the actuation of one alarm will activate all alarms in both the primary dwelling unit and the accessory dwelling unit. |
EXCEPTION: | Wall assemblies need not extend through attic spaces where the ceiling is protected by not less than 5/8-inch (15.9 mm) Type X gypsum board, an attic draft stop constructed as specified in Section R302.12.1 is provided above and along the wall assembly separating the dwellings and the structural framing supporting the ceiling is protected by not less than 1/2-inch (12.7 mm) gypsum board or equivalent. |
EXCEPTION: | A 20-minute fire-rated door assembly is permitted in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section P2904 or NFPA 13D. |
SEPARATION | MATERIAL |
From the dwelling units and attics. | Not less than 1/2-inch gypsum board or equivalent applied to the accessory room side wall. |
From habitable rooms above or below the shared accessory room. | Not less than 5/8-inch Type X gypsum board or equivalent. |
Structures supporting floor/ceiling assemblies used for separation required by this section. | Not less than 1/2-inch gypsum board or equivalent. |
EXCEPTIONS: | 1. Floor assemblies located directly over a space protected by an automatic sprinkler system in accordance with Appendix WU, NFPA 13D, or other approved equivalent sprinkler system. |
2. Floor assemblies located directly over a crawl space not intended for storage or fuel-fired appliances. | |
3. Portions of floor assemblies shall be permitted to be unprotected when complying with the following: | |
3.1. The aggregate area of the unprotected portions shall not exceed 80 square feet per story. | |
3.2. Fire blocking in accordance with Section R302.11.1 is installed along the perimeter of the unprotected portion to separate the unprotected portion from the remainder of the floor assembly. | |
4. Wood floor assemblies using ((dimensional))dimension lumber or structural composite lumber with a cross sectional area equal to or greater than 2-inch by 10-inch nominal dimension, or other approved floor assemblies demonstrating equivalent fire performance. |
EXCEPTION: | The glazed areas need not be installed in rooms where artificial light is provided capable of producing an average illumination of 6 footcandles (65 lux) over the area of the room at a height of 30 inches (762 mm) above the floor level. |
EXCEPTION: | Openings required for light shall be permitted to open into a sunroom with thermal isolation or a patio cover, provided there is an openable area between the adjoining room and the sunroom or a patio cover of not less than one-tenth of the floor area of the interior room but not less than 20 square feet (2 m2). |
EXCEPTION: | Additions with less than 500 square feet of conditioned floor area are exempt from the requirements in this Code for Whole-House Ventilation Systems. |
EXCEPTIONS: | 1. The 10-foot (3048 mm) separation is not required where the intake opening is located 3 feet (914 mm) or greater below the contaminant source. |
2. Vents and chimneys serving fuel-burning appliances shall be terminated in accordance with the applicable provisions of Chapters 18 and 24. | |
3. Clothes dryer exhaust ducts shall be terminated in accordance with Section M1502.3. |
EXCEPTION: | A switch is not required where remote, central or automatic control of lighting is provided. |
EXCEPTIONS: | 1. Required glazed openings that face into a roofed porch where the porch abuts a street, yard or court are permitted where the longer side of the porch is not less than 65 percent unobstructed and the ceiling height is not less than 7 feet (2134 mm). |
2. Eave projections shall not be considered as obstructing the clear open space of a yard or court. | |
3. Required glazed openings that face into the area under a deck, balcony, bay or floor cantilever are permitted where an unobstructed pathway of not less than 36 inches (914 mm) in height, 36 inches (914 mm) in width, and no greater than 60 inches (1524 mm) in length is provided and opens to a yard or court. The pathway shall be measured from the exterior face of the glazed opening, or if the glazed opening is in a window well, at the window well wall furthest from the exterior face of the glazed opening. |
EXCEPTION: | Unheated recreational tents or yurts not exceeding 500 square feet provided it is not occupied as a permanent dwelling. |
EXCEPTIONS: | 1. Wood cook stoves. |
2. Antique wood heaters manufactured prior to 1940. |
EXCEPTION: | Stairways, alternating tread devices, ship's ladders, or ladders within an individual dwelling unit or sleeping unit used for access to areas of 200 square feet (18.6 m2) or less, are exempt from the requirements of Sections R311.4 and R311.7, where such devices do not provide exclusive access to a kitchen or bathroom. Such areas shall not be located more than 10 feet (3048 mm) above the finished floor of the space below. |
EXCEPTION: | Not adopted. |
EXCEPTION: | Not adopted. |
EXCEPTIONS: | 1. Guards on the open sides of stairs shall have a height of not less than 34 inches (864 mm) measured vertically from a line connecting the nosings. |
2. Where the top of the guard serves as a handrail on the open sides of stairs, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) as measured vertically from a line connecting the nosings. | |
3. In areas with ceiling heights of 7 feet (2134 mm) or less in lofts constructed in accordance with Section R333, guards shall not be less than 36 inches (914 mm) in height or one-half of the clear height from the loft floor to the loft ceiling, whichever is less. |
EXCEPTIONS: | 1. Work involving the exterior surfaces of dwellings, such as the replacement of roofing or siding, the addition or replacement of windows or doors, or the addition of a porch or deck are exempt from the requirements of this section. |
2. Installation, alteration or repairs of plumbing, electrical or mechanical systems are exempt from the requirements of this section. |
EXCEPTION: | Heat detectors and heat alarms shall not be required in dwellings without commercial power. |
EXCEPTION: | Smoke alarms and alarms installed to satisfy Section R314.4.1 shall not be required to be interconnected to existing smoke alarms where such existing smoke alarms are not interconnected or where such new smoke alarm or alarm is not capable of being interconnected to the existing smoke alarms. |
EXCEPTIONS: | 1. Smoke alarms shall be permitted to be battery operated where installed in buildings without commercial power. |
2. Smoke alarms installed in accordance with Section R314.2.2 shall be permitted to be battery powered. |
EXCEPTION: | Detached, nonhabitable Group U structures shall not be subject to the requirements of this section for structural and fire safety. |
EXCEPTION: | The roof structure shall be deemed adequate to support the load of the rooftop solar photovoltaic system if all of the following requirements are met: |
1. The solar photovoltaic panel system shall be designed for the wind speed of the local area, and shall be installed per the manufacturer's specifications. | |
2. The ground snow load does not exceed 70 pounds per square foot (3.35 kPa). | |
3. The total dead load of modules, supports, mountings, raceways, and all other appurtenances weigh no more than 4 pounds per square foot (19.5 kg/m2). | |
4. Photovoltaic modules are not mounted higher than 18 inches (457 mm) above the surface of the roofing to which they are affixed. | |
5. Supports for solar modules are to be installed to spread the dead load across as many roof-framing members as needed, so that no point load exceeds 50 pounds (22.7 kg). |
EXCEPTION: | Lofts in dwelling units and sleeping units shall be permitted to comply with Section R333, subject to the limitations in Section R333.1. |
EXCEPTION: | Swing-up grab bars shall not be required to meet the 1 1/2 inch (32 mm) spacing requirement. |
EXCEPTION: | The required vertical grab bar can be substituted with a floor to ceiling grab bar meeting the requirements of Section R325.8 at the control end and head end entry points. |
EXCEPTION: | Shower stalls with permanent built-in seats are not required to have vertical or horizontal grab bars at the seat end wall. A vertical floor to ceiling grab bar shall be installed within 4 inches of the exterior of the shower aligned with the nose of the built-in seat. |
EXCEPTIONS: | 1. Use of toilet facilities while under supervision of an adult staff person; |
2. Family home child care may be allowed on the second story if one of the following conditions exists: | |
2.1. Stairways from the second story open directly to the exterior of the building without entering the first floor; | |
2.2. One of the two required means of egress discharges directly to the exterior from the second story level, and a self-closing door is installed at the top or bottom of the interior stair leading to the floor below; or | |
2.3. A residential sprinkler system is provided throughout the entire building in accordance with NFPA 13d. |
EXCEPTION: | Sleeping or napping rooms having doors leading to two separate means of egress, or a door leading directly to the exterior of the building. |
EXCEPTION: | A ((fire-resistive))fire-resistant separation shall not be required where the food preparation kitchen contains only a domestic cooking range, and the preparation of food does not result in the production of smoke or grease laden vapors. |
EXCEPTION: | Lofts need not comply with Section R333 where they meet any of the following conditions: |
1. The loft has a maximum depth of less than 3 feet (914 mm). | |
2. The loft has a floor area of less than 35 square feet (3.3 m2). | |
3. The loft is not provided with a permanent means of egress. |
EXCEPTION: | The area of a single loft located within a dwelling unit or sleeping unit equipped with an automatic sprinkler system in accordance with Section P2904 shall not be greater than two-thirds of the area of the room in which it is located, provided that no other lofts or mezzanines are open to the room in which the loft is located. |
EXCEPTION: | Light-frame construction shall be permitted to have minimum footing size in accordance with Figures R403.1.1(1) through R403.1.1(4) in lieu of that determined by Table R403.1(1). |
![]() |
Notes: | a | The minimum footing size is based on the following assumptions: Material weights per Section R301.2.2.2.1 and soil density = 120 pcf. Wood-framed walls = 10 foot; crawlspace stem wall = 6 inches × 36 inches; basement wall = 8 inches × 120 inches. Total load (TL) equal to the maximum of three load combinations: LC1=D+L, LC2=D+S and LC3=D=0.75(L+S), where D=dead load, L=live load, S=snow load. TL=max (LC1, LC2, LC3). |
b | Use tributary span of floor and roof. Figure may be used to size exterior and interior footings. | |
c | Add 4 feet to tributary floor span for each wood-framed wall above first level (i.e., ((4'))4 feet for 2-story, ((8'))8 feet for 3-story). | |
d | Multiply floor span by 1.25 for interior footings supporting continuous joists. | |
e | Multiply footing width by (1500 psf/capacity) for soil capacity other than 1500 psf. See Section R403.1.1 for thickness. | |
f | Dashed line may be used for interior footing size only. | |
g | Use footing size indicated on line above the span combination used. | |
h | For span combinations above the upper line, a design professional is required. | |
i | Interpolation between footing sizes is allowed. Extrapolation is not allowed. |
![]() |
Notes: | a | The minimum footing size is based on the following assumptions: Material weights per Section R301.2.2.2.1 and soil density = 120 pcf. Wood-framed walls = 10 foot; crawlspace stem wall = 6 inches × 36 inches; basement wall = 8 inches × 120 inches. Total load (TL) equal to the maximum of three load combinations: LC1=D+L, LC2=D+S and LC3=D=0.75(L+S), where D=dead load, L=live load, S=snow load. TL=max (LC1, LC2, LC3). |
b | Use tributary span of floor and roof. Figure may be used to size exterior and interior footings. | |
c | Add 4 feet to tributary floor span for each wood-framed wall above first level (i.e., ((4'))4 feet for 2-story, ((8'))8 feet for 3-story). | |
d | Multiply floor span by 1.25 for interior footings supporting continuous joists. | |
e | Multiply footing width by (1500 psf/capacity) for soil capacity other than 1500 psf. See Section R403.1.1 for thickness. | |
f | Dashed line may be used for interior footing size only. | |
g | Use footing size indicated on line above the span combination used. | |
h | For span combinations above the upper line, a design professional is required. | |
i | Interpolation between footing sizes is allowed. Extrapolation is not allowed. |
![]() |
Notes: | a | The minimum footing size is based on the following assumptions: Material weights per Section R301.2.2.2.1 and soil density = 120 pcf. Wood-framed walls = 10 foot; crawlspace stem wall = 6 inches × 36 inches; basement wall = 8 inches × 120 inches. Total load (TL) equal to the maximum of three load combinations: LC1=D+L, LC2=D+S and LC3=D=0.75(L+S), where D=dead load, L=live load, S=snow load. TL=max (LC1, LC2, LC3). |
b | Use tributary span of floor and roof. Figure may be used to size exterior and interior footings. | |
c | Add 4 feet to tributary floor span for each wood-framed wall above first level (i.e., ((4'))4 feet for 2-story, ((8'))8 feet for 3-story). | |
d | Multiply floor span by 1.25 for interior footings supporting continuous joists. | |
e | Multiply footing width by (1500 psf/capacity) for soil capacity other than 1500 psf. See Section R403.1.1 for thickness. | |
f | Dashed line may be used for interior footing size only. | |
g | Use footing size indicated on line above the span combination used. | |
h | For span combinations above the upper line, a design professional is required. | |
i | Interpolation between footing sizes is allowed. Extrapolation is not allowed. |
![]() |
Notes: | a | The minimum footing size is based on the following assumptions: Material weights per Section R301.2.2.2.1 and soil density = 120 pcf. Wood-framed walls = 10 foot; crawlspace stem wall = 6 inches × 36 inches; basement wall = 8 inches × 120 inches. Total load (TL) equal to the maximum of three load combinations: LC1=D+L, LC2=D+S and LC3=D=0.75(L+S), where D=dead load, L=live load, S=snow load. TL=max (LC1, LC2, LC3). |
b | Use tributary span of floor and roof. Figure may be used to size exterior and interior footings. | |
c | Add 4 feet to tributary floor span for each wood-framed wall above first level (i.e., ((4'))4 feet for 2-story, ((8'))8 feet for 3-story). | |
d | Multiply floor span by 1.25 for interior footings supporting continuous joists. | |
e | Multiply footing width by (1500 psf/capacity) for soil capacity other than 1500 psf. See Section R403.1.1 for thickness. | |
f | Dashed line may be used for interior footing size only. | |
g | Use footing size indicated on line above the span combination used. | |
h | For span combinations above the upper line, a design professional is required. | |
i | Interpolation between footing sizes is allowed. Extrapolation is not allowed. |
EXCEPTION: | The ground cover may be omitted in crawl spaces if the crawl space has a concrete slab floor with a minimum thickness of ((two))2 inches (51 mm). |
EXCEPTION: | The total area of ventilation openings shall be permitted to be reduced to 1/1,500 of the under-floor area where the ground surface is covered with an approved Class I vapor retarder material and the required openings are placed to provide cross ventilation of the space. The installation of operable louvers shall not be prohibited. If the installed ventilation is less than 1/300, or if operable louvers are installed, a radon vent shall be installed to originate from a point between the ground cover and soil. The radon vent shall be installed in accordance with the requirements of Appendix F (Radon) of this code. |
EXCEPTION: | Plenum in existing structures complying with Section M1601.5, if under-floor space is used as a plenum. |
LIVE OR GROUND SNOW LOAD (psf) | TRIBUTARY AREA((c)) (sq.ft.) | LOAD-BEARING VALUE OF SOILSacd(psf) | ||||||||
1500e((psf)) | 2000e((psf)) | ≥ 3000e((psf)) | ||||||||
Side of a square footing (inches) | Diameter of a round footing (inches) | Thicknessf (inches) | Side of a square footing (inches) | Diameter of a round footing (inches) | Thicknessf (inches) | Side of a square footing (inches) | Diameter of a round footing (inches) | Thicknessf (inches) | ||
60 Live or 70 Ground Snow Load | 5 | 7 | 8 | 6 | 7 | 8 | 6 | 7 | 8 | 6 |
20 | 12 | 14 | 6 | 11 | 13 | 6 | 9 | 10 | 6 | |
40 | 18 | 20 | 6 | 15 | 17 | 6 | 12 | 14 | 6 | |
60 | 21 | 24 | 8 | 19 | 21 | 6 | 15 | 17 | 6 | |
80 | 25 | 28 | 9 | 21 | 24 | 8 | 18 | 20 | 6 | |
100 | 28 | 31 | 11 | 24 | 27 | 9 | 20 | 22 | 7 | |
120 | 30 | 34 | 12 | 26 | 30 | 10 | 21 | 24 | 8 | |
140 | 33 | 37 | 13 | 28 | 32 | 11 | 23 | 26 | 9 | |
160 | 35 | 40 | 15 | 30 | 34 | 12 | 25 | 28 | 9 |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa. | |
a. | Interpolation permitted, extrapolation not permitted. |
b. | Reserved. |
c. | Footing dimensions shall allow complete bearing of the post. |
d. | If the support is a brick or CMU pier, the footing shall have a minimum 2-inch projection on all sides. |
e. | Area, in square feet, of deck surface supported by post and footings. |
f. | Minimum thickness shall only apply to plain concrete footings, |
((LOADSb (psf) | POST SPECIESc | POST SIZEd | MAXIMUM DECK POST HEIGHTa (feet-inches) | |||||||
Tributary Areag,h (sq. ft.) | ||||||||||
20 | 40 | 60 | 80 | 100 | 120 | 140 | 160)) | |||
TRIBUTARY AREAg,h (sq. ft.) | ||||||||||
20 | 40 | 60 | 80 | 100 | 120 | 140 | 160 | |||
LOADSb (psf) | POST SPECIESc | POST SIZEd | MAXIMUM DECK POST HEIGHTa (feet-inches) | |||||||
60 Live Load, ≤60 Ground Snow Load | Douglas Fire, Hem-fire, SPFe | 4 x 4 | 14-0 | 10-10 | 8-7 | 7-0 | 5-8 | 4-1 | NP | NP |
4 x 6 | 14-0 | 13-10 | 11-1 | 9-5 | 8-2 | 7-3 | 6-4 | 5-4 | ||
6 x 6 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 13-3 | 10-9 | 6-11 | ||
8 x 8 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | ||
Redwoodf, Western Cedarsf, Ponderosa Pinef, Red Pinef | 4 x 4 | 14-0 | 10-3 | 7-0 | NP | NP | NP | NP | NP | |
4 x 6 | 14-0 | 13-6 | 10-6 | 8-4 | 5-10 | NP | NP | NP | ||
6 x 6 | 14-0 | 14-0 | 14-0 | 14-0 | 11-11 | NP | NP | NP | ||
8 x 8 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | ||
70 Ground Snow Load | Douglas Fire, Hem-fire, SPFe | 4 x 4 | 14-0 | 10-1 | 7-11 | 6-6 | 5-3 | 3-7 | NP | NP |
4 x 6 | 14-0 | 12-10 | 10-3 | 8-9 | 7-7 | 6-8 | 5-10 | 4-11 | ||
6 x 6 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 12-2 | 9-9 | 5-9 | ||
8 x 8 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | ||
Redwoodf, Western Cedarsf, Ponderosa Pinef, Red Pinef | 4 x 4 | 14-0 | 9-5 | 6-5 | NP | NP | NP | NP | NP | |
4 x 6 | 14-0 | 12-6 | 9-8 | 7-7 | 5-3 | NP | NP | NP | ||
6 x 6 | 14-0 | 14-0 | 14-0 | 14-0 | 10-8 | NP | NP | NP | ||
8 x 8 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 | 14-0 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa, NP = Not permitted. | |
a. | Measured from the underside of the beam to top of footing or pier. |
b. | 10 psf dead load. Snow load not assumed to be concurrent with live load. |
c. | No. 2 grade, wet service factor included. |
d. | Notched deck posts shall be sized to accommodate beam size ((per)) in accordance with Section R507.5.2. |
e. | Includes incising factor. |
f. | Incising factor not included. |
g. | Area, in square feet, of deck surface supported by post and footing. |
h. | Interpolation permitted. Extrapolation not permitted. |
BEAM SPECIESd | BEAM SIZEe | EFFECTIVE DECK JOIST SPAN LENGTHa,i (feet) | |||||||
6 | 8 | 10 | 12 | 14 | 16 | 18 | |||
MAXIMUM DECK BEAM SPAN LENGTHa,b,f (feet-inches) | |||||||||
Douglas fir-larchg, Hem-firg, Spruce-pine-firg | 1-2×6 | 3-5 | 2-10 | 2-5 | 2-2 | 2-0 | 1-10 | 1-9 | |
1-2×8 | 4-7 | 3-8 | 3-2 | 2-10 | 2-7 | 2-5 | 2-4 | ||
1-2×10 | 5-8 | 4-9 | 4-1 | 3-8 | 3-4 | 3-1 | 2-11 | ||
1-2×12 | 6-7 | 5-8 | 5-0 | 4-6 | 4-1 | 3-10 | 3-7 | ||
2-2×6 | 5-2 | 4-6 | 4-0 | 3-5 | 3-1 | 2-10 | 2-7 | ||
2-2×8 | 6-11 | 6-0 | 5-3 | 4-7 | 4-1 | 3-8 | 3-5 | ||
2-2×10 | 8-5 | 7-4 | 6-6 | 5-10 | 5-2 | 4-9 | 4-5 | ||
2-2×12 | 9-10 | 8-6 | 7-7 | 6-11 | 6-4 | 5-9 | 5-4 | ||
3-2×6 | 6-6 | 5-7 | 5-0 | 4-7 | 4-2 | 3-9 | 3-5 | ||
3-2×8 | 8-8 | 7-6 | 6-8 | 6-1 | 5-6 | 5-0 | 4-7 | ||
3-2×10 | 10-7 | 9-2 | 8-2 | 7-6 | 6-11 | 6-4 | 5-10 | ||
3-2×12 | 12-4 | 10-8 | 9-7 | 8-9 | 8-1 | 7-7 | 7-1 | ||
Redwoodh, Western Cedarsh, Ponderosa Pineh, Red Pineh | 1-2×6 | 3-6 | 2-11 | 2-6 | 2-3 | 2-0 | 1-11 | 1-9 | |
1-2×8 | 4-6 | 3-10 | 3-3 | 2-11 | 2-8 | 2-6 | 2-4 | ||
1-2×10 | 5-6 | 4-9 | 4-2 | 3-9 | 3-5 | 3-2 | 3-0 | ||
1-2×12 | 6-4 | 5-6 | 4-11 | 4-6 | 4-2 | 3-11 | 3-8 | ||
2-2×6 | 5-3 | 4-7 | 4-1 | 3-6 | 3-2 | 2-11 | 2-8 | ||
2-2×8 | 6-8 | 5-9 | 5-2 | 4-8 | 4-2 | 3-10 | 3-6 | ||
2-2×10 | 8-2 | 7-1 | 6-4 | 5-9 | 5-4 | 4-10 | 4-6 | ||
2-2×12 | 9-5 | 8-2 | 7-4 | 6-8 | 6-2 | 5-9 | 5-5 | ||
3-2×6 | 6-4 | 5-8 | 5-1 | 4-8 | 4-3 | 3-10 | 3-6 | ||
3-2×8 | 8-4 | 7-3 | 6-5 | 5-11 | 5-5 | 5-1 | 4-8 | ||
3-2×10 | 10-2 | 8-10 | 7-11 | 7-2 | 6-8 | 6-3 | 5-11 | ||
3-2×12 | 11-10 | 10-3 | 9-2 | 8-4 | 7-9 | 7-3 | 6-10 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound = 0.454 kg. | |
a. | Interpolation allowed. Extrapolation is not allowed. |
b. | Beams supporting a single span of joists with or without cantilever. |
c. | Dead load = 10 psf, L/Δ = 360 at mainspan, L/Δ = 180 at cantilever. Snow load not assumed to be concurrent with live load. |
d. | No. 2 grade, wet service factor included. |
e. | Beam depth shall be equal to or greater than the depth of intersecting joist for a flush beam connection. |
f. | Beam cantilevers are limited to the adjacent beam's span divided by 4. |
g. | Includes incising factor. |
h. | Incising factor not included. |
i. | Deck joist span as shown in Figure R507.5. |
j. | For calculation of effective joist span, the actual joist span length shall be multiplied by the joist span factor in accordance with Table R507.5(5). |
LOADa (psf) | JOIST SPECIESb | JOIST SIZE | ALLOWABLE JOIST SPANb,c (feet-inches) | MAXIMUM CANTILEVERd,f((,g)) (feet-inches) | |||||||||
Joist Spacing (inches) | Adjacent Joist Back Spang (feet) | ||||||||||||
12 | 16 | 24 | 4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |||
60 Live Load or 70 Ground Snow Load | Douglas fir-larche, Hem-fire, Spruce-pine-fire | 2×6 | 7-11 | 7-1 | 5-9 | 1-0 | 1-6 | NP | NP | NP | NP | NP | NP |
2×8 | 10-5 | 9-5 | 7-8 | 1-0 | 1-6 | 2-0 | 2-1 | NP | NP | NP | NP | ||
2×10 | 13-3 | 11-6 | 9-5 | 1-0 | 1-6 | 2-0 | 2-6 | 2-8 | NP | NP | NP | ||
2×12 | 15-5 | 13-4 | 10-11 | 1-0 | 1-6 | 2-0 | 2-6 | 3-0 | 3-3 | NP | NP | ||
Redwoodf, Western Cedarsf, Ponderosa Pinef, Red Pinef | 2×6 | 7-4 | 6-8 | 5-10 | 1-0 | 1-4 | NP | NP | NP | NP | NP | NP | |
2×8 | 9-8 | 8-10 | 7-4 | 1-0 | 1-6 | 1-11 | NP | NP | NP | NP | NP | ||
2×10 | 12-4 | 11-0 | 9-0 | 1-0 | 1-6 | 2-0 | 2-6 | 2-6 | NP | NP | NP | ||
2×12 | 14-9 | 12-9 | 10-5 | 1-0 | 1-6 | 2-0 | 2-6 | 3-0 | 3-0 | NP | NP |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound = 0.454 kg, NP = Not permitted. | |
a. | Dead load = 10 psf dead load. Snow load not assumed to be concurrent with live load. |
b. | No. 2 grade, wet service factor included. |
c. | L/Δ = 360 at main span. |
d. | L/Δ = 180 at cantilever with 220-pound point load applied to end. |
e. | Includes incising factor. |
f. | Incising factor not included. |
g. | Interpolation permitted. Extrapolation not permitted. |
LOADc (psf) | JOIST SPANa (feet) | ON-CENTER SPACING OF FASTENERSb (inches) | |||
1/2-inch diameter lag screw with 1/2-inch maximum sheathingd,e | 1/2-inch diameter bolt with 1/2-inch maximum sheathinge | 1/2-inch diameter bolt with 1-inch maximum sheathingf | |||
60 Live Load or 70 Ground Snow Load | 6 | 22 | 36 | 35 | |
8 | 16 | 31 | 26 | ||
10 | 13 | 25 | 21 | ||
12 | 11 | 20 | 17 | ||
14 | 9 | 17 | 15 | ||
16 | 8 | 15 | 13 | ||
18 | 7 | 13 | 11 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. | |
a. | Interpolation permitted. Extrapolation is not permitted. |
b. | Ledgers shall be flashed in accordance with Section R703.4 to prevent water from contacting the house band joist. |
c. | Dead load = 10 psf. Snow load shall not be assumed to act concurrently with live load. |
d. | The tip of the lag screw shall fully extend beyond the inside face of the band joist. |
e. | Sheathing shall be wood structural panel or solid sawn lumber. |
f. | Sheathing shall be permitted to be wood structural panel, gypsum board, fiberboard, lumber or foam sheathing. Up to 1/2-inch thickness of stacked washers shall be permitted to substitute for up to 1/2 inch of allowable sheathing thickness where combined with wood structural panel or lumber sheathing. |
EXCEPTION: | Decks not more than 30 inches above grade at any point may be unattached. |
MINIMUM END AND EDGE DISTANCES AND SPACING BETWEEN ROWS | ||||
TOP EDGE | BOTTOM EDGE | ENDS | ROW SPACING | |
Ledgera | 2 inchesd | 3/4 inch | 2 inchesb | 1 5/8 inchesb |
Band joistc | 3/4 inch | 2 inchese | 2 inchesb | 1 5/8 inchesb |
For SI: | 1 inch = 25.4 mm. |
a | Lag screws or bolts shall be staggered from the top to the bottom along the horizontal run of the deck ledger in accordance with Figure ((R507.2.1(1)))R507.9.1.3(1). |
b | Maximum 5 inches. |
c | For engineered rim joists, the manufacturer's recommendations shall govern. |
d | The minimum distance from bottom row of lag screws or bolts to the top edge of the ledger shall be in accordance with Figure ((R507.2.1(1)))R507.9.1.3(1). |
e | The 2 inches may be reduced to 3/4 inch when the band joist is directly supported by a mudsill, a header or by double top wall plates. |
LOADc (psf) | JOIST SPANa (feet) | 1/2-inch diameter leg screw with 1/2-inch maximum sheathingd,e | 1/2-inch diameter bolt with 1/2-inch maximum sheathinge | 1/2-inch diameter bolt with 1-inch maximum sheathingf |
ON-CENTER SPACING OF FASTENERSb (inches) | ||||
60 Ground Snow Load | 6 | 25 | 36 | 36 |
8 | 18 | 35 | 30 | |
10 | 15 | 28 | 24 | |
12 | 12 | 23 | 20 | |
14 | 10 | 20 | 17 | |
16 | 9 | 17 | 15 | |
18 | 8 | 15 | 13 | |
70 Ground Snow Load | 6 | 22 | 36 | 35 |
8 | 16 | 31 | 26 | |
10 | 13 | 25 | 21 | |
12 | 11 | 20 | 17 | |
14 | 9 | 17 | 15 | |
16 | 8 | 15 | 13 | |
18 | 7 | 13 | 11 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. | |
a. | Interpolation permitted. Extrapolation not permitted. |
b. | Legers shall be flashed in accordance with Section R703.4 to prevent water from contacting the house band joist. |
c. | Dead Load = 10 psf. Snow load shall not be assumed to act concurrently with live load. |
d. | The tip of the lag screw shall fully extend beyond the inside face of the band joist. |
e. | Sheathing shall be wood structural panel or solid sawn lumber. |
f. | Sheathing shall be permitted to be wood structural panel, gypsum board, fiberboard, lumber or foam sheathing. Up to 1/2 inch thickness of stacked washers shall be permitted to substitute for up to 1/2 inch of allowable sheathing thickness where combined with wood structural panel or lumber sheathing.)) |
EXCEPTION: | Fireplaces with gas logs shall be installed in accordance with the International Mechanical Code Section 901, except that the standards for liquefied petroleum gas installations shall be NFPA 58 (Liquefied Petroleum Gas Code) and NFPA 54 (National Fuel Gas Code). |
EXCEPTION: | Combustion air may be supplied to the room in which the solid fuel burning appliance is located in lieu of direct ducting, provided that one of the following conditions is met: |
1. The solid fuel-burning appliance is part of a central heating plant and installed in an unconditioned space in conformance with the International Mechanical Code; or | |
2. The solid fuel-burning appliance is installed in existing construction directly on a concrete floor or surrounded by masonry materials as in a fireplace. The combustion air terminus shall be located as close to the solid fuel-burning appliance as possible and shall be provided with a barometric damper or equivalent. The combustion air source shall be specified by the manufacturer or no less than 4 inches (102 mm) in diameter or the equivalent in area or as approved. |
EXCEPTION: | The standards for liquefied petroleum gas installations shall be the 2011 Edition of NFPA 58 (Liquefied Petroleum Gas Code) and the 2012 Edition of ANSI Z223.1/NFPA 54 (National Fuel Gas Code). |
EXCEPTION: | Alternate balanced whole-house ventilation systems and local exhaust systems designed and commissioned in accordance with ASHRAE 62.2 are permitted. |
EXCEPTION: | HVAC air handlers, ERV/HRV units, and remote mounted fans need not meet the sound requirements. To be considered for this exception, a remote mounted fan must be mounted outside the habitable spaces, bathrooms, toilets, and hallways, and there must be at least 4 ((ft))feet (1.3 m) of ductwork between the fan and the intake grille. |
EXCEPTION: | Interior joining spaces provided with a 30 cfm whole-house transfer fan or a permanent opening with an area of not less than 8 percent of the floor area of the interior adjoining space but not less than 25 square feet do not require ducted outdoor ventilation air to be supplied directly to the space. Whole-house transfer fans shall meet the sone rating of Section M1505.4.1.1 and shall have whole-house ventilation controls that comply with Section M1505.4.2. |
EXCEPTION: | Air handler fans shall have multispeed or variable speed supply airflow control capability with a low speed operation not greater than 25 percent of the rated supply airflow capacity during ventilation only operation. Outdoor air intake openings must meet the provisions of Sections R303.5 and R303.6 and must include a motorized damper that is activated by the whole-house ventilation system controller. The motorized damper must be controlled to maintain the outdoor airflow intake airflow within 10 percent of the whole-house mechanical exhaust airflow rate. The flow rate for the outdoor air intake must be tested and verified at the minimum ventilation fan speed and the maximum heating or cooling fan speed. The results of the test shall be submitted and posted in accordance with Section M1505.4.1.7. |
Number of Bedrooms | |||||
Dwelling Unit Floor Area (square feet) | 0 - 1 | 2 | 3 | 4 | 5 or more |
Airflow in cfm | |||||
< 500 | 30 | 30 | 35 | 45 | 50 |
501 - 1,000 | 30 | 35 | 40 | 50 | 55 |
1,001 - 1,500 | 30 | 40 | 45 | 55 | 60 |
1,501 - 2,000 | 35 | 45 | 50 | 60 | 65 |
2,001 - 2,500 | 40 | 50 | 55 | 65 | 70 |
2,501 - 3,000 | 45 | 55 | 60 | 70 | 75 |
3,001 - 3,500 | 50 | 60 | 65 | 75 | 80 |
3,501 - 4,000 | 55 | 65 | 70 | 80 | 85 |
4,001 - 4,500 | 60 | 70 | 75 | 85 | 90 |
4,501 - 5,000 | 65 | 75 | 80 | 90 | 95 |
Where: | ||
Qv | = | Quality-adjusted ventilation airflow rate in cubic feet per minute (cfm). |
Qr | = | Ventilation airflow rate, cubic feet per minute (cfm) from Equation 15-1 or Table M1505.4.3(1). |
Csystem | = | System coefficient from Table 1505.4.3(2). |
System Type | Distributed | Not Distributed |
Balanced | 1.0 | 1.25 |
Not balanced | 1.25 | 1.5 |
Run-time % in Each 4-hour Segment | 50% | 66% | 75% | 100% |
Factora | 2 | 1.5 | 1.3 | 1.0 |
Area to Be Exhausted | Exhaust Rates | |
Intermittent | Continuous | |
Open Kitchens | In accordance with Section M1505.4.4.3 | Not Permitted |
Enclosed Kitchens | In accordance with Section M1505.4.4.3 | 5 ACH based on kitchen volume |
Bathrooms - Toilet rooms | 50 cfm | 20 cfm |
EXCEPTIONS: | 1. The installed airflow is not required to be field-verified where an exhaust airflow rating at a pressure of 0.25 in. w.g. is used, provided the duct sizing meets the prescriptive requirements of Table M1505.4.4.2. |
2. Remote mounted fans need not meet sound requirements. To be considered for this exception, a remote mounted fan shall be mounted outside the kitchen, and there shall be at least 4 feet (1 m) of ductwork between the fan and the intake grille. |
Fan Tested cfm at 0.25 inches w.g. | Minimum Flex Diameter | Maximum Length in Feet | Minimum Smooth Diameter | Maximum Length in Feet | Maximum Elbowsa |
50 | 4 inches | 25 | 4 inches | 70 | 3 |
50 | 5 inches | 90 | 5 inches | 100 | 3 |
50 | 6 inches | No Limit | 6 inches | No Limit | 3 |
80 | 4 inchesb | NA | 4 inches | 20 | 3 |
80 | 5 inches | 15 | 5 inches | 100 | 3 |
80 | 6 inches | 90 | 6 inches | No Limit | 3 |
100 | 5 inchesb | NA | 5 inches | 50 | 3 |
100 | 6 inches | 45 | 6 inches | No Limit | 3 |
125 | 6 inches | 15 | 6 inches | No Limit | 3 |
125 | 7 inches | 70 | 7 inches | No Limit | 3 |
EXCEPTION: | Other intermittent kitchen exhaust fans, including downdraft, shall meet or exceed 300 cfm airflow. |
Hood Over Electric Range | Hood Over Combustion Range |
60% CE or 160 cfm | 80% CE or 250 cfm |
EXCEPTION: | The installed airflow is not required to be field-verified where an exhaust airflow rating at a pressure of 0.25 in. w.g. is used, provided the duct sizing meets the prescriptive requirements of Table M1505.4.4.2. |
EXCEPTIONS: | 1. Uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the remainder of the space. |
2. Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m2) in area, with the smallest dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board. | |
3. Bathrooms not more than 55 square feet (5.1 m2) in area. | |
4. Garages; carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas. |
EXCEPTION: | Where only the window glazing is being replaced. |
EXCEPTION: | Ceiling heights in ((sleeping)) lofts shall be in accordance with Section ((R326))R333. |
EXCEPTIONS: | 1. Uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the remainder of the space. |
2. Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m2) in area, with the smallest dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board. | |
3. Bathrooms not more than 55 square feet (5.1 m2) in area. | |
4. Garages; carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas. |
EXCEPTION: | Projects determined to be unsafe. |
EXCEPTION: | Projects that include only new construction. |
EXCEPTIONS: | 1. The structure is determined to be unsafe by the engineer of record; |
2. The structure shall be relocated; | |
3. The engineer of ((recordbuilding official))record determines that 50 percent, by weight, of the material in the structure that is not concrete, is not suitable for reuse. |