EXCEPTIONS: | 1. Chilled-water cooling coils that have an airside pressure drop exceeding 0.70 in. of water when rated at 500 fpm face velocity and dry conditions (no condensation). |
2. Individual fan-cooling units with a design supply airflow rate ≤ 5000 cfm. | |
3. Constant-air-volume systems. | |
4. Coils selected at the maximum temperature difference allowed by the cooling plant equipment manufacturer's approved operating conditions. | |
5. Passive coils (no mechanically supplied airflow). | |
6. Coils with design entering chilled-water temperature ≥ 50°F (10°C). | |
7. Coils with design entering air dry-bulb temperature ≤ 65°F (18°C). |
EXCEPTIONS: | 1. Hot-water heating systems which utilize heat pumps as the primary source. |
2. Individual terminal fan units with a design supply airflow rate ≤ 1500 cfm are exempt from the 20°F maximum temperature difference between leaving and entering water temperature requirement. | |
3. Passive coils (no mechanically supplied airflow). | |
4. Coils with design leaving air temperature ≥ 95°F (35°C). |