EXCEPTION: | An energy recovery ventilation system shall not be required in any of the following conditions: |
1. Where energy recovery systems are restricted per Section 514 of the International Mechanical Code to sensible energy, recovery shall comply with one of the following: | |
1.1. Kitchen exhaust systems where they comply with Section C403.7.7.1. | |
1.2. Laboratory fume hood systems where they comply with Exception 2 of Section C403.7.6. | |
1.3. Other sensible energy recovery systems with the capability to provide a change in dry-bulb temperature of the outdoor air supply of not less than 50 percent of the difference between the outdoor air and the return air dry-bulb temperatures, at design conditions. | |
2. Laboratory fume hood systems that include at least one of the following features and also comply with Section C403.7.7.2: | |
2.1. Variable-air-volume hood exhaust and room supply systems configured to reduce exhaust and makeup air volume to 50 percent or less of design values. | |
2.2. Direct makeup (auxiliary) air supply equal to at least 75 percent of the exhaust rate, heated no warmer than 2°F (1.1°C) above room setpoint, cooled to no cooler than 3°F (1.7°C) below room setpoint, no humidification added, and no simultaneous heating and cooling used for dehumidification control. | |
3. Systems serving spaces that are heated to less than 60°F (15.5°C) and are not cooled. | |
4. Where more than 60 percent of the outdoor air heating energy is provided from site-recovered energy. | |
5. Systems exhausting toxic, flammable, paint or corrosive fumes or dust. | |
6. Cooling energy recovery. | |
7. Systems requiring dehumidification that employ energy recovery in series with the cooling coil. | |
8. Multiple-zone systems where the supply airflow rate is less than the values specified in Tables C403.7.6 (1) and (2), for the corresponding percent of outdoor air. Where a value of NR is listed, energy recovery shall not be required. | |
9. Equipment which meets the requirements of Section C403.9.2.4. | |
10. Systems serving Group R-1 dwelling or sleeping units where the largest source of air exhausted at a single location at the building exterior is less than 25 percent of the design outdoor air flow rate. |
Percent (%) Outdoor Air at Full Design Airflow Rate | ||||||||
Climate zone | ≥ 10% and < 20% | ≥ 20% and < 30% | ≥ 30% and < 40% | ≥ 40% and < 50% | ≥ 50% and < 60% | ≥ 60% and < 70% | ≥ 70% and < 80% | ≥ 80% |
Design Supply Fan Airflow Rate (cfm) | ||||||||
4C, 5B | NR | NR | NR | NR | NR | NR | ≥ 5000 | ≥ 5000 |
NR = Not required. |
Percent (%) Outdoor Air at Full Design Airflow Rate | ||||||||
Climate zone | ≥ 10% and < 20% | ≥ 20% and < 30% | ≥ 30% and < 40% | ≥ 40% and < 50% | ≥ 50% and < 60% | ≥ 60% and < 70% | ≥ 70% and < 80% | ≥ 80% |
Design Supply Fan Airflow Rate (cfm) | ||||||||
4C | NR | ≥ 19500 | ≥ 9000 | ≥ 5000 | ≥ 4000 | ≥ 3000 | ≥ 1500 | ≥ 120 |
5B | ≥ 2500 | ≥ 2000 | ≥ 1000 | ≥ 500 | ≥ 140 | ≥ 120 | ≥ 100 | ≥ 80 |
NR = Not required. |