Building Specific Space-by-Space Typesa | LPD (w/ft2) | |
Automotive (see vehicular maintenance) | ||
Convention center - Exhibit spacei | 0.61 | |
Dormitory living quartersa,b | 0.50 | |
Facility for the visually impairedb | ||
In a chapel (and not used primarily by the staff)b | 0.70 | |
In a recreation room (and not used primarily by the staff)b | 1.77 | |
Fire stations | ||
Sleeping quarters | 0.23 | |
Gymnasium/fitness center | ||
In an exercise area | 0.90 | |
In a playing area | 0.85 | |
Health care facilityc,i | ||
In an exam/treatment room | 1.40 | |
In an imaging room | 0.94 | |
In a medical supply room | 0.62 | |
In a nursery | 0.92 | |
In a nurse's station | 1.17 | |
In an operating room | 2.26 | |
In a patient room | 0.68 | |
In a physical therapy room | 0.91 | |
In a recovery room | 1.25 | |
Library | ||
In a reading areai | 0.96 | |
In the stacks | 1.10 | |
Manufacturing facility | ||
In a detailed manufacturing area | 0.80 | |
In an equipment room | 0.76 | |
In an extra high bay area (greater than 50-foot floor-to-ceiling height) | 1.42 | |
In a high bay area (25 - 50-foot floor-to-ceiling height) | 1.24 | |
In a low bay (< 25-foot floor-to-ceiling height) | 0.86 | |
Museum | ||
In a general exhibition areai | 0.31 | |
In a restoration room | 1.10 | |
Performing arts theater dressing/fitting room | 0.41 | |
Post office - Sorting area | 0.76 | |
Religious buildings | ||
In a fellowship halli | 0.54 | |
In a worship/pulpit/choir areai | 0.85 | |
Retail facilities | ||
In a dressing/fitting room | 0.51 | |
In a mall concourse | 0.82 | |
Sports arena - Playing area | ||
For a Class 1 facilityd | 2.94 | |
For a Class 2 facilitye | 2.01 | |
For a Class 3 facilityf | 1.30 | |
For a Class 4 facilityg | 0.86 | |
Transportation | ||
In a baggage/carousel area | 0.39 | |
In an airport concourse | 0.25 | |
At a terminal ticket counteri | 0.51 | |
Warehouse - Storage area | ||
For medium to bulky palletized items | 0.33 | |
For smaller, hand-carried items | 0.69 |
For SI: 1 foot = 304.8 mm, 1 watt per square foot = 10.76 W/m2. | |
a | In cases where both a common space type and a building area specific space type are listed, the building area specific space type shall apply. |
b | A facility for the visually impaired is a facility that is licensed or will be licensed by local or state authorities for senior long-term care, adult daycare, senior support or people with special visual needs. |
c | Additional lighting power allowance of 0.2 watts per square foot for the purpose of highlighting art or exhibits. This additional power allowance shall be permitted only where the specified lighting is installed in addition to and controlled separately from general lighting in accordance with Section C405.2.6. This additional power allowance shall be used only for the specified luminaires and shall not be used for any other purpose and it shall not be added to any other space or the interior power allowance. |
d | Class I facilities consist of professional facilities; and semiprofessional, collegiate or club facilities with seating for 5,000 or more spectators. |
e | Class II facilities consist of collegiate and semiprofessional facilities with seating for fewer than 5,000 spectators; club facilities with seating between 2,000 and 5,000 spectators; and amateur league and high school facilities with seating for more than 2,000 spectators. |
f | Class III facilities consist of club, amateur league and high school facilities with seating for 2,000 or fewer spectators. |
g | Class IV facilities consist of elementary school and recreational facilities; and amateur league and high school facilities without provisions for spectators. |
h | For classrooms, additional lighting power allowance of 4.50 W/lineal foot of white or chalk boards for directional lighting dedicated to white or chalk boards. |
i | Additional lighting power allowance of 0.15 W/ft2 for ornamental lighting. Qualifying ornamental lighting includes luminaires that are specifically used in a decorative manner. This additional power shall be permitted only where the specified lighting is installed in addition to and controlled separately from display or general lighting in accordance with Section C405.2.6. This additional power shall be used only for the specified luminaires and it shall not be added to any other space or the interior power allowance. |
j | Where a space is designated as unfinished, neither the area nor the lighting power in the space shall be calculated as part of the LPA. |