a | See Section R401.1 and residential building in Section R202 for Group R-2 scope. |
b | The gas back-up furnace will operate as fan-only when the heat pump is operating. The heat pump shall operate at all temperatures above 38°F (3.3°C) (or lower). Below that "changeover" temperature, the heat pump would not operate to provide space heating. The gas furnace provides heating below 38°F (3.3°C) (or lower). |
c | Additional points for this HVAC system are included in Table R406.3. |