For SI: 1 foot = 304.8 mm. | ||
UL = Unlimited; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3. | ||
a | See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter. | |
b | See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies. | |
c | New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5. | |
d | The NS value is only for use in evaluation of existing building height in accordance with the International Existing Building Code. | |
e | New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies Condition 1, see Exception 1 of Section 903.2.6. | |
f | New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International Fire Code. | |
g | For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6. | |
h | New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8. | |
i |
Occupancy Classification | Type of Construction | ||||||||||||
See Footnotes | Type I | Type II | Type III | Type IV | Type V | ||||||||
A | B | A | B | A | B | A | B | C | HT | A | B | ||
A-1 | NS | UL | 5 | 3 | 2 | 3 | 2 | 3 | 3 | 3 | 3 | 2 | 1 |
S | UL | 6 | 4 | 3 | 4 | 3 | 9 | 6 | 4 | 4 | 3 | 2 | |
A-2 | NS | UL | 11 | 3 | 2 | 3 | 2 | 3 | 3 | 3 | 3 | 2 | 1 |
S | UL | 12 | 4 | 3 | 4 | 3 | 18 | 12 | 6 | 4 | 3 | 2 | |
A-3 | NS | UL | 11 | 3 | 2 | 3 | 2 | 3 | 3 | 3 | 3 | 2 | 1 |
S | UL | 12 | 4 | 3 | 4 | 3 | 18 | 12 | 6 | 4 | 3 | 2 | |
A-4 | NS | UL | 11 | 3 | 2 | 3 | 2 | 3 | 3 | 3 | 3 | 2 | 1 |
S | UL | 12 | 4 | 3 | 4 | 3 | 18 | 12 | 6 | 4 | 3 | 2 | |
A-5 | NS | UL | UL | UL | UL | UL | UL | 1 | 1 | 1 | UL | UL | UL |
S | UL | UL | UL | UL | UL | UL | UL | UL | UL | UL | UL | UL | |
B | NS | UL | 11 | 5 | 3 | 5 | 3 | 5 | 5 | 5 | 5 | 3 | 2 |
S | UL | 12 | 6 | 4 | 6 | 4 | 18 | 12 | 9 | 6 | 4 | 3 | |
E | NS | UL | 5 | 3 | 2 | 3 | 2 | 3 | 3 | 3 | 3 | 1 | 1 |
S | UL | 6 | 4 | 3 | 4 | 3 | 9 | 6 | 4 | 4 | 2 | 2 | |
F-1 | NS | UL | 11 | 4 | 2 | 3 | 2 | 3 | 3 | 3 | 4 | 2 | 1 |
S | UL | 12 | 5 | 3 | 4 | 3 | 10 | 7 | 5 | 5 | 3 | 2 | |
F-2 | NS | UL | 11 | 5 | 3 | 4 | 3 | 5 | 5 | 5 | 5 | 3 | 2 |
S | UL | 12 | 6 | 4 | 5 | 4 | 12 | 8 | 6 | 6 | 4 | 3 | |
H-1 | NSc,d | 1 | 1 | 1 | 1 | 1 | 1 | NP | NP | NP | 1 | 1 | NP |
S | 1 | 1 | 1 | ||||||||||
H-2 | NSc,d | UL | 3 | 2 | 1 | 2 | 1 | 1 | 1 | 1 | 2 | 1 | 1 |
S | 2 | 2 | 2 | ||||||||||
H-3 | NSc,d | UL | 6 | 4 | 2 | 4 | 2 | 3 | 3 | 3 | 4 | 2 | 1 |
S | 4 | 4 | 4 | ||||||||||
H-4 | NSc,d | UL | 7 | 5 | 3 | 5 | 3 | 5 | 5 | 5 | 5 | 3 | 2 |
S | UL | 8 | 6 | 4 | 6 | 4 | 8 | 7 | 6 | 6 | 4 | 3 | |
H-5 | NSc,d | 4 | 4 | 3 | 3 | 3 | 3 | 2 | 2 | 2 | 3 | 3 | 2 |
S | 3 | 3 | 3 | ||||||||||
I-1 Condition 1 | NSd,e | UL | 9 | 4 | 3 | 4 | 3 | 4 | 4 | 4 | 4 | 3 | 2 |
S | UL | 10 | 5 | 4 | 5 | 4 | 10 | 7 | 5 | 5 | 4 | 3 | |
I-1 Condition 2 | NSd,e | UL | 9 | 4 | 3 | 4 | 3 | 3 | 3 | 3 | 4 | 3 | 2 |
Si | UL | 10 | 5 | 10 | 6 | 4 | |||||||
I-2 | NSd,f | UL | 4 | 2 | 1 | 1 | NP | NP | NP | NP | 1 | 1 | NP |
S | UL | 5 | 3 | 7 | 5 | 1 | |||||||
I-3 | NSd,e | UL | 4 | 2 | 1 | 2 | 1 | 2 | 2 | 2 | 2 | 2 | 1 |
S | UL | 5 | 3 | 2 | 3 | 2 | 7 | 5 | 3 | 3 | 3 | 2 | |
I-4 | NSd,g | UL | 5 | 3 | 2 | 3 | 2 | 3 | 3 | 3 | 3 | 1 | 1 |
S | UL | 6 | 4 | 3 | 4 | 3 | 9 | 6 | 4 | 4 | 2 | 2 | |
M | NS | UL | 11 | 4 | 2 | 4 | 2 | 4 | 4 | 4 | 4 | 3 | 1 |
S | UL | 12 | 5 | 3 | 5 | 3 | 12 | 8 | 6 | 5 | 4 | 2 | |
R-1h | NSd | UL | 11 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 3 | 2 |
S13R | 4 | 4 | 4 | 3 | |||||||||
S | UL | 12 | 5 | 5 | 5 | 5 | 18 | 12 | 8 | 5 | 4 | 3 | |
R-2h | NSd | UL | 11 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 3 | 2 |
S13R | 4 | 4 | 4 | 4 | 3 | ||||||||
S | UL | 12 | 5 | 5 | 5 | 5 | 18 | 12 | 8 | 5 | 4 | 3 | |
R-3h | NSd | UL | 11 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 3 | 3 |
S13D | 4 | 4 | 3 | 3 | |||||||||
S13R | 4 | 4 | 4 | 4 | |||||||||
S | UL | 12 | 5 | 5 | 5 | 5 | 18 | 12 | 5 | 5 | 4 | 4 | |
R-4h | NSd | UL | 11 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 3 | 2 |
S13D | 4 | 4 | 3 | 2 | |||||||||
S13R | 4 | 4 | 4 | 3 | |||||||||
S | UL | 12 | 5 | 5 | 5 | 5 | 18 | 12 | 5 | 5 | 4 | 3 | |
S-1 | NS | UL | 11 | 4 | 2 | 3 | 2 | 4 | 4 | 4 | 4 | 3 | 1 |
S | UL | 12 | 5 | 4 | 4 | 4 | 10 | 7 | 5 | 5 | 4 | 2 | |
S-2 | NS | UL | 11 | 5 | 3 | 4 | 3 | 4 | 4 | 4 | 5 | 4 | 2 |
S | UL | 12 | 6 | 4 | 5 | 4 | 12 | 8 | 5 | 6 | 5 | 3 | |
U | NS | UL | 5 | 4 | 2 | 3 | 2 | 4 | 4 | 4 | 4 | 2 | 1 |
S | UL | 6 | 5 | 3 | 4 | 3 | 9 | 6 | 5 | 5 | 3 | 2 |
UL = Unlimited; NP = Not permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3. | ||
a | See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter. | |
b | See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies. | |
c | New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5. | |
d | The NS value is only for use in evaluation of existing building height in accordance with the International Existing Building Code. | |
e | New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies Condition 1, see Exception 1 of Section 903.2.6. | |
f | New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International Fire Code. | |
g | For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6. | |
h | New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8. | |
i |