Fire Separation Distance = X (feet) | Type of Construction | Occupancy Group He | Occupancy Group F-1, M, S-1f | Occupancy Group A, B, E, F-2, I, Ri, S-2, Uh |
X < 5b | All | 3 | 2 | 1 |
5 ≤ X < 10 | IA, IVA | 3 | 2 | 1 |
Others | 2 | 1 | 1 | |
10 ≤ X < 30 | IA, IB, IVA, IVB | 2 | 1 | 1c |
IIB, VB | 1 | 0 | 0 | |
Others | 1 | 1 | 1c | |
X ≥ 30 | All | 0 | 0 | 0 |
For SI: 1 foot = 304.8 mm. | ||
a | Load-bearing exterior walls shall also comply with the fire-resistance rating requirements of Table 601. | |
b | See Section 706.1.1 for party walls. | |
c | Open parking garages complying with Section 406 shall not be required to have a fire-resistance rating. | |
d | The fire-resistance rating of an exterior wall is determined based upon the fire separation distance of the exterior wall and the story in which the wall is located. | |
e | For special requirements for Group H occupancies, see Section 415.6. | |
f | For special requirements for Group S aircraft hangars, see Section 412.3.1. | |
g | Where Table 705.8 permits nonbearing exterior walls with unlimited area of unprotected openings, the required fire-resistance rating for the exterior walls is 0 hours. | |
h | For a building containing only a Group U occupancy private garage or carport, the exterior wall shall not be required to have a fire-resistance rating where the fire separation distance is 5 feet (1523 mm) or greater. | |
i | For a Group R-3 building of Type II-B or Type V-B construction, the exterior wall shall not be required to have a fire-resistance rating where the fire separation distance is 5 feet (1523 mm) or greater. | |
j | In a mixed occupancy building containing Group R-3 and Group U private garage, the exterior wall fire-resistance rating shall be as required for Group R-3. |
Fire Separation Distance (feet) | Degree of Opening Protection | Allowable Areaa |
Unprotected, Nonsprinklered (UP, NS) | Not Permittedk | |
0 to less than 3b,c,k | Unprotected, Sprinklered (UP, S)i | Not Permittedk |
Protected (P) | Not Permittedk | |
Unprotected, Nonsprinklered (UP, NS) | Not Permitted | |
3 to less than 5d,e | Unprotected, Sprinklered (UP, S)i | 15% |
Protected (P) | 15% | |
Unprotected, Nonsprinklered (UP, NS) | 10%h | |
5 to less than 10e,f,j | Unprotected, Sprinklered (UP, S)i | 25% |
Protected (P) | 25% | |
Unprotected, Nonsprinklered (UP, NS) | 15%h | |
10 to less than 15e,f,g,j | Unprotected, Sprinklered (UP, S)i | 45% |
Protected (P) | 45% | |
Unprotected, Nonsprinklered (UP, NS) | 25% | |
15 to less than 20f,g,j | Unprotected, Sprinklered (UP, S)i | 75% |
Protected (P) | 75% | |
Unprotected, Nonsprinklered (UP, NS) | 45% | |
20 to less than 25f,g,j | Unprotected, Sprinklered (UP, S)i | No Limit |
Protected (P) | No Limit | |
Unprotected, Nonsprinklered (UP, NS) | 70% | |
25 to less than 30f,g,j | Unprotected, Sprinklered (UP, S)i | No Limit |
Protected (P) | No Limit | |
Unprotected, Nonsprinklered (UP, NS) | No Limit | |
30 or greater | Unprotected, Sprinklered (UP, S)i | No Limit |
Protected (P) | No Limit |
For SI: 1 foot = 304.8 mm. | ||
UP, NS = Unprotected openings in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. | ||
UP, S = Unprotected openings in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. | ||
P = Openings protected with an opening protective assembly in accordance with Section 705.8.2. | ||
a | Values indicated are the percentage of the area of the exterior wall, per story. | |
b | For the requirements for fire walls of buildings with differing heights, see Section 706.6.1. | |
c | For openings in a fire wall for buildings on the same lot, see Section 706.8. | |
d | The maximum percentage of unprotected and protected openings shall be 25 percent for Group R-3 occupancies. | |
e | Unprotected openings shall not be permitted for openings with a fire separation distance of less than 15 feet for Group H-2 and H-3 occupancies. | |
f | The area of unprotected and protected openings shall not be limited for Group R-3 occupancies, with a fire separation distance of 5 feet or greater. | |
g | The area of openings in an open parking structure with a fire separation distance of 10 feet or greater shall not be limited. | |
h | Includes buildings accessory to Group R-3. | |
i | Not applicable to Group H-1, H-2, and H-3 occupancies. | |
j | The area of openings in a building containing only a Group U occupancy private garage or carport with a fire separation distance of 5 feet or greater shall not be limited. | |
k | For openings between S-2 parking garage and Group R-2 building, see Section 705.3, Exception 2. | |
l | In a mixed occupancy building containing Group R-3 and Group U private garage, the maximum area of exterior openings shall be as required for Group R-3. |