EXCEPTIONS: | 1. Fire doors located in common walls separating sleeping units in Group R-l shall be permitted without automatic- or self-closing devices. |
| 2. The elevator car doors and the associated hoistway enclosure doors at the floor level designated for recall in accordance with Section 3003.2 shall be permitted to remain open during Phase I emergency recall operation. |
| 3. In Group I-1, Condition 2 Assisted living facilities licensed under chapter 388-78A WAC and residential treatment facilities licensed under chapter 246-337 WAC, fire doors in dwelling and sleeping units opening to the corridor shall be permitted without automatic or self-closing devices when all of the following conditions exist: |
| 3.1 Each floor is constantly attended by staff on a 24-hour basis and stationed on that floor; |
| 3.2 The facility is provided with an NFPA 13 sprinkler system throughout; |
| 3.3 Doors shall be equipped with positive latching; |
| 3.4 Dwelling and sleeping units are not equipped with cooking appliances; |
| 3.5 Dwelling and sleeping units shall be equipped with a smoke detection system interconnected with the smoke detection system required by Section 907.2.6.1. |