EXCEPTION: | Fireplaces with gas logs shall be installed in accordance with the International Mechanical Code Section 901, except that the standards for liquefied petroleum gas installations shall be NFPA 58 (Liquefied Petroleum Gas Code) and NFPA 54 (National Fuel Gas Code). |
2. An outside source for combustion air ducted into the firebox. The duct shall be at least 6 square inches, and shall be provided with an operable outside air duct damper.
EXCEPTION: | Washington certified fireplaces shall be installed with the combustion air systems necessary for their safe and efficient combustion and specified by the manufacturer in accordance with IBC Section 2115 (WAC 51-50-2115). |
3. Site built fireplaces shall have tight fitting glass or metal doors, or a flue draft induction fan or as approved for minimizing back-drafting. Factory built fireplaces shall use doors listed for the installed appliance.
2111.8.1 Lintel and throat. Masonry over a fireplace opening shall be supported by a lintel of noncombustible material. The minimum required bearing length on each end of the fireplace opening shall be 4 inches (102 mm). The fireplace throat or damper shall be located a minimum of 8 inches (203 mm) above the top of the fireplace opening.
[Statutory Authority: RCW
19.27.031,
19.27.074, and
19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-2111, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW
19.27.031 and
19.27.074. WSR 16-03-064, § 51-50-2111, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW
19.27.031 and chapters
19.27 and
34.05 RCW. WSR 13-04-067, § 51-50-2111, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW
19.27.031 and
19.27.074. WSR 10-03-097, § 51-50-2111, filed 1/20/10, effective 7/1/10.]