EXCEPTIONS: | 1. Cooling coils that are designed, controlled and operated to provide sensible cooling only do not require filtration at the terminal device. |
| 2. Ambient air that enters the building through intentional openings for natural ventilation or by infiltration is not required to be filtered. |
| 3. Recirculated air serving systems without wetted cooling coils or with unducted heater (hydronic coils, fossil fuel heating elements or electric resistance heating elements) do not require filtration at the terminal device. |
605.4 Particulate matter removal. Particulate matter filters or air cleaners shall have a minimum efficiency reporting value (MERV) of not less than the following:
1. MERV 13 for ducted air handlers and ventilation systems serving occupiable spaces in Groups A, B, E, M, R and I occupancies.
2. MERV 8 for ducted air handlers and ventilation systems serving occupiable spaces in Groups F, H, S, and U occupancies.
3. MERV 4 for unducted air handlers and fan coil units.
EXCEPTIONS: | 1. Ducted air handlers and ventilation systems 500 cfm or less shall have a filter not less than MERV 8. |
| 2. Recirculated air at fan powered variable air volume terminal units with hydronic heating coils or electric resistance heating elements shall have a filter not less than MERV 8. |
| 3. Exhaust or relief air upstream of a heat exchanger or coil shall have a filter not less than MERV 6. |