End-Use | Prohibited Substances | Exemptions |
Commercial refrigeration: Retail food refrigeration, including chillers (New or retrofit) | Refrigerants with a GWP greater than 150 | Equipment with 50 pounds or less of refrigerant; Replacement of a refrigeration component in an existing facility as part of normal maintenance provided the result does not meet the criteria of "new refrigeration equipment" as defined in WAC 173-443-030; Facilities with new refrigeration equipment with an approved building permit issued before the effective date of this chapter; and Mission-critical military end-uses, as defined in WAC 173-443-030. |
Commercial refrigeration: Cold storage warehouses (New or retrofit) | Refrigerants with a GWP greater than 150 | Equipment with 50 pounds or less of refrigerant; Replacement of a refrigeration component in an existing facility as part of normal maintenance provided the result does not meet the criteria of "new refrigeration equipment" as defined in WAC 173-443-030; Facilities with new refrigeration equipment with an approved building permit issued before the effective date of this chapter; and Mission-critical military end-uses, as defined in WAC 173-443-030. |
Industrial process refrigeration, excluding chillers (New or retrofit) | Refrigerants with a GWP greater than 150 | Equipment with 50 pounds or less of refrigerant; Replacement of a refrigeration component in an existing facility as part of normal maintenance provided the result does not meet the criteria of "new refrigeration equipment" as defined in WAC 173-443-030; Very low temperature (VLT) refrigeration or cooling uses; Facilities with new refrigeration equipment with an approved building permit issued before the effective date of this chapter; and Mission-critical military end-uses, as defined in WAC 173-443-030. |
Chillers used for industrial process refrigeration (New or retrofit) | Refrigerants with a GWP greater than 750 | Equipment with 50 pounds or less of refrigerant; Replacement of a refrigeration component in an existing facility as part of normal maintenance provided the result does not meet the criteria of "new refrigeration equipment" as defined in WAC 173-443-030; Very low temperature (VLT) refrigeration or cooling uses; Facilities with new refrigeration equipment with a building permit issued before the effective date of this chapter; and Mission-critical military end-uses, as defined in WAC 173-443-030. |
End-Use | Prohibited Substances | Exemptions |
Room air conditioners and residential dehumidifiers (New or retrofit) | Refrigerants with a GWP greater than 750 | Facilities with new air conditioning equipment with a building permit issued before the effective date of this chapter; and Mission-critical military end-uses, as defined in WAC 173-443-030. |
Variable refrigerant flow (VRF) or volume system (New or retrofit) | Refrigerants with a GWP greater than 750 | Facilities with new air conditioning equipment with a building permit issued before the effective date of this chapter; and Mission-critical military end-uses, as defined in WAC 173-443-030. |
Other types of air conditioning equipment used in residential and nonresidential applications (New or retrofit) | Refrigerants with a GWP greater than 750 | Facilities with new air conditioning equipment with a building permit issued before the effective date of this chapter; and Mission-critical military end-uses, as defined in WAC 173-443-030. |