* | Mixed oak or equivalent with a bending strength not less than 850 psi. |
** | Manufactured members of equivalent strength may be substituted for wood. |
TABLE N-3
TIMBER TRENCH SHORING — MINIMUM TIMBER REQUIREMENTS*
SOIL TYPE B Pa - 45 X H + 72 psf (2 ft. Surcharge)
* | Mixed oak or equivalent with a bending strength not less than 850 psi. |
** | Manufactured members of equivalent strength may be substituted for wood. |
TABLE N-4
TIMBER TRENCH SHORING — MINIMUM TIMBER REQUIREMENTS*
SOIL TYPE C Pa - 80 X H + 72 psf (2 ft. Surcharge)
* | Mixed oak or equivalent with a bending strength not less than 850 psi. |
** | Manufactured members of equivalent strength may be substituted for wood. |
TABLE N-5
TIMBER TRENCH SHORING — MINIMUM TIMBER REQUIREMENTS*
SOIL TYPE A Pa - 25 X H + 72 psf (2 ft. Surcharge)
* | Douglas fir or equivalent with a bending strength not less than 1500 psi. |
** | Manufactured members of equivalent strength may be substituted for wood. |
TABLE N-6
TIMBER TRENCH SHORING — MINIMUM TIMBER REQUIREMENTS*
SOIL TYPE B Pa - 45 X H + 72 psf (2 ft. Surcharge)
* | Douglas fir or equivalent with a bending strength not less than 1500 psi. |
** | Manufactured members of equivalent strength may be substituted for wood. |
TABLE N-7
TIMBER TRENCH SHORING — MINIMUM TIMBER REQUIREMENTS*
SOIL TYPE C Pa - 80 X H + 72 psf (2 ft. Surcharge)
* | Douglas fir or equivalent with a bending strength not less than 1500 psi. |
** | Manufactured members of equivalent strength may be substituted for wood. |
[Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050,
49.17.060. WSR 16-09-085, § 296-155-66405, filed 4/19/16, effective 5/20/16. Statutory Authority: RCW
49.17.010, [49.17].040, [49.17].050. WSR 02-12-098, § 296-155-66405, filed 6/5/02, effective 8/1/02. Statutory Authority: Chapter
49.17 RCW and RCW
49.17.040, [49.17].050 and [49.17].060. WSR 92-22-067 (Order 92-06), § 296-155-66405, filed 10/30/92, effective 12/8/92.]