Exception: | The employer may use uniformly spaced standpipe systems or hose stations connected to a sprinkler system for emergency use by employees instead of Class A portable fire extinguishers, if: |
| 1. The system meets all regulatory requirements governing total coverage of the area to be protected; and |
| 2. Employees are trained at least annually in their use. |
(b) For Class B fires: The employer must distribute portable fire extinguishers so that no employee must travel more than 50 feet (15.2 m) to a fire extinguisher.
(c) For Class C fires: The employer must distribute portable fire extinguishers on the basis of the appropriate pattern for the existing Class A or Class B hazards.
(d) For Class D fires: The employer must distribute portable fire extinguishers or other containers of Class D extinguishing agent so no employee must travel more than 75 feet (22.9 m) from the combustible metal working area to any extinguishing agent. Portable fire extinguishers for Class D hazards are required in those combustible metal working areas where combustible metal powders, flakes, shavings, or similarly sized products are generated at least once every two weeks.