Nominal voltage to ground | Minimum clear distance for condition (ft) |
(a) | (b) | (c) |
0-150 | 13 | 13 | 3 |
151-600 | 13 | 3-1/2 | 4 |
Conditions: | (a) Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides guarded by suitable wood or other insulating material. Insulated wire or insulated busbars operating at 300 volts or less are not considered live parts. |
| (b) Exposed live parts on one side and grounded parts on the other side. |
| (c) Exposed live parts on both sides of the workspace (not guarded as in (a)) with the operator between. |
(2) Working space required by this part must not be used for storage. When normally enclosed live parts are exposed for inspection or servicing, the working space, if in a passageway or general open space, must be suitably guarded.
(3) At least one entrance of sufficient area must be provided to give access to the working space about electric equipment.
(4) Where there are live parts normally exposed on the front of switchboards or motor control centers, the working space in front of such equipment must be at least 3 feet.
(5) All working spaces around service equipment, switchboards, panelboards, and motor control centers installed indoors must be adequately lit.
(6) The minimum headroom of working spaces about service equipment, switchboards, panelboards, or motor control centers must be 6 feet 3 inches.
Motor control center. An assembly of one or more enclosed sections having a common power bus and principally containing motor control units.
[Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050, and
49.17.060. WSR 20-21-091, § 296-307-36227, filed 10/20/20, effective 11/20/20. WSR 97-09-013, recodified as § 296-307-36227, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW
49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-36227, filed 10/31/96, effective 12/1/96.]