Note: | It is impossible to set out in a table the length of a fixed dip tube for various tank capacities because of the various tank diameters and lengths, and because the tank may be installed either vertically or horizontally. If the maximum permitted filling volume in gallons is known, however, the employer can determine the length of the fixed tube by using a strapping table from the container manufacturer. |
| The fixed tube should be long enough so that when its lower end touches the surface of the liquid in the container, the contents of the container will be the maximum permitted volume as determined by the following formula: |
Water capacity of container1 (gals.) X filling density2 | = | Maximum volume of LP-gas |
Specific gravity of LP-gas1 x volume correction factor3 x 100 |
1 | Measure at 60°F. |
2 | |
3 | For aboveground containers the liquid temperature is assumed to be 40°F and for underground containers the liquid temperature is assumed to be 50°F. To correct the liquid volumes at these temperatures to 60°F, use the following factors: |
(a) To determine maximum volume of LP-gas for which a fixed length of dip tube must be set:
TABLE U-6
VOLUME CORRECTION FACTORS
Specific gravity | Aboveground | Underground |
0.500 | 1.033 | 1.017 |
.510 | 1.031 | 1.016 |
.520 | 1.029 | 1.015 |
.530 | 1.028 | 1.014 |
.540 | 1.026 | 1.013 |
.550 | 1.025 | 1.013 |
.560 | 1.024 | 1.012 |
.570 | 1.023 | 1.011 |
.580 | 1.021 | 1.011 |
.590 | 1.020 | 1.010 |
(b) To calculate the maximum volume of LP-gas that can be placed in a container when determining the length of the dip tube expressed as a percentage of total water content of the container, use the formula in (c) of this subsection.
(c) Determine the maximum weight of LP-gas that may be placed in a container for determining the length of a fixed dip tube by multiplying the maximum volume of LP-gas from Table U-6 by the pounds of LP-gas in a gallon at 40°F for aboveground and at 50°F for underground containers. Typical pounds per gallon are specified below:
Example: | Assume a one hundred gallon total water capacity tank for aboveground storage of propane having a specific gravity of 0.510 of 60°F. |
100 (gals.) x 42 (filling density) | = | 4200 | |
0.510 x 1.031 (correction factor from Table U-6) x 100 | 52.6 |
| 4200 | = | 79.8 gallons propane, the maximum amount permitted to be placed in a 100-gallon total water capacity above ground container equipped with a fixed dip tube. |
52.6 |
Maximum volume of LP-gas (from formula in (a) of this subsection) x 100 | = | Maximum percent of LP-gas |
Total water content of container in gallons |
| Aboveground, pounds per gallon | Underground, pounds per gallon |
Propane | 4.37 | 4.31 |
N Butane | 4.97 | 4.92 |
(6) Fixed liquid-level gauges used on non-DOT containers must be stamped on the exterior of the gauge with the letters DT followed by the vertical distance (expressed in inches and carried out to one decimal place) from the top of container to the end of the dip tube or to the centerline of the gauge when located at the maximum permitted filling level. For portable containers that may be filled in the horizontal and/or vertical position the letters DT must be followed by V with the vertical distance from the top of the container to the end of the dip tube for vertical filling, and with H followed by the proper distance for horizontal filling. For DOT containers the stamping must be placed both on the exterior of the gauge and on the container. On aboveground or cargo containers where the gauges are positioned at specific levels, the marking may be specified in percent of total tank contents and the marking must be stamped on the container.
(7) Columnar gauge glasses must be restricted to charging plants where the fuel is withdrawn in the liquid phase only. They must have valves with metallic handwheels, excess flow valves, and extra-heavy glass adequately protected with a metal housing applied by the gauge manufacturer. They must be shielded against the direct rays of the sun. Columnar gauge glasses are prohibited on tank trucks, motor fuel tanks, and containers used in domestic, commercial, and industrial installations.
(8) Float gauging devices or equivalent that do not require flow for their operation and that have connections extending outside the container do not have to have excess flow valves if the piping and fittings are adequately designed to withstand the container pressure and are properly protected against physical damage and breakage.
[Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050, and
49.17.060. WSR 20-21-091, § 296-307-41049, filed 10/20/20, effective 11/20/20. Statutory Authority: RCW
49.17.040. WSR 98-24-096, § 296-307-41049, filed 12/1/98, effective 3/1/99. WSR 97-09-013, recodified as § 296-307-41049, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW
49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-41049, filed 10/31/96, effective 12/1/96.]