Note: | This section establishes minimal levels of lighting for safety purposes only. Guidelines pertaining to optimal levels of lighting and illumination may be found in Practice for Industrial Lighting, ANSI/IES RP7-1979. (See the resource section of this book on how to contact ANSI.) |
(1) You must provide and maintain adequate lighting for all work activities in your workplace. See the following table.
Lighting Table |
Activity | Minimum acceptable average lighting level in an area: | Any one single measurement used to determine the average lighting level* cannot be less than: |
| (Foot-candles) | (Foot-candles) |
Indoor task | 10 | 5 |
Outdoor task | 5 | 2.5 |
Nontask activities for both indoor and outdoor | 3 | 1.5 |
* | Lighting levels must be measured at thirty inches above the floor/working surface at the task. |
(2) You must have adequate light for employees to see nearby objects that might be potential hazards or to see to operate emergency controls or other equipment, if general lighting is not available.
Note: | • Lighting levels can be measured with a light meter. |
| • Conversion information: 1 foot-candle = 1 lumen incident per square foot = 10.76 lux. |