Note: | Specific rules regarding conducting hydrostatic tests are covered in WAC 296-24-59212. |
(6) You must maintain records showing that hydrostatic testing has been performed. Provide the following evidence to the department upon request:
(a) Date of test.
(b) Test pressure used.
(c) The serial number, or other identifier of the fire extinguisher that was tested.
(d) Person or agency performing the test.
(7) You must keep records until:
(a) The extinguisher is retested; or
(b) The extinguisher is taken out of service, whichever comes first.
(8) You must empty and maintain stored-pressure dry chemical extinguishers requiring a 12-year hydrostatic test, every six years:
When recharging or hydrostatic testing is performed, the 6-year requirement begins from that date
Hydrostatic Test Table
Type of Extinguisher | Test Interval (Years) |
Stored pressure water and/or antifreeze | 5 |
Wetting agent | 5 |
Foam (stainless steel shell) | 5 |
Aqueous film forming form (AFFF) | 5 |
Loaded stream | 5 |
Dry chemical with stainless steel | 5 |
Carbon dioxide | 5 |
Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells | 12 |
Halon 1211 | 12 |
Halon 1301 | 12 |
Dry powder, cartridge or cylinder operated, with mild steel shell | 12 |
Note: Due to a manufacturer's recall, stored pressure water extinguishers with fiberglass shell (pre-1976) are prohibited from hydrostatic testing. |
[Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050, and
49.17.060. WSR 18-22-116, § 296-800-30020, filed 11/6/18, effective 12/7/18. Statutory Authority: RCW
49.17.010, [49.17].040, and [49.17].050. WSR 01-23-060, § 296-800-30020, filed 11/20/01, effective 12/1/01; WSR 01-11-038, § 296-800-30020, filed 5/9/01, effective 9/1/01.]