PDFWAC 296-826-60030

Nonrefrigerated containers.

You must meet the requirements …
in this section:
Nonrefrigerated containers
WAC 296-826-60030
Refrigerated tanks
Welding
You must make sure filling densities for nonrefrigerated containers are below or equal to the requirements in Table 15, Filling Densities.
Table 15
Filling Densities
Containers
Aboveground Containers
Underground Containers
Uninsulated
56%
58%
Insulated
57%
——
Note:
For uninsulated, aboveground containers, the 56% corresponds to:
 
1. 82% by volume at -28°F.
 
2. 85% by volume at 5°F.
 
3. 87.5% by volume at 30°F.
 
4. 90.6% by volume at 60°F.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050. WSR 15-23-086, § 296-826-60030, filed 11/17/15, effective 12/18/15. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. WSR 06-10-067, § 296-826-60030, filed 5/2/06, effective 9/1/06.]