Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
Air cooled (cooling mode) | < 65,000 Btu/hb | All | Split System | 14.0 SEER | AHRI 210/240 |
| | | Single Packaged | 14.0 SEER | |
Through-the-wall, air cooled (cooling mode) | ≤ 30,000 Btu/hb | All | Split System | 12.0 SEER | |
| | | Single Packaged | 12.0 SEER | |
Small duct high velocity, air cooled | < 65,000 Btu/hb | All | Split System | 11.0 SEER | |
Air cooled (cooling mode) | ≥ 65,000 Btu/h and < 135,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 11.0 EER 12.2 IEER | AHRI 340/360 |
| | All Other | Split System and Single Package | 10.8 EER 12.0 IEER | |
| ≥ 135,000 Btu/h and < 240,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 10.6 EER 11.6 IEER | |
| | All Other | Split System and Single Package | 10.4 EER 11.4 IEER | |
| ≥ 240,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 9.5 EER 10.6 IEER | |
| | All Other | Split System and Single Package | 9.3 EER 10.4 IEER | |
Water source (cooling mode) | < 17,000 Btu/h | All | 86°F entering water | 12.2 EER | ISO 13256-1 |
| ≥ 17,000 Btu/h and < 65,000 Btu/h | All | 86°F entering water | 13.0 EER | |
| ≥ 65,000 Btu/h and < 135,000 Btu/h | All | 86°F entering water | 13.0 EER | |
Ground water source (cooling mode) | < 135,000 Btu/h | All | 59°F entering water | 18.0 EER | |
Ground water source (cooling mode) | < 135,000 Btu/h | All | 77°F entering water | 14.1 EER | |
Water-source water to water (cooling mode) | < 135,000 Btu/h | All | 86°F entering water | 10.6 EER | ISO 13256-2 |
| | | 59°F entering water | 16.3 EER | |
Ground water source brine to water (cooling mode) | < 135,000 Btu/h | All | 77°F entering fluid | 12.1 EER | |
Air cooled (heating mode) | < 65,000 Btu/hb | — | Split System | 8.2 HSPF | AHRI 210/240 |
| | — | Single Package | 8.0 HSPF | |
Through-the-wall, (air cooled, heating mode) | ≤ 30,000 Btu/hb (cooling capacity) | — | Split System | 7.4 HSPF | |
| | — | Single Package | 7.4 HSPF | |
Small-duct high velocity (air cooled, heating mode) | < 65,000 Btu/hb | — | Split System | 6.8 HSPF | |
Air cooled (heating mode) | ≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) | — | 47°F db/43ºF wb Outdoor Air | 3.3 COP | AHRI 340/360 |
| | | 17ºF db/15ºF wb Outdoor Air | 2.25 COP | |
| ≥ 135,000 Btu/h (cooling capacity) | — | 47°F db/43ºF wb Outdoor Air | 3.2 COP | |
| | | 17ºF db/15ºF wb Outdoor Air | 2.05 COP | |
Water source (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 68°F entering water | 4.3 COP | ISO 13256-1 |
Ground water source (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 50°F entering water | 3.7 COP | |
Ground source (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 32°F entering fluid | 3.2 COP | |
Water-source water to water (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 68°F entering water | 3.7 COP | ISO 13256-2 |
| | — | 50°F entering water | 3.1 COP | |
Ground source brine to water (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 32°F entering fluid | 2.5 COP | |
For SI: | 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8. |
a | Chapter 6 of the referenced standard contains a complete specification of the referenced test procedure, including the reference year version of the test procedure. |
b | Single-phase, air-cooled air conditioners less than 65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA. |
[Statutory Authority: RCW
19.27A.025,
19.27A.160, and
19.27.074. WSR 16-03-072, § 51-11C-403232, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW
19.27A.020,
19.27A.025 and chapters
19.27 and
34.05 RCW. WSR 13-04-056, § 51-11-403232 (codified as WAC 51-11C-403232), filed 2/1/13, effective 7/1/13.]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency.
(Effective July 1, 2020)
Table C403.3.2(2)—Minimum efficiency requirements—Electrically operated unitary and applied heat pumps.
Table C403.3.2(2)
Minimum Efficiency Requirements—Electrically Operated Unitary and Applied Heat Pumps
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
Air cooled (cooling mode) | < 65,000 Btu/hb | All | Split System | 14.0 SEER | AHRI 210/240 |
| | | Single Packaged | 14.0 SEER | |
Through-the-wall, air cooled (cooling mode) | ≤ 30,000 Btu/hb | All | Split System | 12.0 SEER | |
| | | Single Packaged | 12.0 SEER | |
Small duct high velocity, air cooled | < 65,000 Btu/hb | All | Split System | 11.0 SEER | |
Air cooled (cooling mode) | ≥ 65,000 Btu/h and < 135,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 11.0 EER 12.2 IEER | AHRI 340/360 |
| | All Other | Split System and Single Package | 10.8 EER 12.0 IEER | |
| ≥ 135,000 Btu/h and < 240,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 10.6 EER 11.6 IEER | |
| | All Other | Split System and Single Package | 10.4 EER 11.4 IEER | |
| ≥ 240,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 9.5 EER 10.6 IEER | |
| | All Other | Split System and Single Package | 9.3 EER 10.4 IEER | |
Water to air, water loop (cooling mode) | < 17,000 Btu/h | All | 86°F entering water | 12.2 EER | ISO 13256-1 |
| ≥ 17,000 Btu/h and < 65,000 Btu/h | All | 86°F entering water | 13.0 EER | |
| ≥ 65,000 Btu/h and < 135,000 Btu/h | All | 86°F entering water | 13.0 EER | |
Water to air, ground water (cooling mode) | < 135,000 Btu/h | All | 59°F entering water | 18.0 EER | |
Brine to air, ground loop (cooling mode) | < 135,000 Btu/h | All | 77°F entering water | 14.1 EER | |
Water to water, water loop (cooling mode) | < 135,000 Btu/h | All | 86°F entering water | 10.6 EER | ISO 13256-2 |
Water to water, ground water (cooling mode) | < 135,000 Btu/h | All | 59°F entering water | 16.3 EER | |
Brine to water, ground loop (cooling mode) | < 135,000 Btu/h | All | 77°F entering fluid | 12.1 EER | |
Air cooled (heating mode) | < 65,000 Btu/hb | — | Split System | 8.2 HSPF | AHRI 210/240 |
| | — | Single Package | 8.0 HSPF | |
Through-the-wall, (air cooled, heating mode) | ≤ 30,000 Btu/hb (cooling capacity) | — | Split System | 7.4 HSPF | |
| | — | Single Package | 7.4 HSPF | |
Small-duct high velocity (air cooled, heating mode) | < 65,000 Btu/hb | — | Split System | 6.8 HSPF | |
Air cooled (heating mode) | ≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) | — | 47°F db/43ºF wb Outdoor Air | 3.3 COP | AHRI 340/360 |
| | | 17ºF db/15ºF wb Outdoor Air | 2.25 COP | |
| ≥ 135,000 Btu/h (cooling capacity) | — | 47°F db/43ºF wb Outdoor Air | 3.2 COP | |
| | | 17ºF db/15ºF wb Outdoor Air | 2.05 COP | |
Water to air, water loop (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 68°F entering water | 4.3 COP | ISO 13256-1 |
Water to air, ground water (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 50°F entering water | 3.7 COP | |
Brine to air, ground loop (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 32°F entering fluid | 3.2 COP | |
Water to water, water loop (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 68°F entering water | 3.7 COP | ISO 13256-2 |
| | — | 50°F entering water | 3.1 COP | |
Brine to water, ground loop (heating mode) | < 135,000 Btu/h (cooling capacity) | — | 32°F entering fluid | 2.5 COP | |
For SI: | 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8. |
a | Chapter 12 of the referenced standard contains a complete specification of the referenced test procedure, including the reference year version of the test procedure. |
b | Single-phase, air-cooled air conditioners less than 65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA. |
[Statutory Authority: RCW
19.27A.020,
19.27A.025,
19.27A.160 and chapter
19.27 RCW. WSR 19-24-040, § 51-11C-403232, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW
19.27A.025,
19.27A.160, and