a | Net sensible cooling capacity: The total gross cooling capacity less the latent cooling less the energy to the air movement system. (Total Gross – Latent – Fan Power.) |
b | Sensible coefficient of performance (SCOP-127): A ratio calculated by dividing the net sensible cooling capacity in watts by the total power input in watts (excluding reheaters and humidifiers) at conditions defined in ASHRAE Standard 127. The net sensible cooling capacity is the gross sensible capacity minus the energy dissipated into the cooled space by the fan system. |
Equipment Type | Subcategory | Minimum Efficiency | Test Procedurea |
Liquid-to-liquid heat exchangers | Plate type | NR | AHRI 400 |
NR = No requirement. | |
a | Chapter 6 of the referenced standard contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. |
Equipment Type | Net Sensible Cooling Capacity | Standard Model | Minimum Net Sensible COPc | Test Procedure | ||
Return Air Dry-Bulb Temperature/Dew-Point Temperature | ||||||
Class 1 | Class 2 | Class 3 | ||||
75°F/52°F | 85°F/52°F | 95°F/52°F | ||||
Air cooled | < 65,000 Btu/h | Downflow unit | 2.30 | AHRI 1360 | ||
Upflow unit - Ducted | 2.10 | |||||
Upflow unit - Unducted | 2.09 | |||||
Horizontal-flow unit | 2.45 | |||||
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | 2.20 | ||||
Upflow unit - Ducted | 2.05 | |||||
Upflow unit - Unducted | 1.99 | |||||
Horizontal-flow unit | 2.35 | |||||
≥ 240,000 Btu/h | Downflow unit | 2.00 | ||||
Upflow unit - Ducted | 1.85 | |||||
Upflow unit - Unducted | 1.79 | |||||
Horizontal-flow unit | 2.15 | |||||
Water cooled | < 65,000 Btu/h | Downflow unit | 2.50 | AHRI 1360 | ||
Upflow unit - Ducted | 2.30 | |||||
Upflow unit - Unducted | 2.25 | |||||
Horizontal-flow unit | 2.70 | |||||
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | 2.40 | ||||
Upflow unit - Ducted | 2.20 | |||||
Upflow unit - Unducted | 2.15 | |||||
Horizontal-flow unit | 2.60 | |||||
≥ 240,000 Btu/h | Downflow unit | 2.25 | ||||
Upflow unit - Ducted | 2.10 | |||||
Upflow unit - Unducted | 2.05 | |||||
Horizontal-flow unit | 2.45 | |||||
Water cooled with fluid economizer | < 65,000 Btu/h | Downflow unit | 2.45 | AHRI 1360 | ||
Upflow unit - Ducted | 2.25 | |||||
Upflow unit - Unducted | 2.20 | |||||
Horizontal-flow unit | 2.60 | |||||
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | 2.35 | ||||
Upflow unit - Ducted | 2.15 | |||||
Upflow unit - Unducted | 2.10 | |||||
Horizontal-flow unit | 2.55 | |||||
≥ 240,000 Btu/h | Downflow unit | 2.20 | ||||
Upflow unit - Ducted | 2.05 | |||||
Upflow unit - Unducted | 2.00 | |||||
Horizontal-flow unit | 2.40 | |||||
Glycol cooled | < 65,000 Btu/h | Downflow unit | 2.30 | AHRI 1360 | ||
Upflow unit - Ducted | 2.10 | |||||
Upflow unit - Unducted | 2.00 | |||||
Horizontal-flow unit | 2.40 | |||||
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | 2.05 | ||||
Upflow unit - Ducted | 1.85 | |||||
Upflow unit - Unducted | 1.85 | |||||
Horizontal-flow unit | 2.15 | |||||
≥ 240,000 Btu/h | Downflow unit | 1.95 | ||||
Upflow unit - Ducted | 1.80 | |||||
Upflow unit - Unducted | 1.75 | |||||
Horizontal-flow unit | 2.10 | |||||
Glycol cooled with fluid economizer | < 65,000 Btu/h | Downflow unit | 2.25 | AHRI 1360 | ||
Upflow unit - Ducted | 2.10 | |||||
Upflow unit - Unducted | 2.00 | |||||
Horizontal-flow unit | 2.35 | |||||
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | 1.95 | ||||
Upflow unit - Ducted | 1.80 | |||||
Upflow unit - Unducted | 1.75 | |||||
Horizontal-flow unit | 2.10 | |||||
≥ 240,000 Btu/h | Downflow unit | 1.90 | ||||
Upflow unit - Ducted | 1.80 | |||||
Upflow unit - Unducted | 1.70 | |||||
Horizontal-flow unit | 2.10 |
Equipment Type | Subcategory | Minimum Efficiency | Test Procedurea |
Liquid-to-liquid heat exchangers | Plate type | NR | AHRI 400 |
NR = No requirement. | |
a | Chapter 12 of the referenced standard contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. |
EQUIPMENT TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDURE |
Air cooled (dehumidification mode) | 4.0 ISMRE | AHRI 920 | |
Air source heat pumps (dehumidification mode) | 4.0 ISMRE | AHRI 920 | |
Water cooled (dehumidification mode) | Cooling tower condenser water | 4.9 ISMRE | AHRI 920 |
Chilled water | 6.0 ISMRE | ||
Air source heat pump (heating mode) | 2.7 ISCOP | AHRI 920 | |
Water source heat pump (dehumidification mode) | Ground source, closed loop | 4.8 ISMRE | AHRI 920 |
Ground-water source | 5.0 ISMRE | ||
Water source | 4.0 ISMRE | ||
Water source heat pump (heating mode) | Ground source, closed loop | 2.0 ISCOP | AHRI 920 |
Ground-water source | 3.2 ISCOP | ||
Water source | 3.5 ISCOP |
EQUIPMENT TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDURE |
Air cooled (dehumidification mode) | 5.2 ISMRE | AHRI 920 | |
Air source heat pumps (dehumidification mode) | 5.2 ISMRE | AHRI 920 | |
Water cooled (dehumidification mode) | Cooling tower condenser water | 5.3 ISMRE | AHRI 920 |
Chilled water | 6.6 ISMRE | ||
Air source heat pump (heating mode) | 3.3 ISCOP | AHRI 920 | |
Water source heat pump (dehumidification mode) | Ground source, closed loop | 5.2 ISMRE | AHRI 920 |
Ground-water source | 5.8 ISMRE | ||
Water source | 4.8 ISMRE | ||
Water source heat pump (heating mode) | Ground source, closed loop | 3.8 ISCOP | AHRI 920 |
Ground-water source | 4.0 ISCOP | ||
Water source | 4.8 ISCOP |