TYPE OF HOOD | LIGHT-DUTY EQUIPMENT | MEDIUM-DUTY EQUIPMENT | HEAVY-DUTY EQUIPMENT | EXTRA-HEAVY-DUTY EQUIPMENT |
Wall-mounted canopy | 140 | 210 | 280 | 385 |
Single island | 280 | 350 | 420 | 490 |
Double island (per side) | 175 | 210 | 280 | 385 |
Eyebrow | 175 | 175 | NA | NA |
Backshelf/pass-over | 210 | 210 | 280 | NA |
For SI: | 1 cfm = 0.4719 L/s; 1 foot = 305 mm |
NA = Not allowed |
EXCEPTIONS: | 1. Variable air volume laboratory exhaust and room supply systems configured to reduce exhaust and make-up air volume to 50 percent or less of design values; or |
2. Direct make-up (auxiliary) air supply equal to at least 75 percent of the exhaust rate, heated no warmer than 2°F (1.1°C) below room set point, cooled to no cooler than 3°F (1.7°C) above room set point, no humidification added, and no simultaneous heating and cooling used for dehumidification control; or | |
3. Combined energy reduction method: VAV exhaust and room supply system configured to reduce exhaust and makeup air volumes and a heat recovery system to precondition makeup air from laboratory exhaust that when combined will produce the same energy reduction as achieved by a heat recovery system with a 50 percent sensible recovery effectiveness as required above. For calculation purposes, the heat recovery component can be assumed to include the maximum design supply airflow rate at design conditions. The combined energy reduction (QER) shall meet the following: |
QER | ≥ | QMIN | |
QMIN | = | CFMS • (TR - TO) • 1.1 • 0.6 | |
QER | = | CFMS • (TR - TO) • 1.1(A + B)/100 | |
Where: | |||
QMIN | = | Energy recovery at 60 percent sensible effectiveness (Btu/h) | |
QER | = | Combined energy reduction (Btu/h) | |
CFMS | = | The maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute | |
TR | = | Space return air dry bulb at winter design conditions | |
TO | = | Outdoor air dry bulb at winter design conditions | |
A | = | Percentage that the exhaust and makeup air volumes can be reduced from design conditions | |
B | = | Percentage sensible heat recovery effectiveness |