EXCEPTION: | The use of mixed air temperature limit control shall be permitted for systems that are both controlled from space temperature (such as single zone systems) and having cooling capacity less than 65,000 Btu/h. |
C403.3.3.3 High-limit shutoff. Air economizers shall be configured to automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage. High-limit shutoff control types for specific climates shall be chosen from Table C403.3.3.3. High-limit shutoff control settings for these control types shall be those specified in Table C403.3.3.3.
Table C403.3.3.3
High-limit Shutoff Control Setting for Air Economizersb
Device Type | Climate Zone | Required High Limit (economizer off when): |
Equation | Description |
Fixed dry-bulb | 4C, 5B | TOA ˃ 75°F | Outdoor air temperature exceeds 75°F |
Differential dry-bulb | 4C, 5B | TOA ˃ TRA | Outdoor air temperature exceeds return air temperature |
Fixed enthalpy with fixed dry-bulb temperatures | All | hOA ˃ 28 Btu/lba or TOA ˃ 75°F | Outdoor air enthalpy exceeds 28 Btu/lb of dry aira or outdoor air temperature exceeds 75°F |
Differential enthalpy with fixed dry-bulb temperature | All | hOA ˃ hRA or TOA ˃ 75°F | Outdoor air enthalpy exceeds return air enthalpy or outdoor air temperature exceeds 75°F |
For SI: | °C = (°F - 32) × 5/9, 1 Btu/lb = 2.33 kJ/kg. |
a | At altitudes substantially different than sea level, the fixed enthalpy limit shall be set to the enthalpy value at 75°F and 50 percent relative humidity. As an example, at approximately 6,000 feet elevation the fixed enthalpy limit is approximately 30.7 Btu/lb. |
b | Devices with selectable setpoints shall be capable of being set to within 2°F and 2 Btu/lb of the setpoint listed. |
C403.3.3.4 Relief of excess outdoor air. Systems shall be capable of relieving excess outdoor air during air economizer operation to prevent over-pressurizing the building. The relief air outlet shall be located to avoid recirculation into the building.
C403.3.3.5 Economizer dampers. Return, exhaust/relief and outdoor air dampers used in economizers shall comply with Section C403.2.4.3.
(Effective July 1, 2020)
Section C403.3.3—Hot gas bypass.
C403.3.3 Hot gas bypass limitation. Cooling systems shall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as indicated in Table C403.3.3, as limited by Section C403.5.1.
Table C403.3.3
Maximum Hot Gas Bypass Capacity
Rated Capacity | Maximum Hot Gas Bypass Capacity (% of total capacity) |
≤ 240,000 Btu/h | 50 |
≥ 240,000 Btu/h | 25 |
For SI: | 1 British thermal unit per hour = 0.2931 W. |
[Statutory Authority: RCW
19.27A.020,
19.27A.025,
19.27A.160 and chapter
19.27 RCW. WSR 19-24-040, § 51-11C-40333, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW