Section C404.13—Service water-heating system commissioning and completion requirements.
C404.13 Service water-heating system commissioning and completion requirements. Service water-heating systems, swimming pool water-heating systems, spa water-heating systems and the controls for those systems shall be commissioned and completed in accordance with Section C408.
(Effective July 1, 2020)
Section C404.13—Service water pressure-booster systems.
C404.13 Servicewater pressure-booster systems. Service water pressure-booster systems shall be designed and configured such that the following apply:
1. One or more pressure sensors shall be used to vary pump speed and/or start and stop pumps. The sensors shall either be located near the critical fixtures that determine the pressure required, or logic shall be employed that adjusts the setpoint to simulate operations of remote sensors.
2. No devices shall be installed for the purpose of reducing the pressure of all of the water supplied by any booster system pump or booster system, except for safety devices.
3. Booster system pumps shall not operate when there is no service water flow except to refill hydro-pneumatic tanks.
4. System pump motors 7.5 hp and greater shall be provided with variable flow capacity in accordance with Section C403.2.3.
C404.14 Commissioning. Service water heating systems shall be commissioned in accordance with Section C408.