Total Chiller Plant Capacity | Number of Chillers |
≤ 300 tons | 1 |
˃ 300 tons, < 600 tons | 2, sized equally |
≥ 600 tons | 2 minimum, with chillers added so that no chiller is larger than 800 tons, all sized equally |
(Effective July 1, 2020)
Reserved.
[Statutory Authority: RCW
19.27A.020,
19.27A.025,
19.27A.160 and chapter
19.27 RCW. WSR 19-24-040, § 51-11C-407054, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW
19.27A.025,
19.27A.160, and
19.27.074. WSR 16-03-072, § 51-11C-407054, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW
19.27A.020,
19.27A.025 and chapters
19.27 and
34.05 RCW. WSR 13-04-056, § 51-11C-407054, filed 2/1/13, effective 7/1/13.]