(1) For utility interactive systems, any person making interconnections between a power production source and the utility distribution network must consult the serving utility and is required to meet all additional utility standards.
031 Location of overcurrent protection.
(2) In addition to the requirements of NEC 705.31, electric power production source conductors connected to the supply side of the service disconnecting means must be installed using wiring methods specified for service conductors in WAC
296-46B-230(7). The disconnecting means providing overcurrent protection for the electric power production source conductors is not required to be grouped with the service disconnecting means for the building or structure. Grounding and bonding must be in accordance with all applicable requirements for an additional service disconnect.