EXCEPTIONS: | 1. Buildings on the same lot and considered as portions of one building in accordance with Section 705.3 are not required to comply with this section for projections between the buildings. |
| 2. Projecting floors complying with Section 705.2.4 are not required to comply with the projection limitations of Table 705.2. |
705.2.4 Projecting floors. Where the fire separation distance on a lower floor is greater than the fire separation distance on the floor immediately above, the projecting floor shall have not less than the fire-resistance rating as the exterior wall above based on Table 602. The fire-resistant rating of the horizontal portion shall be continuous to the lower vertical wall.
705.2.5 Bay and oriel windows. Bay and oriel windows constructed of combustible materials shall conform to the type of construction required for the building to which they are attached.
EXCEPTION: | Fire-retardant-treated wood shall be permitted on buildings three stories or less above grade plane of Type I, II, III or IV construction. |
[Statutory Authority: RCW
19.27.031 and
19.27.074. WSR 20-21-021, § 51-50-0705, filed 10/9/20, effective 11/9/20; WSR 20-01-090, § 51-50-0705, filed 12/12/19, effective 7/1/20.]