Table 1 | Table 2 |
Minimum Design Candle power Requirements for Amber Light | Minimum Design Candle power Requirements for Green Light |
Test | Points | Candle power | Test | Points | Candle power |
10 up and 10 down | 10L V 10R | 25 65 25 | | 10 up and 10 down | 10L V 10R | 1 1 1 | .5 |
| 20L | 25 | | | 20L | 1 | |
| 10L | 65 | | | 10L | 2 | |
5 up | 5L | 85 | | 5 up | 5L | 4 | |
and | V | 125 | | and | V | 4 | |
5 down | 5R | 85 | | 5 down | 5R | 4 | |
| 10R | 65 | | | 10R | 2 | |
| 20R | 25 | | | 20R | 1 | |
| 20L | 25 | | | 20L | 2 | |
| 10L | 75 | | | 10L | 3 | |
| 5L | 125 | | | 5L | 5 | |
| H-V | 175 | | | H-V | 5 | |
| 5R | 125 | | | 5R | 5 | |
| 10R | 75 | | | 10R | 3 | |
| 20R | 25 | | | 20R | 2 | |
Maximum | 450 | | Maximum | 45 | |
(ii) Type II - The system must:
(A) Operate so as to indicate a component of deceleration of the vehicle on which it is installed by varying the flashing rate of a yellow lamp when the service brakes are applied.
(B) Incorporate an automatic means for reducing the intensity of the lamp during darkness. The system must cause the voltage to the deceleration lamps to decrease to 5.0 V ± 10% at 0 g deceleration during darkness. The specified voltage must be reached when the illumination on the sensor is not more than 5 lm/sq. ft., nor less than 0.5 lm/sq. ft.
(C) Have an output voltage, duty cycle, and flash rate of the control unit as a temperature of 24° ± 5.5°C (75° ± 10°F), when 12.8 V dc is applied to the input terminal, as shown in Table I when the control sensor is placed on a tilt table and slightly vibrated as the table is slowly rotated through the angles representing the specified vehicle deceleration rates.
table i
Test Requirements for Deceleration Lamps |
Deceleration (g) | Output (V) | Peak Relative Brightness | Flash Rate (Hz) | On Time (%) |
0.0 | 7.0 | 1.0 | 1.0 | 50 |
0.1 | — | 1.0 | 1.5 | 48 |
0.2 | — | 1.0 | 2.3 | 46 |
0.3 | — | 1.2 | 3.4 | 44 |
0.4 | — | 1.4 | 5.0 | 42 |
0.5 | — | 1.7 | 7.6 | 40 |
(D) Have a deceleration at which the unit switches from a lower to a higher flash rate that is within ± 0.05 g of the rate specified in Table I. If the unit operates at more steps than the required minimum, the additional values for each column must lie on the smooth curve connecting the indicated values within the specified tolerances. The values specified in Table II apply to ramp-type inertial sensors for which the downward angles correspond to the deceleration and a tolerance of 3.0° applies to the tilt angle.
table ii
Test Requirements for Deceleration Sensors |
| | DEGREES | | | |
Deceleration (g) | Forward Tilt Angle | | Dip Correction | | Corrected Tilt Angle |
0.0 | 0.0 | | 0.0 | 0.0 |
0.1 | 5.7 | | 0.8 | 6.5 |
0.2 | 11.3 | | 1.6 | 12.9 |
0.3 | 16.7 | | 2.4 | 19.1 |
0.4 | 21.8 | | 3.2 | 25.0 |
0.5 | 26.6 | | 4.0 | 30.6 |
(E) Have the rms of the output voltage during the on portion of the flash cycle at the 1 Hz flash rate within ± 5% of the specified value, measured at the lamp bulbs with daytime illumination on the automatic darkness sensor.
(F) Have a relative brightness of the lamp or bulbs at the decelerations within ± 25% of the specified values after the fifth flash with the brightness of the lamp or its bulbs taken as 1.0 when measured with the rms output voltage specified for 0 g deceleration.
(G) Have a flash rate within ± 15% of the specified value. The percent on time must be within ± 10% of the specified value.
(H) Have linear dip corrections varying from 4° at 0.5 g or more deceleration to 0° at 0 g on passenger vehicles and pickup trucks that have substantial front end dip upon braking.
(I) Comply with the following mechanical tests in SAE Standard J575g (tests for motor vehicle lighting devices and components): Corrosion, dust, moisture, vibration, and warpage (at a flashing rate of 1 Hz when a plastic lens or housing is used).
(J) Meet the following control system requirements at both 11 V and 15 V:
(I) Low temperature test. The control system must be placed in its normal operating position in a circulating air cabinet at -32° ± 3°C (-25° ± 5°F) for 2 hours. At the end of that period and while still at that temperature, the unit must meet the requirements in Table I at 0 g and 0.3 g.
(II) High temperature test. The control system must be placed in its normal operating position in a circulating air cabinet at 74° 0°, -2.8°C (165° 0°, -5°F) for 2 hours. At the end of that period and while at that temperature, the unit must meet the requirements in Table I at 0 g and 0.3 g.
(K) Operate the control system continuously at a supply voltage of 12.8 V dc for 200 hours with no failure (except bulb replacement), after which it must meet the requirements in Table I at 0 g and 0.3 g.
(L) Meet the photometric requirements in Table III after the sample has been mechanically tested in the order shown in (b)(ii)(J) of this subsection for the luminous intensity of a deceleration lamp with the bulbs operated at mean spherical candela.
table iii
Photometric Requirements for Deceleration Signal Lamps |
| Test Point Coordinates | Max | Cd | | Min |
Vertical | | Horizontal | Amber | Red | Amber | Red |
| | 10L | 70 | 35 | 25 | 12.5 |
10U | | V | 200 | 100 | 60 | 30 |
| | 10R | 70 | 35 | 25 | 12.5 |
| | 20L | 40 | 20 | 15 | 7.5 |
| | 10L | 200 | 100 | 60 | 30 |
| | 5L | 600 | 300 | 200 | 100 |
5U | | V | 800 | 400 | 350 | 175 |
| | 5R | 600 | 300 | 200 | 100 |
| | 10R | 200 | 100 | 60 | 30 |
| | 20R | 40 | 20 | 15 | 7.5 |
| | 20L | 40 | 20 | 15 | 7.5 |
| | 10L | 200 | 100 | 60 | 30 |
| | 5L | 800 | 400 | 350 | 175 |
H | | V | 1,300 | 650 | 600 | 300 |
| | 5R | 800 | 400 | 350 | 175 |
| | 10R | 200 | 100 | 60 | 30 |
| | 20R | 40 | 20 | 15 | 7.5 |
| | 20L | 40 | 20 | 15 | 7.5 |
| | 10L | 200 | 200 | 60 | 30 |
| | 5L | 600 | 300 | 200 | 100 |
5D | | V | 800 | 400 | 350 | 175 |
| | 5R | 600 | 300 | 200 | 100 |
| | 10R | 200 | 100 | 60 | 30 |
| | 20R | 40 | 20 | 15 | 7.5 |
| | 10L | 70 | 35 | 25 | 12.5 |
10D | | V | 200 | 100 | 60 | 30 |
| | 10R | 70 | 35 | 25 | 12.5 |
[Statutory Authority: RCW
46.37.005 and
46.37.320. WSR 15-16-124, § 204-21-180, filed 8/5/15, effective 9/5/15; WSR 08-19-104, § 204-21-180, filed 9/17/08, effective 10/18/08.]