| | | Overall U-Factor for Assembly of Base Roof Plus Continuous Insulation (uninterrupted by framing) Rated R-Value of Continuous Insulation |
Insulation System | Rated R-Value of Insulation | Overall U-Factor for Entire Base Roof Assembly | R-6.5 | R-13 | R-19.5 | R-26 | R-32.5 | R-39 |
Standing Seam Roofs with Thermal Spacer Blocksa, b |
| None | 1.280 | 0.137 | 0.073 | 0.049 | 0.037 | 0.030 | 0.025 |
| R-10 | 0.115 | 0.066 | 0.046 | 0.035 | 0.029 | 0.024 | 0.021 |
Single | R-11 | 0.107 | 0.063 | 0.045 | 0.035 | 0.028 | 0.024 | 0.021 |
Layer | R-13 | 0.101 | 0.061 | 0.044 | 0.034 | 0.028 | 0.024 | 0.020 |
| R-16 | 0.096 | 0.059 | 0.043 | 0.033 | 0.027 | 0.023 | 0.020 |
| R-19 | 0.082 | 0.053 | 0.040 | 0.031 | 0.026 | 0.022 | 0.020 |
| R-10 + R-10 | 0.088 | 0.056 | 0.041 | 0.032 | 0.027 | 0.023 | 0.020 |
| R-10 + R-11 | 0.086 | 0.055 | 0.041 | 0.032 | 0.027 | 0.023 | 0.020 |
| R-11 + R-11 | 0.085 | 0.055 | 0.040 | 0.032 | 0.026 | 0.023 | 0.020 |
| R-10 + R-13 | 0.084 | 0.054 | 0.040 | 0.032 | 0.026 | 0.023 | 0.020 |
Double | R-11 + R-13 | 0.082 | 0.053 | 0.040 | 0.032 | 0.026 | 0.022 | 0.020 |
Layer | R-13 + R-13 | 0.075 | 0.050 | 0.038 | 0.030 | 0.025 | 0.022 | 0.019 |
| R-10 + R-19 | 0.074 | 0.050 | 0.038 | 0.030 | 0.025 | 0.022 | 0.019 |
| R-11 + R-19 | 0.072 | 0.049 | 0.037 | 0.030 | 0.025 | 0.022 | 0.019 |
| R-13 + R-19 | 0.068 | 0.047 | 0.036 | 0.029 | 0.025 | 0.021 | 0.019 |
| R-16 + R-19 | 0.065 | 0.046 | 0.035 | 0.029 | 0.024 | 0.021 | 0.018 |
| R-19 + R-19 | 0.060 | 0.043 | 0.034 | 0.028 | 0.023 | 0.020 | 0.018 |
Liner | R-19 + R-11 | 0.035 | | | | | | |
System | R-25 + R-11 | 0.031 | | | | | | |
| R-30 + R-11 | 0.029 | | | | | | |
| R-25 + R-11 + R-11 | 0.026 | | | | | | |
Filled Cavity with Thermal Spacer Blocksc |
| R-10 + R-19 | 0.057 | 0.042 | 0.033 | 0.027 | 0.023 | 0.020 | 0.018 |
Standing Seam Roofs without Thermal Spacer Blocks |
Liner System | R-19 + R-11 | 0.040 | | | | | | |
Thru-Fastened Roofs without Thermal Spacer Blocks |
Single | R-10 | 0.184 | | | | | | |
Layer | R-11 | 0.182 | | | | | | |
| R-13 | 0.174 | | | | | | |
| R-16 | 0.157 | | | | | | |
| R-19 | 0.151 | | | | | | |
Liner System | R-19 + R-11 | 0.044 | | | | | | |
| (Multiple R-values are listed in order from inside to outside) |
a | A standing seam roof clip that provides a minimum 1.5 inch distance between the top of the purlins and the underside of the metal roof panels is required. |
b | A minimum R-3 thermal spacer block is required. |
c | A minimum R-5 thermal spacer block is required. |