Where: | | |
Annual carbon emissions from energy consumption of the building HVAC systems | = | sum of the annual carbon emissions in pounds for heating, cooling, fans, energy recovery, pumps, and heat rejection calculated by multiplying site energy consumption by the carbon emission factors from Table C407.1 |
Annual heating and cooling load | = | sum of the annual heating and cooling loads met by the building HVAC system in thousands of Btus. |
Table C407.1 (Reprinted from Chapter 4)
Carbon Emissions Factors
Type | CO2e (lb/unit) | Unit |
Electricity | 0.70 | kWh |
Natural gas | 11.70 | Therm |
Oil | 19.2 | Gallon |
Propane | 10.5 | Gallon |
Othera | 195.00 | mmBtu |
On-site renewable energy | 0.00 | |
a | District energy systems may use alternative emissions factors supported by calculations approved by the code official. |
D300 Simulation program.
D301 General.
D302 Calculation of the HVAC TSPR for the Standard Reference Design. The simulation program shall calculate the HVAC TSPR based only on the input for the proposed design and the requirements of this appendix. The calculation procedure shall not allow the user to directly modify the building component characteristics of the standard reference design.
D303 Specific approval. Performance analysis tools meeting the applicable subsections of Appendix D and tested according to ASHRAE Standard 140 shall be permitted to be approved. Tools are permitted to be approved based on meeting a specified threshold for a jurisdiction. The code official shall be permitted to approve tools for a specified application or limited scope.
D400 Climatic data. The simulation program shall perform the simulation using hourly values of climatic data, such as temperature and humidity, using TMY3 data for the site as specified here: https://buildingenergyscore.energy.gov/resources
D500 Documentation. Documentation conforming to the provisions of this section shall be provided to the code official.
D501 Compliance report. Building permit submittals shall include:
1. A report produced by the simulation software that includes the following:
1.1 Address of the building.
1.2 Name of individual completing the compliance report.
1.3 Name and version of the compliance software tool.
1.4 The dimensions, floor heights and number of floors for each block.
1.5 By block, the U-factor, C-factor, or F-factor for each simulated opaque envelope component and the U-factor and SHGC for each fenestration component.
1.6 By block or by surface for each block, the fenestration area.
1.7 By block, a list of the HVAC equipment simulated in the proposed design including the equipment type, fuel type, equipment efficiencies and system controls.
1.8 The HVAC total system performance ratio for both the standard reference design and the proposed design.
2. A mapping of the actual building HVAC component characteristics and those simulated in the proposed design showing how individual pieces of HVAC equipment identified above have been combined into average inputs as required by Section D601.11 including:
2.1 Fans.
2.2 Hydronic pumps.
2.3 Air handlers.
2.4 Packaged cooling equipment.
2.5 Furnaces.
2.6 Heat pumps.
2.7 Boilers.
2.8 Chillers.
2.9 Cooling towers.
2.10 Electric resistance coils.
2.11 Condensing units.
2.12 Motors for fans and pumps.
2.13 Energy recovery devices.
For each piece of equipment identified above, include the following as applicable:
2.14 Equipment name or tag consistent with that found on the design documents.
2.15 Efficiency level.
2.16 Capacity.
2.17 Input power for fans and pumps.
3. Floor plan of the building identifying how portions of the building are assigned to the simulated blocks and areas of the building that are not covered under the requirements of Section C403.1.1.
D600 Calculation procedure. Except as specified by this appendix, the standard reference design and proposed design shall be configured and analyzed using identical methods and techniques.
D601 Simulation of the proposed building design. The proposed design shall be configured and analyzed as specified in this section.
D601.1 Utility rates. For the purpose of calculating the HVAC TSPR the following simple utility rate determined by the Washington state department of commerce shall be used:
$0.112/kWh of electricity.
$1.158/therm of fossil fuel.
D601.2 Block geometry. The geometry of buildings shall be configured using one or more blocks. Each block shall define attributes including block dimensions, number of floors, floor to floor height and floor to ceiling height. Simulation software may allow the use of simplified shapes (such as rectangle, L shape, H shape, U shape or T shape) to represent blocks. Where actual building shape does not match these predefined shapes, simplifications are permitted providing the following requirements are met:
1. The conditioned floor area and volume of each block shall match the proposed design within 10 percent.
2. The area of each exterior envelope component from Table C402.1.4 is accounted for within 10 percent of the actual design.
3. The area of vertical fenestration and skylights is accounted for within 10 percent of the actual design.
4. The orientation of each component in 2 and 3 above is accounted for within 45 degrees of the actual design.
The creation of additional blocks may be necessary to meet these requirements.
EXCEPTION: | Portions of the building that are unconditioned or served by systems not covered by the requirements of Section C403.1.1 shall be omitted. |
D601.2.1 Number of blocks. One or more blocks may be required per building based on the following restrictions:
1. Each block can have only one occupancy type (office, library, education or retail). Therefore, at least one single block shall be created for each unique use type.
2. Each block can be served by only one type of HVAC system. Therefore, a single block shall be created for each unique HVAC system and use type combination. Multiple HVAC units of the same type may be represented in one block. Table D601.10.2 provides directions for combining multiple HVAC units or components of the same type into a single block.
3. Each block can have a single definition of floor to floor or floor to ceiling heights. Where floor heights differ by more than 2 feet, unique blocks should be created for the floors with varying heights.
4. Each block can include either above grade or below grade floors. For buildings with both above grade and below grade floors, separate blocks should be created for each. For buildings with floors partially above grade and partially below grade, if the total wall area of the floor(s) in consideration is greater than or equal to 50 percent above grade, then it should be simulated as a completely above grade block, otherwise it should be simulated as a below grade block.
5. Each wall on a façade of a block shall have similar vertical fenestration. The product of the proposed designU-factor times the area of windows (UA) on each façade of a given floor cannot differ by more than 15 percent of the average UA for that façade in each block. The product of the proposed design SHGC times the area of windows (USHGC) on each façade of a given floor cannot differ by more than 15 percent of the average USHGC for that façade in each block. If either of these conditions are not met, additional blocks shall be created consisting of floors with similar fenestration.
6. For a building model with multiple blocks, the blocks should be configured together to have the same adjacencies as the actual building design.
D601.3 Thermal zoning. Each floor in a block shall be modeled as a single thermal zone or as five thermal zones consisting of four perimeter zones and a core zone. Below grade floors shall be modeled as a single thermal block. If any façade in the block is less than 45 feet in length, there shall only be a single thermal zone per floor. Otherwise each floor shall be modeled with 5 thermal zones. A perimeter zone shall be created extending from each façade to a depth of 15 feet. Where facades intersect, the zone boundary shall be formed by a 45 degree angle with the 2 facades. The remaining area or each floor shall be modeled as a core zone with no exterior walls.
D601.4 Occupancy.
D601.4.1 Occupancy type. The occupancy type for each block shall be consistent with the building area type as determined in accordance with Section C405.4.2.1. Portions of the building that are building area types other than office, school (education), library, or retail shall not be included in the simulation.
D601.4.2 Occupancy schedule, density, and heat gain. The occupant density, heat gain, and schedule shall be for office, retail, library, or school as specified by ASHRAE Standard 90.1 Normative Appendix C.
D601.5 Envelope components.
D601.5.1 Roofs. Roofs will be modeled with insulation above a steel roof deck. The roof U-factor and area shall be modeled as in the proposed design. If different roof thermal properties are present in a single block, an area weighted U-factor shall be used. Roof solar absorbtance shall be modeled at 0.70 and emittance at 0.90.
D601.5.2 Above grade walls. Walls will be modeled as steel frame construction. The U-factor and area of above grade walls shall be modeled as in the proposed design. If different wall constructions exist on the façade of a block an area-weighted U-factor shall be used.
D601.5.3 Below grade walls. The C-factor and area of below grade walls shall be modeled as in the proposed design. If different slab on grade floor constructions exist in a block, an area-weighted C-factor shall be used.
D601.5.4 Above grade exterior floors. Exterior floors shall be modeled as steel frame. The U-factor and area of floors shall be modeled as in the proposed design. If different wall constructions exist in the block an area-weighted U-factor shall be used.
D601.5.5 Slab on grade floors. The F-factor and area of slab on grade floors shall be modeled as in the proposed design. If different below grade wall constructions exist in a block, an area-weighted F-factor shall be used.
D601.5.6 Vertical fenestration. The window area and area weighted U-factor and SHGC shall be modeled for each façade based on the proposed design. Each exterior surface in a block must comply with Section D601.2.1 item 5. Windows will be combined in to a single window centered on each façade based on the area and sill height input by the user.
D601.5.7 Skylights. The skylight area and area weighted U-factor and SHGC shall be modeled for each floor based the proposed design. Skylights will be combined in to a single skylight centered on the roof of each zone based on the area and sill height input by the user.
D601.6 Lighting. Interior lighting power density shall be equal to the allowance in Table C405.4.2(1) for office, retail, library, or school. The lighting schedule shall be for office, retail, library, or school as specified by ASHRAE Standard 90.1 Normative Appendix C. The impact of lighting controls is assumed to be captured by the lighting schedule and no explicit controls shall be modeled. Exterior lighting shall not be modeled.
D601.7 Miscellaneous equipment. The miscellaneous equipment schedule and power shall be for office, retail, library, or school as specified by ASHRAE Standard 90.1 Normative Appendix C. The impact of miscellaneous equipment controls is assumed to be captured by the equipment schedule and no explicit controls shall be modeled.
D601.8 Elevators. Elevators shall not be modeled.
D601.9 Service water heating equipment. Service water heating shall not be modeled.
D601.10 On-site renewable energy systems. On-site renewable energy systems shall not be modeled.
D601.11 HVAC equipment. HVAC systems shall meet the requirements of Section C403.
D601.11.1 Supported HVAC systems. At a minimum, the HVAC systems shown in Table D601.11.1 shall be supported by the simulation program.
Table D601.11.1
Proposed Building HVAC Systems Supported by HVAC TSPR Simulation Software
System No. | System Name | System Abbreviation |
1 | Packaged Terminal Air Conditioner | PTAC |
2 | Packaged Terminal Air Heat Pump | PTHP |
3 | Packaged Single Zone Gas Furnace | PSZGF |
4 | Packaged Single Zone Heat Pump (air to air only) | PSZHP |
5 | Variable Refrigerant Flow (air cooled only) | VRF |
6 | Four Pipe Fan Coil | FPFC |
7 | Water Source Heat Pump | WSHP |
8 | Ground Source Heat Pump | GSHP |
9 | Packaged Variable Air Volume (dx cooling) | PVAV |
10 | Variable Air Volume (hydronic cooling) | VAV |
11 | Variable Air Volume with Fan Powered Terminal Units | VAVFPTU |
12 | Dedicated Outdoor Air System (in conjunction with systems 1-8) | DOAS |
D601.11.2 Proposed building HVAC system simulation. The HVAC systems shall be modeled as in the proposed design with clarifications and simplifications as described in Table D601.11.2. System parameters not described in the following sections shall be simulated to meet the minimum requirements of Section C403. All zones within a block shall be served by the same HVAC system type as described in Section D601.2.1 item 2. Where multiple system components serve a block, average values weighed by the appropriate metric as described in this section shall be used. Heat loss from ducts and pipes shall not be modeled.
EXCEPTION: | Where the building permit applies to only a portion of an HVAC system and remaining components will be designed under a future building permit, the future components shall be modeled to meet, but not exceed, the requirements of Section C403. |
Table D601.11.2
Proposed Building System Parameters
Category | Parameter | Fixed or User Defined | Required | Applicable Systems |
HVAC System Type | System Type | User Defined | Selected from Table D601.11.1 | All |
System Sizing | Design Day Information | Fixed | 99.6 percent heating design and 1 percent dry-bulb and 1 percent wet-bulb cooling design | All |
Zone Coil Capacity | Fixed | Sizing factors used are 1.25 for heating equipment and 1.15 for cooling equipment | All |
Supply Airflow | Fixed | Based on a supply-air-to-room-air temperature set-point difference of 20°F | 1-11 |
Fixed | Equal to required outdoor air ventilation | 12 |
Outdoor Ventilation Air | Outdoor Ventilation Air Flow Rate | Fixed | As specified in ASHRAE Standard 90.1 Normative Appendix C, adjusted for proposed DCV control | All |
System Operation | Space Temperature Setpoints | Fixed | As specified in ASHRAE Standard 90.1 Normative Appendix C | 1-11 |
Fan Operation - Occupied | User Defined | Runs continuously during occupied hours or cycled to meet load | 1-11 |
Fan Operation - Occupied | Fixed | Fan runs continuously during occupied hours | 12 |
Fan Operation -Night Cycle | Fixed | Fan cycles on to meet setback temperatures | 1-11 |
Packaged Equipment Efficiency | DX Cooling Efficiency | User Defined | Cooling COP without fan energy calculated in accordance with ASHRAE Standard 90.1 Section 11.5.2c.b | 1, 2, 3, 4, 5, 7, 8, 9, 11, 12 |
Heat Pump Efficiency | User Defined | Heating COP without fan energy calculated in accordance with ASHRAE Standard 90.1 Section 11.5.2c.c | 2, 4, 5, 7, 8 |
Furnace Efficiency | User Defined | Furnace thermal efficiencyc | 3, 11 |
Heat Pump Supplemental Heat | Control | Fixed | Supplemental electric heat locked out above 40°F. Runs in conjunction with compressor between 40°F and 0°F. | 2, 4 |
System Fan Power | Design Fan Power (W/cfm) | User Defined | Input electric power for all fans is required to operate at fan system design conditions divided by the supply airflow rate | All |
Single Zone System Fan Power During Deadband (W/cfm) | User Defined | W/cfm during deadband for VAV or multispeed single zone fans | 3, 4, 5, 6, 7, 8 |
Variable Air Volume Systems | Part Load Fan Controls | User Defined | VFD included. User specifies presence of static pressure reset | 9, 10, 11 |
Supply Air Temperature Controls | User Defined | If not SAT reset constant at 55°F. SAT reset results in 60°F SAT during low load conditions | 9, 10, 11 |
Minimum Terminal Unit Airflow Percentage | User Defined | Average minimum terminal unit airflow percentage for block weighted by cfm | 9, 10, 11 |
Terminal Unit Heating Source | User Defined | Electric or hydronic | 9, 10, 11 |
Fan Powered Terminal Unit (FPTU) Type | User Defined | Series or parallel FPTU | 11 |
Parallel FPTU Fan | Fixed | Sized for 50 percent peak primary air at 0.35 W/cfm | 11 |
Series FPTU Fan | Fixed | Sized for 50 percent peak primary air at 0.35 W/cfm | 11 |
Economizer | Economizer Presence | User Defined | Yes or No | 3, 4, 9, 10, 11 |
Economizer High Limit | Fixed | 75°F fixed dry-bulb | 3, 4, 9, 10, 11 |
Energy Recovery | Sensible Effectiveness | User Defined | Heat exchanger sensible effectiveness at design heating and cooling conditions | 3, 4, 9, 10, 11, 12 |
Latent Effectiveness | User Defined | Heat exchanger latent effectiveness at design heating and cooling conditions | 3, 4, 9, 10, 11, 12 |
Economizer Bypass | User Defined | If ERV is bypassed during economizer conditions | 3, 4, 9, 10, 11, 12 |
Energy Recovery Temp Control | User Defined | If bypass, target supply air temperature | 3, 4, 9, 10, 11, 12 |
Fan Power Reduction during Bypass (W/cfm) | User Defined | If ERV system include bypass, static pressure setpoint and variable speed fan, fan power can be reduced during economizer conditions | 3, 4, 9, 10, 11, 12 |
Demand Controlled Ventilation | DCV Application | User Defined | Percent of block floor area under DCV control | 3, 4, 9, 10, 11, 12 |
DOAS | DOAS Fan Power W/cfm | User Defined | Fan input power in W/cfm of supply airflowa | 12 |
DOAS Supplemental Heating and Cooling | User Defined | Heating source, cooling source | 12 |
DOAS Supply Air Temperature Control | User Defined | SAT setpoint if DOAS includes supplemental heating or cooling and active temperature controls | 12 |
Heating Plant | Boiler Efficiencyd | User Defined | Boiler thermal efficiency | 1, 6, 7, 9, 10, 11, 12 |
Heating Water Pump Power (W/gpm) | User Defined | Pump input W/gpm heating water flow | 1, 6, 7, 9, 10, 11, 12 |
Heating Water Loop Temperature | Fixed | 180°F supply, 130°F return | 1, 6, 9, 10,11 |
Chilled Water Plant | Chiller Compressor Type | User Defined | Screw/scroll, centrifugal or reciprocating | 6,10, 11, 12 |
Chiller Condenser Type | User Defined | Air cooled or water cooled | 6, 10, 11, 12 |
Chiller Full Load Efficiencyd | User Defined | Chiller COP | 6, 10, 11, 12 |
Chilled Water Loop Configuration | User Defined | Variable flow primary only, constant flow primary - variable flow secondary | 6, 10, 11, 12 |
Chilled Water Pump Power (W/gpm) | User Defined | Pump input W/gpm chilled water flow | 6, 10, 11, 12 |
Chilled Water Temperature Reset Included | User Defined | Yes/No | 6, 10, 11, 12 |
Chilled Water Temperature Reset Schedule (if included) | Fixed | Outdoor air reset: CHW supply temperature of 44°F at 80°F outdoor air dry-bulb and above, CHW supply temperature of 54°F at 60°F outdoor air dry-bulb temperature and below, ramped linearly between | 6, 10, 11, 12 |
Condenser Water Pump Power (W/gpm) | User Defined | Pump input W/gpm condenser water flow | 6, 7, 8, 9, 10, 11, 12 |
Condenser Water Pump Control | User Defined | Constant speed or variable speed | 6, 7, 10, 11, 12 |
Cooling Tower Efficiency | User Defined | gpm/hp tower fan | 6, 10, 11, 12 |
Cooling Tower | Cooling Tower Fan Control | User Defined | Constant or variable speed | 6, 10, 11, 12 |
Cooling Tower Approach and Range | User Defined | Design cooling tower approach and range temperature | 6, 10, 11, 12 |
Heat Pump Loop Flow Control | Loop Flow and Heat Pump Control Valve | Fixed | Two position valve with VFD on pump. Loop flow at 3 gpm/ton | 7, 8 |
Heat Pump Loop Temperature Control | | Fixed | Set to maintain temperature between 50°F and 70°F | 7 |
GLHP Well Field | | Fixed | Bore depth = 250 feet Bore length 200 feet/ton for greater of cooling or heating load Bore spacing = 15 feet Bore diameter = 5 inches 3/4 inch Polyethylene pipe Ground and grout conductivity = 4.8 Btu-in/h-ft2-°F | 8 |
a Where multiple fan systems serve a single block, fan power is based on weighted average using on supply air cfm.
b Where multiple cooling systems serve a single block, COP is based on a weighted average using cooling capacity.
c Where multiple heating systems serve a single block, thermal efficiency or heating COP is based on a weighted average using heating capacity.
d Where multiple boilers or chillers serve a heating water or chilled water loop, efficiency is based on a weighted average for using heating or cooling capacity.
D602 Simulation of the standard reference design. The standard reference design shall be configured and analyzed as specified in this section.
D602.1 Utility rates. Same as proposed.
D602.2 Blocks. Same as proposed.
D602.3 Thermal zoning. Same as proposed.
D602.4 Occupancy type, schedule, density, and heat gain. Same as proposed.
D602.5 Envelope components. Same as proposed.
D602.6 Lighting. Same as proposed.
D602.7 Miscellaneous equipment. Same as proposed.
D602.8 Elevators. Not modeled. Same as proposed.
D602.9 Service water heating equipment. Not modeled. Same as proposed.
D602.10 On-site renewable energy systems. Not modeled. Same as proposed.
D602.11 HVAC equipment. The standard reference design HVAC equipment consists of separate space conditioning systems and dedicated outside air systems as described in Table D602.11 for the appropriate building occupancies.
Table D602.11
Standard Reference Design HVAC Systems
Parameter | Building Type |
Large Officea | Small Office and Librariesa | Retail | School |
System Type | Water-source Heat Pump | Packaged air-source Heat Pump | Packaged air-source Heat Pump | Packaged air-source Heat Pump |
Fan Controlb | Cycle on Load | Cycle on Load | Cycle on Load | Cycle on Load |
Space Condition Fan Power (W/cfm) | 0.528 | 0.528 | 0.522 | 0.528 |
Heating/Cooling Sizing Factorc | 1.25/1.15 | 1.25/1.15 | 1.25/1.15 | 1.25/1.15 |
Supplemental Heating Availability | NA | <40°F | <40°F | <40°F |
Modeled cooling COP (Net of Fan) d | 4.46 | 3.83 | 4.25 | 3.83 |
Modeled heating COP (Net of Fan) d | 4.61 | 3.81 | 3.57 | 3.81 |
Cooling Source | DX (Heat Pump) | DX (Heat Pump) | DX (Heat Pump) | DX (Heat Pump) |
Heat Source | Heat Pump | Heat Pump | Heat Pump | Heat Pump |
OSA Economizere | No | No | Yes | Yes |
Occupied Ventilation Sourcef | DOAS | DOAS | DOAS | DOAS |
DOAS Fan Power (W/cfm of Outside Air) | 0.819 | 0.819 | 0.730 | 0.742 |
DOAS Temperature Control g, h | Bypass | Wild | Bypass | Bypass |
ERV Efficiency (Sensible Only) | 70 percent | 70 percent | 70 percent | 70 percent |
WSHP Loop Heat Rejection | Cooling Toweri | NA | NA | NA |
WSHP Loop Heat Source | Gas Boiler j | NA | NA | NA |
WSHP Loop Temperature Controlk | 50°F to 70°F | NA | NA | NA |
WSHP Circulation Pump W/gpml | 16 | NA | NA | NA |
WSHP Loop Pumping Controlm | HP Valves & Pump VSD | NA | NA | NA |
a Offices less than 50,000 square feet use "Small Office" parameters; otherwise use "Large Office" parameters.
b Space conditioning system shall cycle on to meet heating and cooling setpoint schedules as specified in ASHRAE Standard 90.1 Normative Appendix C. One space conditioning system is modeled in each zone. Conditioning system fan operation is not necessary for ventilation delivery.
c The equipment capacities (i.e., system coil capacities) for the standard reference design building design shall be based on design day sizing runs and shall be oversized by 15 percent for cooling and 25 percent for heating.
d COPs shown are direct heating or cooling performance and do not include fan energy use. See ASHRAE 90.1 Appendix G (G3.1.2.1) for separation of fan from COP in packaged equipment for units where the efficiency rating includes fan energy (e.g., SEER, EER, HSPF, COP).
e Economizer on space conditioning systems shall be simulated when outdoor air conditions allow free cooling. Economizer high limit shall be based on differential dry-bulb control. DOAS system continues to operate during economizer mode.
f Airflow equal to the outside air ventilation requirements is supplied and exhausted through a separate DOAS system including a supply fan, exhaust fan and sensible only heat exchanger. No additional heating or cooling shall be provided by the DOAS. A single DOAS system will be provided for each block. The DOAS supply and return fans shall run whenever the HVAC system is scheduled to operate in accordance with ASHRAE 90.1 Normative Appendix C.
g "Wild" DOAS control indicates no active control of the supply air temperature leaving the DOAS system. Temperature will fluctuate based only on entering and leaving conditions and the effectiveness of ERV.
h "Bypass" DOAS control includes modulating dampers to bypass ERV with the intent to maintain supply air temperature at a maximum of 60°F when outside air is below 75°F. Once outside air is above 75°F, bypass dampers will be fully closed.
i Includes a single axial fan cooling tower with variable speed fans at 40.2 gpm/hp, sized for an approach of 10°F and a range of 10°F.
j Includes a single natural draft boiler with 80 percent Et.
k Loop boiler and heat rejection shall be controlled to maintain loop temperature entering heat pumps between 50°F and 70°F.
l Pump motor input power shall be 16 W/gpm.
m Loop flow shall be variable with variable speed drive pump and unit fluid flow shutoff at each heat pump when its compressor cycles off.
[Statutory Authority: RCW
19.27A.025,
19.27A.045 and chapter
19.27 RCW. WSR 20-21-080, § 51-11C-80500, filed 10/19/20, effective 2/1/21. Statutory Authority: RCW
19.27A.020,
19.27A.025,
19.27A.160 and chapter
19.27 RCW. WSR 19-24-040, § 51-11C-80500, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW
19.27A.025,
19.27A.160, and
19.27.074. WSR 16-03-072, § 51-11C-80500, filed 1/19/16, effective 7/1/16.]