EXCEPTION: | Cooling coils that are designed, controlled and operated to provide sensible cooling only do not require filtration at the terminal device. |
605.4 Particulate matter removal. Particulate matter filters or air cleaners having a minimum efficiency reporting value (MERV) of not less than 6 for ducted air handlers and not less than 4 for ductless mini-split systems shall be provided upstream of all cooling coils or other devices with wetted surfaces through which air is supplied to an occupiable space.