(1) The adult family home must have an approved five pound 2A:10B-C rated fire extinguisher on each floor of the home.
(2) The home must ensure fire extinguishers are:
(a) Mounted or securely fastened in a stationary position at a minimum of four inches from the floor and a maximum of sixty inches from the floor;
(b) Inspected and serviced annually;
(c) In proper working order;
(d) Accessible at all times; and
(e) Not located behind a locked door.