Equipment Type | Net Sensible Cooling Capacity | Standard Model | Minimum Net Sensible COPc | Test Procedure |
Return Air Dry-Bulb Temperature/Dew-Point Temperature |
Class 1 | Class 2 | Class 3 |
75°F/52°F | 85°F/52°F | 95°F/52°F |
Air cooled | < 65,000 Btu/h | Downflow unit | | 2.30 | | AHRI 1360 |
Upflow unit - Ducted | | 2.10 | |
Upflow unit - Unducted | 2.09 | | |
Horizontal-flow unit | | | 2.45 |
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | | 2.20 | |
Upflow unit - Ducted | | 2.05 | |
Upflow unit - Unducted | 1.99 | | |
Horizontal-flow unit | | | 2.35 |
≥ 240,000 Btu/h | Downflow unit | | 2.00 | |
Upflow unit - Ducted | | 1.85 | |
Upflow unit - Unducted | 1.79 | | |
Horizontal-flow unit | | | 2.15 |
Water cooled | < 65,000 Btu/h | Downflow unit | | 2.50 | | AHRI 1360 |
Upflow unit - Ducted | | 2.30 | |
Upflow unit - Unducted | 2.25 | | |
Horizontal-flow unit | | | 2.70 |
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | | 2.40 | |
Upflow unit - Ducted | | 2.20 | |
Upflow unit - Unducted | 2.15 | | |
Horizontal-flow unit | | | 2.60 |
≥ 240,000 Btu/h | Downflow unit | | 2.25 | |
Upflow unit - Ducted | | 2.10 | |
Upflow unit - Unducted | 2.05 | | |
Horizontal-flow unit | | | 2.45 |
Water cooled with fluid economizer | < 65,000 Btu/h | Downflow unit | | 2.45 | | AHRI 1360 |
Upflow unit - Ducted | | 2.25 | |
Upflow unit - Unducted | 2.20 | | |
Horizontal-flow unit | | | 2.60 |
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | | 2.35 | |
Upflow unit - Ducted | | 2.15 | |
Upflow unit - Unducted | 2.10 | | |
Horizontal-flow unit | | | 2.55 |
≥ 240,000 Btu/h | Downflow unit | | 2.20 | |
Upflow unit - Ducted | | 2.05 | |
Upflow unit - Unducted | 2.00 | | |
Horizontal-flow unit | | | 2.40 |
Glycol cooled | < 65,000 Btu/h | Downflow unit | | 2.30 | | AHRI 1360 |
Upflow unit - Ducted | | 2.10 | |
Upflow unit - Unducted | 2.00 | | |
Horizontal-flow unit | | | 2.40 |
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | | 2.05 | |
Upflow unit - Ducted | | 1.85 | |
Upflow unit - Unducted | 1.85 | | |
Horizontal-flow unit | | | 2.15 |
≥ 240,000 Btu/h | Downflow unit | | 1.95 | |
Upflow unit - Ducted | | 1.80 | |
Upflow unit - Unducted | 1.75 | | |
Horizontal-flow unit | | | 2.10 |
Glycol cooled with fluid economizer | < 65,000 Btu/h | Downflow unit | | 2.25 | | AHRI 1360 |
Upflow unit - Ducted | | 2.10 | |
Upflow unit - Unducted | 2.00 | | |
Horizontal-flow unit | | | 2.35 |
≥ 65,000 Btu/h and < 240,000 Btu/h | Downflow unit | | 1.95 | |
Upflow unit - Ducted | | 1.80 | |
Upflow unit - Unducted | 1.75 | | |
Horizontal-flow unit | | | 2.10 |
≥ 240,000 Btu/h | Downflow unit | | 1.90 | |
Upflow unit - Ducted | | 1.80 | |
Upflow unit - Unducted | 1.70 | | |
Horizontal-flow unit | | | 2.10 |
Table C403.3.2(10)
Minimum Efficiency Requirements—Heat Transfer Equipment
Equipment Type | Subcategory | Minimum Efficiency | Test Procedurea |
Liquid-to-liquid heat exchangers | Plate type | NR | AHRI 400 |
NR = No requirement. |
a | Chapter 12 of the referenced standard contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. |
Table C403.3.2(11)
Minimum Efficiency Requirements: Electrically Operated DX-DOAS Units, Single-package and Remote Condenser, Without Energy Recovery
EQUIPMENT TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDURE |
Air cooled (dehumidification mode) | | 4.0 ISMRE | AHRI 920 |
Air source heat pumps (dehumidification mode) | | 4.0 ISMRE | AHRI 920 |
Water cooled (dehumidification mode) | Cooling tower condenser water | 4.9 ISMRE | AHRI 920 |
Chilled water | 6.0 ISMRE |
Air source heat pump (heating mode) | | 2.7 ISCOP | AHRI 920 |
Water source heat pump (dehumidification mode) | Ground source, closed loop | 4.8 ISMRE | AHRI 920 |
Ground-water source | 5.0 ISMRE |
Water source | 4.0 ISMRE |
Water source heat pump (heating mode) | Ground source, closed loop | 2.0 ISCOP | AHRI 920 |
Ground-water source | 3.2 ISCOP |
Water source | 3.5 ISCOP |
Table C403.3.2(12)
Minimum Efficiency Requirements: Electrically Operated DX-DOAS Units, Single-package and Remote Condenser, with Energy Recovery
EQUIPMENT TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDURE |
Air cooled (dehumidification mode) | | 5.2 ISMRE | AHRI 920 |
Air source heat pumps (dehumidification mode) | | 5.2 ISMRE | AHRI 920 |
Water cooled (dehumidification mode) | Cooling tower condenser water | 5.3 ISMRE | AHRI 920 |
Chilled water | 6.6 ISMRE |
Air source heat pump (heating mode) | | 3.3 ISCOP | AHRI 920 |
Water source heat pump (dehumidification mode) | Ground source, closed loop | 5.2 ISMRE | AHRI 920 |
Ground-water source | 5.8 ISMRE |
Water source | 4.8 ISMRE |
Water source heat pump (heating mode) | Ground source, closed loop | 3.8 ISCOP | AHRI 920 |
Ground-water source | 4.0 ISCOP |
Water source | 4.8 ISCOP |
[Statutory Authority: RCW
19.27A.020,
19.27A.025,
19.27A.160 and chapter
19.27 RCW. WSR 19-24-040, § 51-11C-403239, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW
19.27A.025,
19.27A.160, and
19.27.074. WSR 16-03-072, § 51-11C-403239, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW
19.27A.020,
19.27A.025 and chapters
19.27 and
34.05 RCW. WSR 13-04-056, § 51-11C-403239, filed 2/1/13, effective 7/1/13.]