For SI: 1 British thermal unit per hour = 0.2931 W. | ||||
a | Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure. | |||
b | These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers. | |||
c | Ec | = | Combustion efficiency (100 percent less flue losses). | |
d | Et | = | Thermal efficiency. | |
e | Maximum capacity – Minimum and maximum ratings as provided for and allowed by the unit's controls. | |||
f | Includes oil-fired (residual). | |||
g | Boilers shall not be equipped with a constant burning pilot light. | |||
h | A boiler not equipped with a tankless domestic water heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied. | |||
i | This table is a replica of ASHRAE 90.1 Table 6.8.1-6 Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements. |