Type of Hood | Light-duty Equipment | Medium-duty Equipment | Heavy-duty Equipment | Extra-heavy-duty Equipment |
Wall-mounted canopy | 140 | 210 | 280 | 385 |
Single island | 280 | 350 | 420 | 490 |
Double island (per side) | 175 | 210 | 280 | 385 |
Eyebrow | 175 | 175 | NA | NA |
Backshelf/pass-over | 210 | 210 | 280 | NA |
For SI: | 1 cfm = 0.4719 L/s; 1 foot = 305 mm |
NA = Not allowed |
EXCEPTIONS: | 1. Where not less than 75 percent of all the replacement air is transfer air that would otherwise be exhausted. |
2. UL 710 listed exhaust hoods that have a design maximum exhaust airflow rate no greater than 250 cfm per linear foot of hood that serve kitchen or kitchen/dining facilities with a total kitchen hood exhaust airflow rate less than 5000 cfm. | |
3. Type II dishwasher exhaust hoods that have an exhaust airflow of 1000 cfm or less. |
EXCEPTIONS: | 1. Variable air volume laboratory exhaust and room supply systems configured to reduce exhaust and makeup air volume to 50 percent or less of design values; or |
2. Direct makeup (auxiliary) air supply equal to at least 75 percent of the exhaust rate, heated no warmer than 2°F (1.1°C) below room setpoint, cooled to no cooler than 3°F (1.7°C) above room setpoint, no humidification added, and no simultaneous heating and cooling used for dehumidification control; or | |
3. Combined energy reduction method: VAV exhaust and room supply system configured to reduce exhaust and makeup air volumes and a heat recovery system to precondition makeup air from laboratory exhaust that when combined will produce the same energy reduction as achieved by a heat recovery system with a 50 percent sensible recovery effectiveness as required above. For calculation purposes, the heat recovery component can be assumed to include the maximum design supply airflow rate at design conditions. The combined energy reduction (QER) shall meet the following: |
QER | ≥ | QMIN | |
QMIN | = | CFMS • (TR - TO) • 1.1 • 0.6 | |
QER | = | CFMS • (TR - TO) • 1.1(A + B)/100 | |
Where: | |||
QMIN | = | Energy recovery at 60 percent sensible effectiveness (Btu/h) | |
QER | = | Combined energy reduction (Btu/h) | |
CFMS | = | The maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute | |
TR | = | Space return air dry-bulb at winter design conditions | |
TO | = | Outdoor air dry-bulb at winter design conditions | |
A | = | Percentage that the exhaust and makeup air volumes can be reduced from design conditions | |
B | = | Percentage sensible heat recovery effectiveness |
EXCEPTIONS: | 1. Laboratories classified as biosafety level 3 or higher. |
2. Vivarium spaces. | |
3. Spaces that are required by applicable codes and standards to be maintained at positive pressure relative to adjacent spaces. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. | |
4. Spaces where the demand for transfer air may exceed the available transfer airflow rate and where the spaces have a required negative pressure relationship. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. |