Duct system | Duct Location and Use | Climate Zone | Airflow | Minimum Installed Duct Insulation R-valuea,b | Notes |
Outdoor Air | Inside conditioned space and upstream of automatic shutoff damper | 4C and 5B | ≥ 2800 CFM | R-16 | See Section C403.10.1.1 for additional requirements |
Outdoor Air | Inside conditioned space and downstream of automatic shutoff damper to HVAC unit or room | 4C | ≥ 2800 CFM | R-8 | |
Outdoor Air | Inside conditioned space and downstream of automatic shutoff damper to HVAC unit or room | 5B | ≥ 2800 CFM | R-12 | |
Outdoor Air | Inside conditioned space | 4C and 5B | ≤ 2800 CFM | R-7 | See Exception 1 to Section C403.10.1.1 for additional details |
a | Insulation R-values, measured in h·ft2·°F/Btu, are for the insulation as installed and do not include film resistance. The required minimum thicknesses do not consider water vapor transmission and possible surface condensation. Insulation resistance measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75°F at the installed thickness. |
b | See International Mechanical Code Sections 603.12 and 604 for further details on duct insulation requirements. |
EXCEPTIONS: | 1. Where located within equipment. |
2. Supply and return ductwork located in unconditioned spaces where the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15°F (8°C) and are insulated in accordance with Table C403.10.1.2. |
EXCEPTION: | Ductwork exposed to view within a zone that serves that zone is not required to be insulated. |
Duct System | Duct Location and Use | Climate Zone | Minimum Installed Duct Insulation R-valuea,b | Notes |
Supply air or return air | Outside the building (outdoors and exposed to weather)c | 4C | R-8 | See Section C403.10.1.2 for details |
Supply air or return air | Outside the building (outdoors and exposed to weather)c | 5B | R-12 | See Section C403.10.1.2 for details |
Supply air or return air | Unconditioned space (enclosed but not in the building conditioned envelope) | 4C and 5B | R-6 | See Section C403.10.1.2 for details |
Supply air or return air | Unconditioned space where the duct conveys air that is within 15°F of the air temperature of the surrounding unconditioned space | 4C and 5B | R-3.3 | See IMC Section 603.12 for additional requirements for condensation control at ductwork |
Supply air or return air | Where located in a building envelope assembly | 4C and 5B | R-16 | Duct or plenum is separated from building envelope assembly with the minimum insulation value |
Supply air | Within conditioned space where the supply duct conveys air that is less than 55°F or greater than 105°F | 4C and 5B | R-3.3 | See Section C403.10.1.2 for details |
Supply air | Within conditioned space that the duct directly serves where the supply duct conveys air that is less than 55°F or greater than 105°F | 4C and 5B | None | See Section C403.10.1.2 for details |
Supply air | Within conditioned space where the supply duct conveys air that is 55°F or greater and 105°F or less | 4C and 5B | None | |
Return or exhaust air | Within conditioned space, downstream of an energy recovery media, upstream of an automatic shutoff damper | 4C | R-8 | |
Return or exhaust air | Within conditioned space, downstream of an energy recovery media, upstream of an automatic shutoff damper | 5B | R-12 | |
Relief or exhaust air | Conditioned space and downstream of an automatic shutoff damper | 4C and 5B | R-16 |
a | Insulation R-values, measured in h·ft2·°F/Btu, are for the insulation as installed and do not include film resistance. The required minimum thicknesses do not consider water vapor transmission and possible surface condensation. Insulation resistance measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75°F at the installed thickness. |
b | See International Mechanical Code Sections 603.12 and 604 for further details on duct insulation requirements. |
c | Includes attics above insulated ceilings, parking garages and crawl spaces. |
EXCEPTION: | Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2 inches water gauge (w.g.) (500 Pa) pressure classification. |
CL | F/P0.65 | |
Where: | ||
F | The measured leakage rate in cfm per 100 square feet of duct surface. | |
P | The static pressure of the test. |
EXCEPTIONS: | 1. Factory-installed piping within HVAC equipment tested and rated in accordance with a test procedure referenced by this code. |
2. Factory-installed piping within room fan-coils and unit ventilators tested and rated according to AHRI 440 (except that the sampling and variation provisions of Section 6.5 shall not apply) and 840, respectively. | |
3. Piping that conveys fluids that have a design operating temperature range between 60°F (15°C) and 105°F (41°C). | |
4. Piping that conveys fluids that have not been heated or cooled through the use of fossil fuels or electric power. | |
5. Strainers, control valves, and balancing valves associated with piping 1 inch (25 mm) or less in diameter. | |
6. Direct buried piping that conveys fluids at or below 60°F (15°C). |
Fluid Operating Temperature Range and Usage (°F) | Insulation Conductivity | Nominal Pipe or Tube Size (inches) | |||||
Conductivity Btu • in. /(h • ft2 • °F)b | Mean Rating Temperature, °F | < 1 | 1 to < 1-1/2 | 1-1/2 to < 4 | 4 to < 8 | ≥ 8 | |
˃ 350 | 0.32 - 0.34 | 250 | 4.5 | 5.0 | 5.0 | 5.0 | 5.0 |
251 - 350 | 0.29 - 0.32 | 200 | 3.0 | 4.0 | 4.5 | 4.5 | 4.5 |
201 - 250 | 0.27 - 0.30 | 150 | 2.5 | 2.5 | 2.5 | 3.0 | 3.0 |
141 - 200 | 0.25 - 0.29 | 125 | 1.5 | 1.5 | 2.0 | 2.0 | 2.0 |
105 - 140 | 0.21 - 0.28 | 100 | 1.0 | 1.0 | 1.5 | 1.5 | 1.5 |
40 - 60 | 0.21 - 0.27 | 75 | 0.5 | 0.5 | 1.0 | 1.0 | 1.0 |
< 40 | 0.20 - 0.26 | 75 | 0.5 | 1.0 | 1.0 | 1.0 | 1.5 |
a | For piping smaller than 1-1/2 inch (38 mm) and located in partitions within conditioned spaces, reduction of these thicknesses by 1 inch (25 mm) shall be permitted (before thickness adjustment required in footnote b) but not to a thickness less than 1 inch (25 mm). |
b | For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows: |
T | r{(1 + t/r)K/k - 1} | |||
Where: | ||||
T | = | Minimum insulation thickness. | ||
r | = | Actual outside radius of pipe. | ||
t | = | Insulation thickness listed in the table for applicable fluid temperature and pipe size. | ||
K | = | Conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature (Btu × in/h × ft2 × °F). | ||
k | = | The upper value of the conductivity range listed in the table for the applicable fluid temperature. |
c | For direct-buried heating and hot water system piping, reduction of these thicknesses by 1-1/2 inches (38 mm) shall be permitted (before thickness adjustment required in footnote b but not to thicknesses less than 1 inch (25 mm). |