EXCEPTION: | Tubular pipe insulation shall not be required on the following: |
| 1. The tubing from the connection at the termination of the fixture supply piping to a plumbing fixture or plumbing appliance. |
| 2. Valves, pumps, strainers and threaded unions in piping that is 1 inch (25 mm) or less in nominal diameter. |
| 3. Piping from user-controlled shower and bath mixing valves to the water outlets. |
| 4. Cold-water piping of a demand recirculation water system. |
| 5. Tubing from a hot drinking-water heating unit to the water outlet. |
| 6. Piping at locations where a vertical support of the piping is installed. |
| 7. Piping surrounded by building insulation with a thermal resistance (R-value) of not less than R-3. |
| 8. Hot water piping that is part of the final pipe run to the plumbing fixture and is not part of the heated-water circulation system circulation path is not required to meet the minimum insulation requirements of Section C404.6. |