EXCEPTIONS: | 1. Motors that are an integral part of specialized process equipment. |
2. Where the motor is integral to a listed piece of equipment for which no complying motor has been approved. | |
3. Motors used as a component of the equipment meeting the minimum efficiency requirements of Section C403.3.2 and Tables C403.3.2(1) through C403.3.2(12) provided that the motor input is included when determining the equipment efficiency. | |
4. Motors in the airstream within fan-coils and terminal units that operate only when providing heating to the space served. | |
5. Fan motors that are not covered by Tables C405.8(1) through C405.8(4) and are used to power heat recovery ventilators, energy recovery ventilators, or local exhaust fans in Group R subject to the efficacy requirements of Section C403.8.4. | |
6. Domestic clothes dryer booster fans, range hood exhaust fans, and domestic range booster fans that operate intermittently. | |
7. Radon and contaminated soil exhaust fans. | |
8. Group R heat recovery ventilator and energy recovery ventilator fans that are less than 400 cfm. |
Motor horsepower (Standard kilowatt equivalent) | Nominal full-load efficiency (%) as of June 1, 2016 | |||||||
2 pole | 4 pole | 6 pole | 8 pole | |||||
Enclosed | Open | Enclosed | Open | Enclosed | Open | Enclosed | Open | |
1 (0.75) | 77.0 | 77.0 | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
1.5 (1.1) | 84.0 | 84.0 | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.5 |
2 (1.5) | 85.5 | 85.5 | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
3 (2.2) | 86.5 | 85.5 | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
5 (3.7) | 88.5 | 86.5 | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
7.5 (5.5) | 89.5 | 88.5 | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
10 (7.5) | 90.2 | 89.5 | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
15 (11) | 91.0 | 90.2 | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
20 (15) | 91.0 | 91.0 | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
25 (18.5) | 91.7 | 91.7 | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
30 (22) | 91.7 | 91.7 | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
40 (30) | 92.4 | 92.4 | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
50 (37) | 93.0 | 93.0 | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
60 (45) | 93.6 | 93.6 | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
75 (55) | 93.6 | 93.6 | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
100 (75) | 94.1 | 93.6 | 95.4 | 95.4 | 95.0 | 95.0 | 93.6 | 94.1 |
125 (90) | 95.0 | 94.1 | 95.4 | 95.4 | 95.0 | 95.0 | 94.1 | 94.1 |
150 (110) | 95.0 | 94.1 | 95.8 | 95.8 | 95.8 | 95.4 | 94.1 | 94.1 |
200 (150) | 95.4 | 95.0 | 96.2 | 95.8 | 95.8 | 95.4 | 94.5 | 94.1 |
250 (186) | 95.8 | 95.0 | 96.2 | 95.8 | 95.8 | 95.8 | 95.0 | 95.0 |
300 (224) | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
350 (261) | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
400 (298) | 95.8 | 95.8 | 96.2 | 95.8 | ||||
450 (336) | 95.8 | 96.2 | 96.2 | 96.2 | ||||
500 (373) | 95.8 | 96.2 | 96.2 | 96.2 |
a | Nominal efficiencies shall be established in accordance with DOE 10 C.F.R. 431. |
b | For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in this table, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows: |
1. A horsepower at or above the midpoint between the two consecutive horsepowers shall be rounded up to the higher of the two horsepowers. | |
2. A horsepower below the midpoint between the two consecutive horsepowers shall be rounded down to the lower of the two horsepowers. | |
3. A kilowatt rating shall be directly converted from kilowatts to horsepower using the formula 1 kW = (1/0.746) horsepower. The conversion should be calculated to three significant decimal places, and the resulting horsepower shall be rounded in accordance with 1 or 2, whichever applies. |
Motor horsepower (Standard kilowatt equivalent) | Nominal full-load efficiency (%) as of June 1, 2016 | |||||
4 pole | 6 pole | 8 pole | ||||
Enclosed | Open | Enclosed | Open | Enclosed | Open | |
1 (0.75) | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
1.5 (1.1) | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.5 |
2 (1.5) | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
3 (2.2) | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
5 (3.7) | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
7.5 (5.5) | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
10 (7.5) | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
15 (11) | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
20 (15) | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
25 (18.5) | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
30 (22) | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
40 (30) | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
50 (37) | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
60 (45) | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
75 (55) | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
100 (75) | 95.4 | 95.4 | 95.0 | 95.0 | 93.6 | 94.1 |
125 (90) | 95.4 | 95.4 | 95.0 | 95.0 | 94.1 | 94.1 |
150 (110) | 95.8 | 95.8 | 95.8 | 95.4 | 94.1 | 94.1 |
200 (150) | 96.2 | 95.8 | 95.8 | 95.4 | 94.5 | 94.1 |
NR - No requirement. | |
a | Nominal efficiencies shall be established in accordance with DOE 10 C.F.R. 431. |
b | For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in this table, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows: |
1. A horsepower at or above the midpoint between the two consecutive horsepowers shall be rounded up to the higher of the two horsepowers. | |
2. A horsepower below the midpoint between the two consecutive horsepowers shall be rounded down to the lower of the two horsepowers. | |
3. A kilowatt rating shall be directly converted from kilowatts to horsepower using the formula 1 kW = (1/0.746) horsepower. The conversion should be calculated to three significant decimal places, and the resulting horsepower shall be rounded in accordance with 1 or 2, whichever applies. |
OPEN MOTORS | |||
NUMBER OF POLES ==˃ | 2 | 4 | 6 |
SYNCHRONOUS SPEED (RPM) ==˃ | 3600 | 1800 | 1200 |
MOTOR HORSEPOWER ▼ | |||
0.25 | 65.6 | 69.5 | 67.5 |
0.33 | 69.5 | 73.4 | 71.4 |
0.50 | 73.4 | 78.2 | 75.3 |
0.75 | 76.8 | 81.1 | 81.7 |
1 | 77.0 | 83.5 | 82.5 |
1.5 | 84.0 | 86.5 | 83.8 |
2 | 85.5 | 86.5 | N/A |
3 | 85.5 | 86.9 | N/A |
a Average full load efficiencies shall be established in accordance with 10 C.F.R. 431. |
OPEN MOTORS | |||
NUMBER OF POLES ==˃ | 2 | 4 | 6 |
SYNCHRONOUS SPEED (RPM) ==˃ | 3600 | 1800 | 1200 |
MOTOR HORSEPOWER ▼ | |||
0.25 | 66.6 | 68.5 | 62.2 |
0.33 | 70.5 | 72.4 | 66.6 |
0.50 | 72.4 | 76.2 | 76.2 |
0.75 | 76.2 | 81.8 | 80.2 |
1 | 80.4 | 82.6 | 81.1 |
1.5 | 81.5 | 83.8 | N/A |
2 | 82.9 | 84.5 | N/A |
3 | 84.1 | N/A | N/A |
a Average full load efficiencies shall be established in accordance with 10 C.F.R. 431. |
EXCEPTION: | The standards in this section shall not apply to the following exempt electric motors. |
1. Air-over electric motors. | |
2. Components sets of an electric motor. | |
3. Liquid-cooled electric motors. | |
4. Submersible electric motors. | |
5. Inverter-only electric motors. |
EXCEPTIONS: | 1. Motors that are an integral part of specialized process equipment. |
2. Where the motor is integral to a listed piece of equipment for which no complying motor has been approved. | |
3. Motors used as a component of the equipment meeting the minimum efficiency requirements of Section C403.3.2 and Tables C403.3.2(1) through C403.3.2(16) provided that the motor input is included when determining the equipment efficiency. | |
4. Motors in the airstream within fan-coils and terminal units that operate only when providing heating to the space served. | |
5. Fan motors that are not covered by Tables C405.8(1) through C405.8(4) and are used to power heat recovery ventilators, energy recovery ventilators, or local exhaust fans in Group R subject to the efficacy requirements of Section C403.8.4. | |
6. Domestic clothes dryer booster fans, range hood exhaust fans, and domestic range booster fans that operate intermittently. | |
7. Radon and contaminated soil exhaust fans. | |
8. Group R heat recovery ventilator and energy recovery ventilator fans that are less than 400 cfm. |
Motor horsepower (Standard kilowatt equivalent) | Nominal full-load efficiency (%) as of June 1, 2016 | |||||||
2 pole | 4 pole | 6 pole | 8 pole | |||||
Enclosed | Open | Enclosed | Open | Enclosed | Open | Enclosed | Open | |
1 (0.75) | 77.0 | 77.0 | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
1.5 (1.1) | 84.0 | 84.0 | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.5 |
2 (1.5) | 85.5 | 85.5 | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
3 (2.2) | 86.5 | 85.5 | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
5 (3.7) | 88.5 | 86.5 | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
7.5 (5.5) | 89.5 | 88.5 | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
10 (7.5) | 90.2 | 89.5 | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
15 (11) | 91.0 | 90.2 | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
20 (15) | 91.0 | 91.0 | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
25 (18.5) | 91.7 | 91.7 | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
30 (22) | 91.7 | 91.7 | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
40 (30) | 92.4 | 92.4 | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
50 (37) | 93.0 | 93.0 | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
60 (45) | 93.6 | 93.6 | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
75 (55) | 93.6 | 93.6 | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
100 (75) | 94.1 | 93.6 | 95.4 | 95.4 | 95.0 | 95.0 | 93.6 | 94.1 |
125 (90) | 95.0 | 94.1 | 95.4 | 95.4 | 95.0 | 95.0 | 94.1 | 94.1 |
150 (110) | 95.0 | 94.1 | 95.8 | 95.8 | 95.8 | 95.4 | 94.1 | 94.1 |
200 (150) | 95.4 | 95.0 | 96.2 | 95.8 | 95.8 | 95.4 | 94.5 | 94.1 |
250 (186) | 95.8 | 95.0 | 96.2 | 95.8 | 95.8 | 95.8 | 95.0 | 95.0 |
300 (224) | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
350 (261) | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
400 (298) | 95.8 | 95.8 | 96.2 | 95.8 | ||||
450 (336) | 95.8 | 96.2 | 96.2 | 96.2 | ||||
500 (373) | 95.8 | 96.2 | 96.2 | 96.2 |
a | Nominal efficiencies shall be established in accordance with DOE 10 C.F.R. 431. |
b | For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in this table, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows: |
1. A horsepower at or above the midpoint between the two consecutive horsepowers shall be rounded up to the higher of the two horsepowers. | |
2. A horsepower below the midpoint between the two consecutive horsepowers shall be rounded down to the lower of the two horsepowers. | |
3. A kilowatt rating shall be directly converted from kilowatts to horsepower using the formula 1 kW = (1/0.746) horsepower. The conversion should be calculated to three significant decimal places, and the resulting horsepower shall be rounded in accordance with 1 or 2, whichever applies. |
Motor horsepower (Standard kilowatt equivalent) | Nominal full-load efficiency (%) as of June 1, 2016 | |||||
4 pole | 6 pole | 8 pole | ||||
Enclosed | Open | Enclosed | Open | Enclosed | Open | |
1 (0.75) | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
1.5 (1.1) | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.5 |
2 (1.5) | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
3 (2.2) | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
5 (3.7) | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
7.5 (5.5) | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
10 (7.5) | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
15 (11) | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
20 (15) | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
25 (18.5) | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
30 (22) | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
40 (30) | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
50 (37) | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
60 (45) | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
75 (55) | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
100 (75) | 95.4 | 95.4 | 95.0 | 95.0 | 93.6 | 94.1 |
125 (90) | 95.4 | 95.4 | 95.0 | 95.0 | 94.1 | 94.1 |
150 (110) | 95.8 | 95.8 | 95.8 | 95.4 | 94.1 | 94.1 |
200 (150) | 96.2 | 95.8 | 95.8 | 95.4 | 94.5 | 94.1 |
NR - No requirement. | |
a | Nominal efficiencies shall be established in accordance with DOE 10 C.F.R. 431. |
b | For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in this table, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows: |
1. A horsepower at or above the midpoint between the two consecutive horsepowers shall be rounded up to the higher of the two horsepowers. | |
2. A horsepower below the midpoint between the two consecutive horsepowers shall be rounded down to the lower of the two horsepowers. | |
3. A kilowatt rating shall be directly converted from kilowatts to horsepower using the formula 1 kW = (1/0.746) horsepower. The conversion should be calculated to three significant decimal places, and the resulting horsepower shall be rounded in accordance with 1 or 2, whichever applies. |
OPEN MOTORS | |||
NUMBER OF POLES ==˃ | 2 | 4 | 6 |
SYNCHRONOUS SPEED (RPM) ==˃ | 3600 | 1800 | 1200 |
MOTOR HORSEPOWER ▼ | |||
0.25 | 65.6 | 69.5 | 67.5 |
0.33 | 69.5 | 73.4 | 71.4 |
0.50 | 73.4 | 78.2 | 75.3 |
0.75 | 76.8 | 81.1 | 81.7 |
1 | 77.0 | 83.5 | 82.5 |
1.5 | 84.0 | 86.5 | 83.8 |
2 | 85.5 | 86.5 | N/A |
3 | 85.5 | 86.9 | N/A |
a Average full load efficiencies shall be established in accordance with 10 C.F.R. 431. |
OPEN MOTORS | |||
NUMBER OF POLES ==˃ | 2 | 4 | 6 |
SYNCHRONOUS SPEED (RPM) ==˃ | 3600 | 1800 | 1200 |
MOTOR HORSEPOWER ▼ | |||
0.25 | 66.6 | 68.5 | 62.2 |
0.33 | 70.5 | 72.4 | 66.6 |
0.50 | 72.4 | 76.2 | 76.2 |
0.75 | 76.2 | 81.8 | 80.2 |
1 | 80.4 | 82.6 | 81.1 |
1.5 | 81.5 | 83.8 | N/A |
2 | 82.9 | 84.5 | N/A |
3 | 84.1 | N/A | N/A |
a Average full load efficiencies shall be established in accordance with 10 C.F.R. 431. |