Where: | |||
AECRRa | = | Section C406.2.5 achieved energy credits for this project as calculated in accordance with Equation 4-17, limited to 50 percent of the required credits in Section C406.1. | |
RRt | = | Actual total rating of on-site and off-site renewable energy systems (W) for each type of renewable energy source in Table C411.2.1. | |
RRr | = | Rating of renewable energy systems required by Section C411.1, other sections in this code, or used to qualify for exceptions in this code (W). | |
RRb | = | 0.1 W/square foot (1.08 W/m2) | |
PGFA | = | Project gross floor area, square feet (m2). | |
AEC0.1 | = | Section C406.2.5 base credits from Table C406.2. | |
REF | = | Renewable Energy Factor from Table C411.2.1. |
Informative Note: | On-site renewable energy may include thermal service water heating or pool water heating, in which case ratings in Btu/h can be converted to W where W = Btu/h / 3.413. |