EXCEPTION: | Lighting control systems are exempt from the commissioning process in buildings where: |
| 1. The total installed lighting load is less than 20 kW; and |
| 2. The lighting load controlled by occupancy sensors or automatic daylighting controls is less than 10 kW. |
C408.4.1 System testing. Functional performance testing shall demonstrate that occupant sensors, time switches, manual overrides, night sweep-off, daylight responsive control, and controlled receptacles are installed and operate in accordance with approved construction documents. Testing shall include the sequence of operation and be conducted under the following conditions:
1. Normal operation;
2. Redundant or automatic back-up mode;
3. Performance of alarms; and
4. Mode of operation upon a loss of power and restoration of power.