Cavity Insulation | ||||||||
Metal Framing | R-Value of Foam Board Insulation | Z-furring Attachment | R-0 | R-11 | R-13 | R-15 | R-19 | R-21 |
16" o.c. | R-0 (none) | Horizontal | 0.352 | 0.132 | 0.124 | 0.118 | 0.109 | 0.106 |
R-5 | Horizontal | 0.155 | 0.089 | 0.086 | 0.083 | 0.078 | 0.077 | |
R-7.5 | Horizontal | 0.128 | 0.080 | 0.077 | 0.074 | 0.071 | 0.069 | |
R-10 | Horizontal | 0.110 | 0.072 | 0.070 | 0.068 | 0.065 | 0.064 | |
R-12.5 | Horizontal | 0.099 | 0.068 | 0.065 | 0.064 | 0.061 | 0.060 | |
R-15 | Horizontal | 0.091 | 0.064 | 0.062 | 0.060 | 0.058 | 0.057 | |
R-17.5 | Horizontal | 0.084 | 0.060 | 0.058 | 0.057 | 0.055 | 0.054 | |
R-20 | Horizontal | 0.078 | 0.057 | 0.056 | 0.054 | 0.052 | 0.052 | |
R-22.5 | Horizontal | 0.074 | 0.055 | 0.054 | 0.052 | 0.051 | 0.050 | |
R-25 | Horizontal | 0.071 | 0.053 | 0.052 | 0.051 | 0.049 | 0.048 | |
R-0 (none) | Vertical | 0.352 | 0.132 | 0.124 | 0.118 | 0.109 | 0.106 | |
R-5 | Vertical | 0.165 | 0.093 | 0.089 | 0.086 | 0.081 | 0.079 | |
R-7.5 | Vertical | 0.142 | 0.085 | 0.081 | 0.079 | 0.075 | 0.073 | |
R-10 | Vertical | 0.126 | 0.079 | 0.076 | 0.074 | 0.070 | 0.069 | |
R-12.5 | Vertical | 0.115 | 0.074 | 0.072 | 0.070 | 0.066 | 0.065 | |
R-15 | Vertical | 0.107 | 0.071 | 0.069 | 0.067 | 0.064 | 0.063 | |
R-17.5 | Vertical | 0.100 | 0.068 | 0.065 | 0.064 | 0.061 | 0.060 | |
R-20 | Vertical | 0.094 | 0.065 | 0.063 | 0.061 | 0.059 | 0.058 | |
R-22.5 | Vertical | 0.090 | 0.063 | 0.061 | 0.060 | 0.057 | 0.056 | |
R-25 | Vertical | 0.086 | 0.061 | 0.059 | 0.058 | 0.056 | 0.055 | |
24" o.c. | R-0 (none) | Horizontal | 0.338 | 0.116 | 0.108 | 0.102 | 0.094 | 0.090 |
R-5 | Horizontal | 0.152 | 0.082 | 0.078 | 0.074 | 0.070 | 0.068 | |
R-7.5 | Horizontal | 0.126 | 0.074 | 0.070 | 0.068 | 0.064 | 0.062 | |
R-10 | Horizontal | 0.109 | 0.067 | 0.065 | 0.062 | 0.059 | 0.058 | |
R-12.5 | Horizontal | 0.098 | 0.063 | 0.061 | 0.059 | 0.056 | 0.055 | |
R-15 | Horizontal | 0.090 | 0.060 | 0.058 | 0.056 | 0.053 | 0.052 | |
R-17.5 | Horizontal | 0.083 | 0.057 | 0.055 | 0.053 | 0.051 | 0.050 | |
R-20 | Horizontal | 0.078 | 0.054 | 0.052 | 0.051 | 0.049 | 0.048 | |
R-22.5 | Horizontal | 0.074 | 0.052 | 0.050 | 0.049 | 0.047 | 0.046 | |
R-25 | Horizontal | 0.070 | 0.050 | 0.049 | 0.047 | 0.046 | 0.045 | |
R-0 (none) | Vertical | 0.338 | 0.116 | 0.108 | 0.102 | 0.094 | 0.090 | |
R-5 | Vertical | 0.162 | 0.084 | 0.080 | 0.077 | 0.072 | 0.070 | |
R-7.5 | Vertical | 0.140 | 0.078 | 0.074 | 0.071 | 0.067 | 0.065 | |
R-10 | Vertical | 0.124 | 0.073 | 0.070 | 0.067 | 0.063 | 0.062 | |
R-12.5 | Vertical | 0.113 | 0.069 | 0.066 | 0.064 | 0.061 | 0.059 | |
R-15 | Vertical | 0.106 | 0.066 | 0.063 | 0.061 | 0.058 | 0.057 | |
R-17.5 | Vertical | 0.098 | 0.063 | 0.061 | 0.059 | 0.056 | 0.055 | |
R-20 | Vertical | 0.093 | 0.061 | 0.059 | 0.057 | 0.054 | 0.053 | |
R-22.5 | Vertical | 0.089 | 0.059 | 0.057 | 0.055 | 0.053 | 0.051 | |
R-25 | Vertical | 0.085 | 0.057 | 0.055 | 0.054 | 0.051 | 0.050 |
Cavity | Insulation | ||||
Nominal Depth, Inches | Actual Depth, Inches | Nominal R-Value | Effective R-Value | ||
16" O.C. | 24" O.C. | ||||
Air Cavity | any | any | R-0.91 (air) | 0.79 | 0.91 |
4 | 3-1/2 | R-11 | 5.5 | 6.6 | |
4 | 3-1/2 | R-13 | 6.0 | 7.2 | |
Wall | 4 | 3-1/2 | R-15 | 6.4 | 7.8 |
6 | 5-1/2 | R-19 | 7.1 | 8.6 | |
6 | 5-1/2 | R-21 | 7.4 | 9.0 | |
8 | 7-1/4 | R-25 | 7.8 | 9.6 | |
Roof | Insulation is uncompressed | R-11 | 5.5 | 6.1 | |
R-19 | 7.0 | 9.1 | |||
R-30 | 9.3 | 11.4 |
Overall U-Factor for Assembly of Base Wall Plus Continuous Insulation (Uninterrupted by Framing) | ||||||||
Insulation System | Rated R-Value of Insulation | Overall U-Factor for Entire Base Wall Assembly | R-6.5 | R-13 | R-19.5 | R-26 | R-32.5 | R-39 |
Single Layer of Mineral Fiber | ||||||||
None | 1.180 | 0.136 | 0.072 | 0.049 | 0.037 | 0.030 | 0.025 | |
R-10 | 0.186 | 0.084 | 0.054 | 0.040 | 0.032 | 0.026 | 0.023 | |
R-11 | 0.185 | 0.084 | 0.054 | 0.040 | 0.032 | 0.026 | 0.023 | |
R-13 | 0.162 | 0.079 | 0.052 | 0.039 | 0.031 | 0.026 | 0.022 | |
R-16 | 0.155 | 0.077 | 0.051 | 0.039 | 0.031 | 0.026 | 0.022 | |
R-19 | 0.147 | 0.075 | 0.050 | 0.038 | 0.030 | 0.025 | 0.022 |