EXCEPTION: | Exterior walls required to be fire-resistance-rated in accordance with Section 1021 for exterior egress balconies, Section 1023.7 for interior exit stairways and ramps, Section 1024.8 for exit passageways and Section 1027.6 for exterior exit stairways and ramp. |
707.5 Continuity. Fire barriers shall extend from the top of the foundation or floor/ceiling assembly below to the underside of the floor or roof sheathing, slab or deck above and shall be securely attached thereto. Such fire barriers shall be continuous through concealed space, such as the space above a suspended ceiling. Joints and voids at intersections shall comply with Sections 707.8 and 707.9.
EXCEPTIONS: | 1. Shaft enclosures shall be permitted to terminate at a top enclosure complying with Section 713.12. |
| 2. Interior exit stairway and ramp enclosures required by Section 1023 and exit access stairway and ramp enclosures required by Section 1019 shall be permitted to terminate at a top enclosure complying with Section 713.12. |
| 3. An exit passageway enclosure required by Section 1024.3 that does not extend to the underside of the roof sheathing, slab or deck above shall be enclosed at the top with construction of the same fire-resistance rating as required for the exit passageway. |
[Statutory Authority: RCW
19.27.031 and
19.27.074. WSR 20-01-090, § 51-50-07070, filed 12/12/19, effective 7/1/20.]
(Effective July 1, 2023)
Reserved.
[Statutory Authority: RCW
19.27.031 and
19.27.074. WSR 22-13-094, § 51-50-07070, filed 6/14/22, effective 7/1/23; WSR 20-01-090, § 51-50-07070, filed 12/12/19, effective 7/1/20.]