PDFWAC 51-50-10170

Section 1017Exit access travel distance.

Table 1017.2
Exit Access Travel Distancea
Occupancy
Without Sprinkler System (feet)
With Sprinkler System (feet)
A, E, F-1, M, R, S-1
200e
250b
I-1
Not Permitted
250b
B
200
300c
F-Z, S-Z, U
300
400c
H-1
Not Permitted
75d
H-Z
Not Permitted
100d
H-3
Not Permitted
150d
H-4
Not Permitted
175d
H-5
Not Permitted
200c
1-Z, 1-3
Not Permitted
200c
l-4
150
200c
For SI: 1 foot = 304.8 mm.
a
See the following sections for modifications to exit access travel distance requirements:
 
• Section 402.8: For the distance limitation in malls.
 
• Section 407.4: For the distance limitation in Group I-2.
 
• Sections 408.6.1 and 408.8.1: For the distance limitations in Group I-3.
 
• Section 411.2: For the distance limitation in special amusement areas.
 
• Section 412.6: For the distance limitations in aircraft manufacturing facilities.
 
• Section 1006.2.2.2: For the distance limitation in refrigeration machinery rooms.
 
• Section 1006.2.2.3: For the distance limitation in refrigerated rooms and spaces.
 
• Section 1006.3.4: For buildings with one exit.
 
• Section 1017.2.2: For increased distance limitation in Groups F-1 and S-1.
 
• Section 1030.7: For increased limitation in assembly seating.
 
• Section 3103.4: For temporary structures.
 
• Section 3104.9: For pedestrian walkways.
 
• Section 3116: For fixed guideway and passenger rail stations.
b
Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2.
c
Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
d
Group H occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5.1.
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, § 51-50-10170, filed 6/14/22, effective 7/1/23.]